Maintenance 

BNA…EX bypass level indicators require no maintenance if used as intended. However, they must 
be subjected to a visual inspection within the framework of regular general inspections and must 
be included in container pressure tests. 

 

 

Important! 

The  float  is  designed  for  the  medium  density  level  indicated  on  the  type  plate.  Use  in 
fluids with a different specific gravity results in measurement deviations. 

The medium to be monitored should not contain any soiling or coarse particles. 
It should also not tend to crystallize out. 
The  magnetic  roller  display  and  attached  magnetic  switch  must  be  positioned  and  set  using  the 
enclosed float prior to installation. 
The  bypass  level  indicator  must  not  be  installed  near  strong  electromagnetic  fields  (at  least  1  m 
away). 
Correct  functioning  of  the  bypass  level  indicator  can  only  be  guaranteed  if  original  KSR  Kuebler 
accessories and replacement parts are used. 
 

Error Search 

 

The following table lists the most frequent causes of error and the necessary 
countermeasures 

 

Error 

Cause 

Countermeasure 

KSR Magnetic Level 
Indicators / Gauges 
BNA...EX cannot be 
attached at the 
intended position on 
the container 

Thread or flange dimensions 
of KSR Magnetic Level 
Indicators / Gauges 
BNA...EX do not agree 

Reworking of container 

Send back to factory 

Thread of mounting plug on 
container defective 

Reworking of the thread or 
replacement of the 
attachment muff 

Bolt threading on the Level 
Sensors KSR Magnetic 
Level Indicators / Gauges 
BNA...EX defective 

Send back to factory 

The axial centre distances of 
the container and bypass 
level indicator do not agree 

Reworking of container 

Send back to factory 

The process connections 
are not installed parallel 

Reworking of container 

 

Please give us a call in case of any difficulties. We will do everything we can to 
provide you with the required advice and help. 

 

Summary of Contents for BNA EX Series

Page 1: ...Rev 7 16 03 2015 Manual de Instru es e de Montagem KEMA 02ATEX2106 X Por favor guarde esta informa o para uso futuro Please retain for future usage BNA EX Montage und Betriebsanleitung Mounting and op...

Page 2: ......

Page 3: ...OI_BNA_EX_pt_en doc...

Page 4: ...OI_BNA_EX_pt_en doc...

Page 5: ...OI_BNA_EX_pt_en doc...

Page 6: ...OI_BNA_EX_pt_en doc...

Page 7: ...OI_BNA_EX_pt_en doc...

Page 8: ...ratura 11 Dados de press o 11 English 12 Symbol legend 12 Safety information 12 Danger 13 Application and field of use 13 Attention 13 Removal of transport packaging and transport safety devices 13 In...

Page 9: ...vor leia estas Instru es antes de instalar e utilizar indicadores de n vel tipo Bypass BNA EX Este Manual destina se a profissionais que realizam a montagem a instala o e a configura o As normas de se...

Page 10: ...rui o dos indicadores de n vel tipo Bypass e causar danos pessais e materiais Todos os materiais do tubo Bypass e do flutuador devem ser resistentes ao meio a ser monitorado Os valores m ximos indicad...

Page 11: ...favor consulte os valores de torque dos parafusos Deve se aplicar selagens apropriadas Verificar se o material de selagem contra o meio e os seus vapores a temperatura e cargas de press o previstas s...

Page 12: ...segundo os folhetos AD Para eliminar o risco de explos o devido ao aquecimento aplicam se os seguintes requisitos para a opera o de aquecimento e para a transfer ncia de calor 1 A temperatura de trans...

Page 13: ...transdutores MG A descri o que se segue pretende ser apenas um guia para uma op o de montagem em determinado local Por favor leia tamb m as instru es de instala o e funcionamento de equipamento desmo...

Page 14: ...mplo de montagem MNAV montagem do interruptor magn tico em barra de reten o A montagem deste interruptor magn tico feita em uma barra de reten o separada 1 Retirar a barra de reten o 1 desapertando os...

Page 15: ...l tipo Bypass s pode ser garantida com a utiliza o de acess rios originais KSR Kuebler e pe as de reposi o Solu o de problemas Na tabela a seguir est o listados os problemas mais comuns e as contramed...

Page 16: ...cos a o inoxid vel 180 C temperatura m dia SG com escala alum nio gravado VSG com escala a o inoxid vel gravado especifica o somente se a op o estiver dispon vel S se pode instalar interruptores magn...

Page 17: ...9 21 OI_BNA_EX_pt_en doc extremidade da solda S S 3 4 Tipo b sico BNA...

Page 18: ...sico Flutuador cilindro Execu o sem gr nulos Tipo b sico Code 1 Code 2 Code 3 Code 4 Code 5 Code 6 Code 7 Z V S 250 16 60 1000 Code 7 Sistema magn tico Code 6 Densidade em kg m Code 5 Temperatura em...

Page 19: ...m xima Temperatura ambiente m xima no dispositivo de avalia o MRA MRAN MNAV MRK MNKV T1 320 C 320 C 50 80 C A temperatura ambiente m xima do dispositivo de avalia o deve ser respeitada A mesma n o de...

Page 20: ...G or MG Safety information Read these instructions before installing the BNA EX and putting them into operation These instructions are intended for the specialists in charge of mounting installation a...

Page 21: ...vels may result in malfunction or destruction of the bypass level indicator as well as to personal injury and property damage All of the materials used in the bypass chamber and float must be resistan...

Page 22: ...nce with any Special Conditions stipulated in such laws or regulations is of particular importance Please comply with the maximum torque ratings of the bolts screws used when tightening them down Use...

Page 23: ...ch this construction is exposed To eliminate the risk of explosion caused by the heating system the following requirements apply to operation of the heating system and the heat carrying medium 1 The t...

Page 24: ...evel Sensor MG The description provided here must be considered as being a means of orientation for the mounting on possibility provided by location specific conditions Please also refer to the assemb...

Page 25: ...witch must then be mounted the other way around with the type plate upside down Example of installation MNAV mounting of magnetic switch on a retainer rod This magnetic switch is attached to a retaine...

Page 26: ...level indicator can only be guaranteed if original KSR Kuebler accessories and replacement parts are used Error Search The following table lists the most frequent causes of error and the necessary cou...

Page 27: ...ature MNKV Magnetic Roller Indicator Edelstahl 180 C ambient temperature SG with Scale Aluminium engraved VSG with Scale Stainless steel engraved Only specification if option is available Only BGUV ma...

Page 28: ...Titanium max 16 bar Basic type Cylindrical floats Design without beads Basic type Code 1 Code 2 Code 3 Code 4 Code 5 Code 6 Code 7 Z V S 250 16 60 1000 Code 7 magnet system Code 6 density in kg m Code...

Page 29: ...processing and display equipment MRA MRAN MNAV MRK MNKV T1 320 C 320 C 50 80 C Avoid temperatures in excess of the maximum ambient temperature allowed for the installed processing and display equipmen...

Page 30: ..._en doc 22 21 KSR KUEBLER AG Adressen KSR KUEBLER Niveau Messtechnik AG Heinrich Kuebler Platz 1 D 69439 Zwingenberg Neckar Tel 49 06263 870 Fax 49 06263 87 99 http www ksr kuebler com e Mail info ksr...

Reviews: