10 Related Documents
KSB Delta Macro
69
of
92
1983.843/04-EN
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
2-2-1-2
Pump 2
Automatic
Manual-Off
Everybody
Display/Customer
-
Manual-Off
Manual-On
2-2-1-3
Pump 3
Automatic
Manual-Off
Everybody
Display/Customer
-
Manual-Off
Manual-On
2-2-1-4
Pump 4
Automatic
Manual-Off
Everybody
Display/Customer
-
Manual-Off
Manual-On
2-2-1-5
Pump 5
Automatic
Manual-Off
Everybody
Display/Customer
-
Manual-Off
Manual-On
2-2-1-6
Pump 6
Automatic
Manual-Off
Everybody
Display/Customer
-
Manual-Off
Manual-On
2-2-2
Rainwater operating mode
-
-
Everybody
Nobody
-
2-2-2-1
Rainwater pump 1
Automatic
Manual-Off
Everybody
Customer
-
Manual-Off
Manual-On
2-2-2-2
Rainwater pump 2
Automatic
Manual-Off
Everybody
Customer
-
Manual-Off
Manual-On
10.2.2.3 Timers
Table 31:
Timers parameters
Parameter
Description
Value range and dependencies
Factory setting
Access level Read
Access level Write
Re-start
required
2-3
Timer
-
-
Everybody
Nobody
-
2-3-1
Start delay time
0 … 99.9 s
3 s
Everybody
Service
-
2-3-2
Stop delay time
0 … 99.9 s
3 s
Everybody
Service
-
2-3-3
Minimum runtime
0 … 999 s
180 s
Everybody
Service
-
2-3-4
Minimum runtime correction
step
0 … 99 s (calculated due to operating
mode)
10 s
Everybody
Service
-