7 Commissioning/shutdown
Ensure that the following requirements are met prior to commissioning:
▪
The pump has been vented and primed with the fluid to be handled.
▪
Flow through the pump is in the design direction specified in order to avoid
generator operation of PumpDrive.
▪
A sudden start-up of the motor or pump set does not result in personal injury or
damage to machinery.
▪
No capacitive loads, for example for reactive current compensation, are
connected to the outputs of the device.
▪
The mains voltage is in the range approved for PumpDrive.
▪
PumpDrive has been properly connected to the power supply. (
▪
All enable and start commands that start PumpDrive are deactivated (digital
input 1 for single-pump operation and digital inputs 1 and 2 for multiple pump
operation).
▪
No voltage is applied to the power supply module of PumpDrive.
▪
PumpDrive or the pump set must not be loaded above the permissible nominal
power.
▪
If PumpDrive is going to be used in multiple pump operation, note (
7.1.3 Page 62) prior to commissioning.
7.1 Pump operation
7.1.1
Single-pump operation
7.1.1.1
Setting motor parameters
Motor-mounted PumpDrive model:
The motor parameters have been set at the factory.
Cabinet-mounted or wall-mounted PumpDrive model:
The factory-set motor parameters must be compared with the data provided on the
motor rating plate and adjusted, if required.
Table 45: Motor parameters
Parameter Description
Possible settings
Reference
to
Factory setting
3-3-2-1
Nominal power
0,55..45 [kW]
Depending on the size
3-3-2-2
Nominal voltage
342..528 [V]
3-3-2-3
Nominal frequency
45..65 [Hz]
3-3-2-4
Nominal motor current
0,1..999 [A]
3-3-2-5
Nominal speed
300..3600 [rpm]
3-3-2-6
Nominal cos phi
0,30 - 0,99
3-3-5-1
Enable/disable thermal motor
protection (PTC)
No Protection
PTC Protection
PTC Protection
3-5-3-4
Output frequency in manual mode
0..100 [100%]
3-11-4-1
0 %
3-6-1-1
Direction of rotation of the motor
Clockwise
Anti-clockwise
Clockwise
3-6-1-2
Lower limit for motor frequency
0..100 [100%]
3-11-4-1
50 %
3-6-1-3
Upper limit for motor frequency
0..100 [100%]
3-11-4-1
100 %
3-11-4-1
Maximum output frequency
1..70 [Hz]
50 Hz
7.1.1.2
Entering the setpoint/setting the setpoint unit
The setpoint can be entered via 5 different sources without this having to be
parameterised beforehand. The setpoint can be specified via: