1 Supplementary Operating Manual
4 of 28
Profibus module
1 Supplementary Operating Manual
1.1 General
This supplementary operating manual accompanies the installation/operating
manual. All information contained in the installation/operating manual must be
observed.
Table 1:
Relevant operating manuals
Type series
Reference number of the operating/installation
manual
PumpDrive 2
4074.81
1.2 Function
The Profibus field bus module serves to connect PumpDrive 2 to a Profibus network.
A Profibus module is required for monitoring and open-loop or closed-loop control
purposes for each frequency inverter in single-pump configuration or multiple pump
configuration.
Interface
The Profibus module is equipped with a Profibus interface with Profibus DP protocol
in accordance with the "Profile for Intelligent Pumps" version 1.0 specification.
Configuration is done via frequency inverter parameters.
Communication protocol
Profibus DP
Bus terminator
External
Interface
EIA-485 (RS485)
Transmission rate
Automatic, 9600-12 Mbit/s
Device type
Slave
For information on Profibus and downloads for PROFIBUS DP and the "Profile for
Intelligent Pumps" please go to
For further accessories for the Profibus module, such as M12 connectors and
terminating resistors please refer to the type series booklet.
GSD file
The characteristic communication configuration data of the frequency inverter, such
as the number of input signals and output signals, diagnosis messages, etc. are
described in an electronic general station description (GSD) file.
The GSD file can be read by a Profibus configuration tool, which is then used to
configure the Profibus Master. The GSD file is a PROFIBUS DP standard text file,
available for download from the KSB website.
1.3 Field bus module connections
The field bus modules are plug-in modules.
B
A
1
3
4
5
2
Fig. 1:
Field bus module
Summary of Contents for Profibus PumpDrive 2
Page 1: ...Field Bus Module Profibus module PumpDrive 2 Supplementary Operating Manual...
Page 26: ......