3 Transport/Temporary Storage/Disposal
11 of 48
Hya-Duo D FL Compact
3 Transport/Temporary Storage/Disposal
3.1 Checking the condition upon delivery
1. On transfer of goods, check each packaging unit for damage.
2. In the event of in-transit damage, assess the exact damage, document it and
notify KSB or the supplying dealer and the insurer about the damage in writing
immediately.
3.2 Transport
DANGER
Tilting break tank package booster set for fire fighting
Risk of injury from falling break tank package booster set for fire fighting!
▷
Never suspend the break tank package booster set for fire fighting by its cable.
▷
Observe the applicable local accident prevention regulations.
▷
Observe the information on weights, centre of gravity and fastening points.
▷
Use suitable and permitted transport equipment, e.g. crane, forklift or pallet
truck.
▷
Attach the break tank package booster set for fire fighting to crane lifting
tackle as shown, or use a forklift or pallet truck to move the pallet.
The break tank package booster set for fire fighting can be separated into three
parts to facilitate transport.
▪
Control cabinet with hydraulic unit (pump sets with valves and piping)
▪
▪
Baseplate
Transporting the separated
break tank package booster
set for fire fighting
Fig. 1:
Transporting the separated parts of the break tank package booster set for
fire fighting
ü
Transport equipment / lifting equipment suitable for the corresponding weight
has been selected and is on hand.
1. Remove the packaging. Remove the caps from the connection openings.
2. Check for any in-transit damage.
3. Disconnect the plug-type connection between the tank and the control cabinet.
4. Undo the flanged connections between the hydraulic unit and the tank.
5. Remove the hydraulic unit from the tank.
6. Unbolt the tank from the baseplate.
7. Transport the three modules to the place of installation.
8. Suspend the tank, hydraulic unit and baseplate as illustrated.