R60047.0002 - Index 2
EN – page 57 / 115
9.15
Producing an Error
After setting of all relevant parameters an error can be produced for testing purpose.
This conduces to force all outputs of the device into the error state and to check
function and behavior of the follower units.
•
Set the device in error state:
Set parameter „Error Stimulation“ to 0 and activate
•
Delete/Reset Error state:
Set parameter „Error Stimulation“ to 2 and activate
•
Set the unit back to normal operation:
Set parameter „Error Stimulation“ to 1 again and activate
While in Error State, the safety monitor acts as follows:
•
The analog output signal is set to 0 mA
•
The relay contact is open (both contacts)
•
The control outputs are in LOW state
•
The traces of the encoder splitter output are in LOW state.
It is important to check for proper detection of these error indications on site of the
target units connected to the monitor.