![Kübler SMC1.3 Safety Manual Download Page 179](http://html1.mh-extra.com/html/kubler-0/smc1-3/smc1-3_safety-manual_2008430179.webp)
R60047.0002 - Index 2
EN – page 59 / 115
11 Error Detection
In order to ensure a maximum of operational safety and reliability, the Safety Monitors
are equipped with several and profound monitoring-functions. This monitoring allows
immediate recognition and messaging of possible failures and malfunctions.
In case of errors:
•
The relay contact switches to its open (safety) condition
(interruption of the safety circuit)
•
The analog output sets to 0 mA
(which is out of the regular operating range of 4 … 20 mA)
•
All control outputs are set to LOW.
No more inversion between OUT and /OUT
(Attention in case of homogenous configuration!)
•
Encoder splitter output does not provide any incremental signals (tri-
state with pull-down termination)
The following types of error recognition are distinguished:
•
Initialization Test Error
•
Runtime Test Error
Both error types are described in detail on the following pages.
11.1
Error Representation
Error Representation
Reference
Front LED’s
Yellow LED lights continuously
SMCB Operator Unit
The bottom line displays the error when
the SMCB is not in the programming mode
Operator surface OS6.0
Initialization Test = red (State field)
Runtime Test = red (State field)
Summary of Contents for SMC1.3
Page 44: ...R60047 0001 Index 2 DE Seite 44 120 8 2 Montage Demontage...
Page 49: ...R60047 0001 Index 2 DE Seite 49 120...
Page 117: ...R60047 0001 Index 2 DE Seite 117 120 20 Zertifikat...
Page 118: ...R60047 0001 Index 2 DE Seite 118 120...
Page 119: ...R60047 0001 Index 2 DE Seite 119 120...
Page 163: ...R60047 0002 Index 2 EN page 43 115 8 2 Mounting Dismounting...
Page 168: ...R60047 0002 Index 2 EN page 48 115...
Page 234: ...R60047 0002 Index 2 EN page 114 115 20 Certificate...