Pump Switchgear / Control Systems

LevelControl Control Units

6

LevelControl Basic 2

4041.5/12-EN

Code

Description

100

400

40 A

630

63 A

>63 A available on request

Product benefits

Ample connection space allows straightforward
connection of pumps and sensors

Reliability provided by detailed information on the
display, including key measurement values and parameters
as well as "in operation" and general fault indication per
pump

Comprehensive functionality for high system availability

Selection information

Lightning protection

Electrical installations must be protected against
overvoltage (compulsory since 14 December 2018) (see
DIN VDE 0100-443 (IEC60364-4-44:2007/A1:2015, modified)
and DIN VDE 0100-534 (IEC 60364-5-53:2001/A2:2015,
modified). Whenever modifications are made to existing
installations, retrofitting a surge protective device (SPD) in
accordance with VDE is mandatory.

The associated lightning protection concept must be
provided by the operator or by a suitable provider
commissioned by the operator. Surge protective devices
can be found in the extended accessories range (type
series booklet 4041.51) as optional control unit
components.

Indoor installation:

A maximum cable length of 10 metres should not be
exceeded between the surge protective device (usually
type 1, internal lightning protection) installed at the
service entrance and the equipment to be protected. For
longer cables, additional surge protective devices (type 2)
must be provided in the sub-distribution board upstream
of the equipment to be protected or directly in the
equipment itself.

Sensor cables that cross the boundaries between lightning
protection zones must be additionally protected by
suitable surge protective devices (e.g. when using a 4 -
 20 mA immersion probe).

Outdoor installation:

Control units installed outdoors (e.g. in outdoor cabinets)
should always be equipped with Type 1 surge protective
devices (lightning protection), as they will not normally be
protected by a suitable upstream service entrance SPD.

Summary of Contents for LevelControl Basic 2

Page 1: ...Level Control Unit LevelControl Basic 2 Type Series Booklet...

Page 2: ...herein must neither be distributed copied reproduced edited or processed for any other purpose nor otherwise transmitted published or made available to a third party without the manufacturer s expres...

Page 3: ...riants 4 Designation 5 Product benefits 6 Selection information 6 Technical data 7 Dimensions and weights 8 LevelControl Basic 2 for Ama Drainer 9 LevelControl Basic 2 for Ama Porter 14 LevelControl B...

Page 4: ...Basic 2 included in the scope of supply in some cases mini Compacta Compacta LevelControl Basic 2 included in the scope of supply Sewatec Sewabloc Etaline Etanorm Etabloc Other pumps on request Varian...

Page 5: ...rement 3 5 m M Pneumatic level measurement 10 5 m L Bubbler control 2 m H Bubbler control 3 m U Analog input 4 20 mA V Voltage input 0 5 4 5 V D Digital level switch N ATEX N Without ATEX functions E...

Page 6: ...htning protection concept must be provided by the operator or by a suitable provider commissioned by the operator Surge protective devices can be found in the extended accessories range type series bo...

Page 7: ...ety barriers type Stahl 9002 13 280 093 001 For ATEX with digital level switches selected via KSB EasySelect ATEX compliant versions in BS housing Single pump station incl 3 intrinsic safety barriers...

Page 8: ...is fully discharged Dimensions and weights Dimensions and weights Type Nominal current per pump H W D kg max A mm BC 10 400 281 135 4 5 4 7 BS1 10 400 300 155 12 BS15 10 600 400 200 12 BS1 14 600 400...

Page 9: ...00 DPNO 063 400 V 6 3 10 A BC2 400 DFNO 100 BC2 400 DPNO 100 400 V 13 18 A BS2 400 SFNO 180 BS2 400 SPNO 180 Functional comparison Symbols key Symbol Description d Digital display of switching points...

Page 10: ...230 V AC Ama Drainer N 301 302 303 Ama Drainer N 358 Ama Drainer NE 4 5 bimetal switch in the motor The bimetal switch is not connected to the control unit 3 400 V AC Ama Drainer ND 4 5 Ama Drainer B...

Page 11: ...D 014 015 Analog IN 24V PE gn ye PE gn ye 29 28 J203 Alarm 29 Fig 1 Circuit diagram Ama Drainer N 301 302 303 Ama Drainer N 358 Ama Drainer NE 4 5 Ama Porter NE 1 Contactor pump 1 16 Pump 2 2 Contacto...

Page 12: ...24V GND 014 015 Analog IN 24V 28 J203 Alarm 30 30 Fig 2 Circuit diagram Ama Drainer ND 4 5 1 Contactor pump 1 16 Pump 2 2 Contactor pump 2 17 Power supply 3 Mains connections 3 400 V 1 230 V 18 High...

Page 13: ...Analog IN 24V 28 J203 Alarm 30 30 Fig 3 Circuit diagram Ama Drainer B 80 1 Contactor pump 1 16 Pump 2 2 Contactor pump 2 17 Power supply 3 Mains connections 3 400 V 1 230 V 18 High water float switch...

Page 14: ...00 DFNO 063 BC2 400 DPNO 063 BS2 400 DLNO 063 BC2 400 DLNO 063 Functional comparison Symbols key Symbol Description d Digital display of switching points o Optional Control unit feature Not a control...

Page 15: ...mal circuit breaker bimetal Optional components Rechargeable battery for powering the device o o Control cabinet heating for type BS o Alarm equipment 1 free alarm input 1 digital input for high water...

Page 16: ...4 015 Analog IN 24V PE gn ye PE gn ye 29 28 J203 Alarm 29 Fig 4 Circuit diagram Ama Porter NE 1 Contactor pump 1 16 Pump 2 2 Contactor pump 2 17 Power supply 3 Mains connections 18 High water float sw...

Page 17: ...24V PE gn ye 30 28 J203 Alarm 30 Fig 5 Circuit diagram Ama Porter ND 1 Contactor pump 1 16 Pump 2 2 Contactor pump 2 17 Power supply 3 Mains connections 18 High water float switch 4 Leakage monitor 1...

Page 18: ...LNO 063 BC2 400 DLNO 063 400 V 6 3 10 A BC2 400 DFNO 100 BC2 400 DPNO 100 BS2 400 DLNO 100 BC2 400 DLNO 100 Functional comparison Symbols key Symbol Description d Digital display of switching points o...

Page 19: ...circuit breaker bimetal Motor leakage moisture monitoring Optional components Rechargeable battery for powering the device o o Control cabinet heating for type BS o o Alarm equipment 1 free alarm inp...

Page 20: ...040 BS2 400 DLEO 040 BC2 400 DLEO 040 400 V 4 0 6 3 A BS2 400 DFEO 063 BC2 400 DPEO 063 BS2 400 DLEO 063 BC2 400 DLEO 063 400 V 6 3 10 A BS2 400 DFEO 100 BC2 400 DPEO 100 BS2 400 DLEO 100 BC2 400 DLE...

Page 21: ...aker bimetal Motor leakage moisture monitoring Optional components Rechargeable battery for powering the device o o Control cabinet heating for type BS o o o o Alarm equipment 1 free alarm input non A...

Page 22: ...GND 014 015 Analog IN 24V 5 4 5 4 PE 6 6 6 9 M 3 1 2 3 5 21 4 20 PE 6 9 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 22 24 25 26 27 28 J203 Alarm 30 30 Fig 6 Circuit diagram Amarex 1 Co...

Page 23: ...6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 22 24 25 26 27 28 J203 Alarm 30 30 Fig 7 Circuit diagram Amarex N 1 Contactor pump 1 16 Pump 2 2 Contactor pump 2 17 Power supply 3 Mains connections...

Page 24: ...DFNO 100 BS2 400 DFEO 100 BS2 400 DPEO 100 BS2 400 DLEO 100 400 V 9 14 A BS2 400 SFNO 140 BS2 400 SFEO 140 BS2 400 SPEO 140 BS2 400 SLEO 140 400 V 13 18 A BS2 400 SFNO 180 BS2 400 SFEO 180 BS2 400 SPE...

Page 25: ...nitoring Optional components Rechargeable battery for powering the device o o Additional intrinsic safety barrier o o o o o o Control cabinet heating o o Alarm equipment 1 free alarm input 1 digital i...

Page 26: ...012 013 014 015 010 011 019 014 015 Analog IN 24V GND 014 015 Analog IN 24V 2 3 4 5 6 7 8 9 10 11 12 13 14 17 18 19 20 21 22 23 22 24 25 26 27 28 J203 Alarm 20 21 9 M 3 1 2 3 PE T PTC Relais 10 11 16...

Page 27: ...rmal circuit breaker 19 Float switch 6 Release 20 Digital switch 7 Volt free alarm contact 21 Analog sensor 4 20 mA 8 Float switch digital switch 22 Peak load ON 9 High water float switch 23 Pump ON O...

Page 28: ...or pump 1 9 Mains supply 4 Connection for pump 2 10 Contactors 5 Manual 0 automatic switch 11 Motor protection switch pumps 6 Control board 12 Rechargeable battery optional Type BC2 400 DFNO 010 100 3...

Page 29: ...p connection 5 Internal pressure sensor 11 Motor protection switch pumps 6 Pneumatic 12 V for horn etc 12 Rechargeable battery optional Type BS2 400 DLNO 010 100 BS2 400 DLEO 010 100 3 400 V AC DOL st...

Page 30: ...ersion 1 2 3 9 10 13 4 6 5 7 8 12 11 1 Master switch 7 Digital inputs 4 20 mA 12 V for horn etc 2 Control panel 8 Contactors pump connection 3 Manual 0 automatic switch 9 Mains supply 4 Control transf...

Page 31: ...arger than usual LevelControl Basic 2 for outdoor installation Type BC Using a heater is recommended Type BS A heater must be used Overview of outdoor cabinets Control unit Material enclosure control...

Page 32: ...f base H W D mm 900 780 315 IP44 glass fibre reinforced polyester colour RAL 7035 locking device profile half cylinder suitable for buried installation including metal frame for setting in concrete 19...

Page 33: ...Description Mat No kg O210 Pump current measuring module Can only be used in combination with signalling module Measuring range 0 5 10 A 15 A 19075188 0 15 O211 Measuring range 10 20 A 30 A 19075189 0...

Page 34: ...in a pump sump above the pump start up point Warning at a water level of 1 mm in areas with a flooding or leakage risk e g in the cellar or next to the washing machine in the kitchen or bathroom Dimen...

Page 35: ...0 155 Operating manual in Russian13 01149725 0 155 Operating manual in Hungarian13 01148344 0 155 Operating manual in Turkish13 01235989 0 155 Operating manual in Bulgarian13 01350442 0 155 Operating...

Page 36: ......

Page 37: ......

Page 38: ...KSB SE Co KGaA Johann Klein Stra e 9 67227 Frankenthal Germany Tel 49 6233 86 0 www ksb com 4041 5 12 EN 28 01 2021...

Reviews: