![Kübler SMC1.3 Safety Manual Download Page 180](http://html1.mh-extra.com/html/kubler-0/smc1-3/smc1-3_safety-manual_2008430180.webp)
R60047.0002 - Index 2
EN – page 60 / 115
11.2
Initialization Test
These self-monitoring tests are processed automatically when switching the unit on.
Error code SMCB Error OS6.0 operator software
Instruction
H‘ 0000 0001
ADC Error
Internal error
H‘ 0000 0002
I2C Error
Internal error
H‘ 0000 0004
OTH Error
Check the SMCB power supply or the
encoder supply or internal error
H‘ 0000 0008
SCI Error
Internal error
H‘ 0000 0010
DIO Error
Check the digital outputs for short
circuit resp. other errors or internal
error
H‘ 0000 0020
GPI Error
Check the connections of the digital
inputs and the input configuration
or internal error
H‘ 0000 0040
CAP Error
Internal error
H‘ 0000 0080
SPI Error
Check the connections of the analog
output or internal error
H‘ 0000 0100
QEP Error
Check the separation or disconnection
of the encoder supply at Self-Test
or internal error
H‘ 0000 0200
SCO Error
Check splitter output or internal error
H‘ 0000 0400
CPU Error
Internal error
H‘ 0000 0800
RAM Error
Internal error
H‘ 0000 1000
WDO Error
Internal error
H‘ 0000 2000
EDM Error
Error in EDM Selftest, ceck connected
contactor or relay
H‘ 0000 4000
FLA Error
Internal error
H‘ 0000 8000
PRG Error
Internal error
H‘ 0001 0000
POE Error
Saved error active, error must be erased
before the device is re-connected.*
For all error messages, the following applies:
Switch the unit OFF and ON again.
If the error message continues, please contact the manufacturer of
the unit
.
If a Poe error is triggered during the initialization phase, the activated
Power-up error will also trigger a run time error, regardless the cause
is still there. The deletion sequence can be found in the parameter
description under the parameter "Power-up error”.
Summary of Contents for SMC1.3
Page 44: ...R60047 0001 Index 2 DE Seite 44 120 8 2 Montage Demontage...
Page 49: ...R60047 0001 Index 2 DE Seite 49 120...
Page 117: ...R60047 0001 Index 2 DE Seite 117 120 20 Zertifikat...
Page 118: ...R60047 0001 Index 2 DE Seite 118 120...
Page 119: ...R60047 0001 Index 2 DE Seite 119 120...
Page 163: ...R60047 0002 Index 2 EN page 43 115 8 2 Mounting Dismounting...
Page 168: ...R60047 0002 Index 2 EN page 48 115...
Page 234: ...R60047 0002 Index 2 EN page 114 115 20 Certificate...