1 Supplementary Operating Manual
10 of 16
BACnet MS/TP Gateway
Settings for the slave address and the control point are made at the control panel of
the frequency inverter.
Table 5:
Parameters for BACnet MS/TP module
Parameter
Description
Possible settings
Factory setting
3-12-5-1
Device Identification
Device Object-Instance Number
0-4194303
Generated value
3-12-5-2
MS/TP MAC Address
Network address in accordance with MS/TP
frame format
1-254
254
3-12-5-3
Baud Rate
Baud rate of the BACnet slave
▪
9600
▪
19200
▪
38400
▪
57600
▪
115200
38400
3-12-5-4
Pump Number
Unique number of the pump in the multiple pump
system
1-2
1
3-12-5-5
Communication Monitoring Time
If the BACnet module is not in the token cycle of
the MSTP network for a longer period of time, a
broken wire is reported.
0...60 s
20 s
3-12-5-6
Device Name
Device Object-Name Device name for device
identification in the network
Configuration via configuration
tool, maximum of 32 characters
KSB PumpDrive
3-12-5-7
Device Description
Device Object-Description Device description for
device identification in the network
Configuration via configuration
tool, maximum of 32 characters
KSB PumpDrive
3-12-5-8
Installation Location
Device Object-Location Installation location of
BACnet subscriber
Configuration via configuration
tool, maximum of 32 characters
KSB PumpDrive
NOTE
If the field bus is only used for monitoring purposes, the Control Point parameter
(3-6-2)
is set to Local.