Installation and operating manual
KT-Elektronik
6.3 Temperature monitoring
If the collector temperature deviates more than 50 K from the turn-on threshold with
running collector pump for a period of 30 minutes, the error message "Err 6" is generated
(temperature monitoring alarm).
It is assumed that the heat carrier medium does not circulate any more. Possible
reasons may be:
Air in the system
Defective pump or pump is stuck
Functions
FS
Configuration
Temperature monitoring
0
CO5 -> F19 - 1
6.4 Error status register
The error status register is used to report controller or system failures. In modem
operating mode with error reporting function, each change of error status (error
detection/error correction) triggers a dial up connection to the building master control
system/station (BCS) to report the status change. The errors that should affect the error
status register can be set after having entered the access code 0025.
The default factory setting „465“ causes that only the error messages in bold in the
following table affect the error status register.
Error message Description
Decimal value
FS Example
Err 1
Sensor failure
1
1
1
Err 2
-
2
Err 3
-
4
Err 4
-
8
Err 5
-
16
16
Err 6
Temperature monitoring alarm
32
32
Err 7
Unauthorized access
64
64
Err 8
-
128
128
Err 9
-
256
256
Sum
Sum
Factory default setting, access code 0025 =
465
Example: Error status register if sensor failure and alarm =
33
26