5 Installation at Site
19 of 64
Hya-Rain/Hya-Rain N
5.4 Connecting the piping
5.4.1 Connecting the mains water inlet
CAUTION
Excessive bend of connection line
System defect due to impermissible loads on the system!
Reduced service life!
▷
Connect the connection line without transmitting any stresses or strains.
No forces must act on the connection nozzles and the system.
CAUTION
Pressure higher than mains water back-up limit of 4 bar
System defect due to impermissible load!
▷
Install pressure reducers upstream of the system to make sure that the inlet
pressure of the mains water supply does not exceed 4 bar.
CAUTION
Solid substances in the drinking water (stones, sediments, limescale deposits)
System defect due to impermissible loads!
Reduced service life!
▷
If used in areas where the drinking water quality is affected by the above,
provide a drinking water filter.
NOTE
Fitting a shut-off valve at the site is recommended.
741.02
Fig. 3:
Connecting the mains water inlet
1. Connect the mains water inlet to the mains water supply (float valve 741.02)
R
3
/
4
.
2. Open the mains water supply line.
ð
The mains water storage tank will fill automatically once the mains water
supply line is opened.