Oil/air cooler
Series OPC
Operating/Assembly instructions
KTR-N
Sheet:
Edition:
43211 EN
18 of 20
5
Please observe protection
note ISO 16016.
Drawn:
2019-10-23 Pz/Str
Replacing:
KTR-N dated 2017-01-02
Verified:
2019-11-04 Pz
Replaced by:
•
The oil/air cooler may be set up horizontally only and must be screwed to the base through all fastening holes.
•
It has to be assured that the suction distances and discharge distances (distance A, as described in place of
arrangement) are observed.
•
The cooler core must not be sealed by foreign substances.
•
Inspect distances between fan and protective grid.
The minimum gap width between rotating components and non-mobile components is at
least 1 % of the relevant contact diameter (see table 4).
Table 4
Size of cooler
Fan Ø
[mm]
Minimum gap to be observed
OPC200
280
> 2.8 mm (corresponds to 1 %)
OPC300 to OPC500
380
> 3.8 mm (corresponds to 1 %)
OPC600 to OPC700
520
> 5.2 mm (corresponds to 1 %)
OPC800
630
> 6.3 mm (corresponds to 1 %)
OPC850
750
> 7.5 mm (corresponds to 1 %)
OPC900 to OPC1000
900
> 9.0 mm (corresponds to 1 %)
•
With the trial run make sure that the permissible motor temperature is not exceeded.
The temperature classes of cooler and motor specified in the type label have to be definitely observed.
Only those accessories certified by ATEX and complying with the temperature class (example: thermal switch,
etc.) may be mounted to the oil/air cooler.
Any modifications on the design of the oil/air cooler intended for the use in potentially
explosive atmospheres are not permissible.
!
The customer bears the sole responsibility for all machining processes performed
subsequently by the customer. KTR does not assume any warranty claims.
8
Enclosure A
Advice and instructions regarding the use in
potentially explosive atmospheres
8.3 Start-up for the use in
potentially explosive atmospheres
8.4 Permissible accessories for the use in
potentially explosive atmospheres