7 Operation
46 of 104
mini-Compacta
2317.886/16-EN
Fault message
Priority
Description
Type of message
Acknowledge
ment
Warning
Alarm
A5
5
Power supply failure
Pump sets 1 and 2 stop.
-
✘
Auto
A6
6
Phase error / phase failure
Pump sets 1 and 2 stop.
-
✘
Auto
A7
7
Leakage motor 1 (Amarex N/KRT)
Pump set 1 stops.
-
✘
Manual
A8
8
Leakage motor 2 (Amarex N/KRT)
Pump set 2 stops.
-
✘
Manual
A9
9
High water alert
Pump sets 1 and 2 stop.
-
✘
Auto
A10
10
External alarm
Pump sets 1 and 2 stop
(can be set via the KSB ServiceTool).
-
✘
Auto
A11
11
Sensor fault
No action
-
✘
Auto
A12
12
Incorrect rotary field of mains supply (phase sequence)
No action
✘
-
Auto
A13
13
Undervoltage
(-15 % of nominal voltage 230 V or 400 V)
No action
✘
-
Auto
A14
14
Overvoltage
(+15 % of nominal voltage 230 V or 400 V)
No action
✘
-
Auto
A15
15
Flat battery
No action
✘
-
Auto
A16
16
Service interval system
No action
(deactivated by default; can be set via the KSB ServiceTool).
✘
-
Auto
7.3.4 Displaying the alerts list
The alerts list serves to call up alerts / warnings that have been acknowledged but are
still present.
Table 27:
Displaying the alerts list
Esc
Step 1: Activating the alerts list
ü
Alerts / warnings have been acknowledged but are still present.
(
1. If no measured value parameter is active, press the ESC key.
Repeat if necessary.
Step 2: Navigating
1. Use the arrow keys to select parameter P 2.1.1.
ð
After 1.5 seconds the most recent fault message on the
alerts list is automatically displayed.
ð
If further fault messages are present, the next fault
message will be displayed after another 1.5 seconds.
Esc
Step 3: Leaving the alerts list
1. To leave the alerts list press the ESC key.
ð