Oil/air cooler
Series OPC
Operating/Assembly instructions
KTR-N
Sheet:
Edition:
43211 EN
9 of 20
5
Please observe protection
note ISO 16016.
Drawn:
2019-10-23 Pz/Str
Replacing:
KTR-N dated 2017-01-02
Verified:
2019-11-04 Pz
Replaced by:
Illustration 7: Oil/air cooler; example: OPC200 to 400
Illustration 8: Oil/air cooler; example: OPC500 to 1000
In order to achieve the optimum cooling capacity the distance to the nearest wall should not fall below the height
of the cooling element (dimension A), since only in this way a proper air supply is ensured (see illustration 7 and
8).
The height of installation should not exceed the figure ≤ 1000 m.
!
Return flow of heated air as well as assembly of the cooler core in front of heat sources
should be avoided.
!
The engines have to be protected from direct solar radiation.
An unfavourable place of installation may increase the noise level by reflection of sound.
4
Assembly
4.2 Place of installation