12
Monitoring Functions
The monitoring functions are used to set the properties of digital outputs and relay output.
12.1
Overspeed (Switch Mode = 0)
With parameter setting “Switch Mode” = 0, the frequency is monitored for overspeed.
The function is always active and independent of the direction of rotation. The
switching point for overspeed is always at Frequency = Presel (no matter if with or
without hysteresis).
Relevant Parameters Remark
„Switch Mode
“ = 0
„Pulse Time
“
statically = 0 or pulse duration in x seconds
„Hysteresis
“
hysteresis
„Lock Output“
lock function
„Output Mode“
homogenous or inverse output configuration (affects the Safety Integrity Level
SIL/PL)
„Presel.
.
“
switching point
„Delay
“
„Input Mode “
configuration of the control inputs (affects the safety level SIL/PL)
„ IN Function“
function of the control input
„ IN Config“
switching behaviour (single-channel, two-channel, inverse, homogeneous,
dynamic, static)
Relevant input functions
Remark
Clear lock function, e.g. parameter „IN1 Function“ = 1 … 6
Only when lock function is active
Switchover switching points, e.g. parameter „IN2 Function“ = 13
Only when switchover is active
Example:
With Presel = 1000.0 Hz and Hysteresis = 10 %, frequencies |f|
≥
1000 Hz are detected
as overspeed. The overspeed output will be cleared with frequencies |f| < 900 Hz.
Summary of Contents for SMC1.3
Page 44: ...R60047 0001 Index 2 DE Seite 44 120 8 2 Montage Demontage...
Page 49: ...R60047 0001 Index 2 DE Seite 49 120...
Page 117: ...R60047 0001 Index 2 DE Seite 117 120 20 Zertifikat...
Page 118: ...R60047 0001 Index 2 DE Seite 118 120...
Page 119: ...R60047 0001 Index 2 DE Seite 119 120...
Page 163: ...R60047 0002 Index 2 EN page 43 115 8 2 Mounting Dismounting...
Page 168: ...R60047 0002 Index 2 EN page 48 115...
Page 234: ...R60047 0002 Index 2 EN page 114 115 20 Certificate...