5 Installation at Site
27 of 92
KSB Delta Macro
1983.843/04-EN
5 Installation at Site
5.1 Installation
WARNING
Installation on mounting surfaces which are unsecured and cannot support the
load
Personal injury and damage to property!
▷
Use a concrete of compressive strength class C12/15 which meets the
requirements of exposure class X0 to EN 206-1.
▷
The mounting surface must have set and must be completely horizontal and
even.
▷
Observe the weights indicated.
NOTE
Do not install pressure booster systems next to sleeping or living quarters.
NOTE
The anti-vibration mounts provide adequate insulation against solid-borne noise.
Before beginning with the installation check the following:
▪
All structural work required has been checked and prepared in accordance with
the dimensions in the outline drawing.
▪
The pressure booster system can be operated on the power supply network in
accordance with the data on the name plate.
▪
The place of installation is frost-free.
▪
The place of installation can be locked.
▪
The place of installation is well-ventilated.
▪
The place of installation is well-lit.
▪
A suitably dimensioned drain connection (e.g. leading to a sewer) is available.
▪
If expansion joints are used, take note of their creep resistance. Expansion joints
must be easily replaceable.
The pressure booster system is designed for a maximum ambient temperature of 0 °C
to 30 °C at a relative humidity of 60 %.
5.2 Installing the pressure booster system
WARNING
Top-heavy pressure booster system
Risk of personal injury by pressure booster system tipping over!
▷
Pressure booster systems awaiting final installation must be secured against
tipping over.
▷
Firmly anchor the pressure booster system.
NOTE
To prevent the transmission of piping forces and solid-borne noise, installing
expansion joints with length-limiters is recommended.