5 Commissioning and Operation
Kübler Group
46 - EN
Manual IO-Link interface - R67071.0002 - 02
• Restoring the factory setting
– the scaling parameters are reset.
• Device reset
– the change is taken into account after device restart. The device logs in with the new
device ID and outputs the process data according to the selected profile.
NOTICE
Profile change
Process data length is different for profiles "Standard Profil" and
"Smart Sensor Profil", requiring separate device IDs and therefore
IODDs. In the event of a profile change, the suitable IODD must be
selected subsequently.
If the data storage mechanism is active in the master, it must be dis-
abled before changing the profile, to avoid an error message due to a
different device ID when restarting the device. After the change, the
functionality can be enabled again.
5.4.17 ISDU 230 - Pin2 Configuration
This parameter allows configuring the use of Pin2 of the IO-Link interface.
Value
Description
0
Pin2 is not used.
>0
Not permitted. Reserved for future use.
5.5 Functionalities
5.5.1 Velocity Events
• Parameter "Velocity limit control" activates the velocity events. In addition, the following set-
tings can be made:
• Setting of the velocity events by the two parameters "Velocity lower limit" and "Velocity upper
limit".
• Hysteresis adjustable by parameter "Velocity hysteresis".
Conditions:
• Velocity upper limit ≤ maximum velocity in the corresponding unit.
• Velocity lower limit ≥ minimum velocity in the corresponding unit.
The setting of the velocity events always is performed in the set unit,
parameter "Velocity format". The validity ranges of the values always depend on the selected
unit.
The following limits apply: