17 / 21
Maintenance
BNA…EX bypass level indicators require no maintenance if used as intended. However, they must
be subjected to a visual inspection within the framework of regular general inspections and must
be included in container pressure tests.
Important!
The float is designed for the medium density level indicated on the type plate. Use in
fluids with a different specific gravity results in measurement deviations.
The medium to be monitored should not contain any soiling or coarse particles.
It should also not tend to crystallize out.
The magnetic roller display and attached magnetic switch must be positioned and set using the
enclosed float prior to installation.
The bypass level indicator must not be installed near strong electromagnetic fields (at least 1 m
away).
Correct functioning of the bypass level indicator can only be guaranteed if original KSR Kuebler
accessories and replacement parts are used.
Error Search
The following table lists the most frequent causes of error and the necessary
countermeasures
Error
Cause
Countermeasure
KSR Magnetic Level
Indicators / Gauges
BNA...EX cannot be
attached at the
intended position on
the container
Thread or flange dimensions
of KSR Magnetic Level
Indicators / Gauges
BNA...EX do not agree
Reworking of container
Send back to factory
Thread of mounting plug on
container defective
Reworking of the thread or
replacement of the
attachment muff
Bolt threading on the Level
Sensors KSR Magnetic
Level Indicators / Gauges
BNA...EX defective
Send back to factory
The axial centre distances of
the container and bypass
level indicator do not agree
Reworking of container
Send back to factory
The process connections
are not installed parallel
Reworking of container
Please give us a call in case of any difficulties. We will do everything we can to
provide you with the required advice and help.