5 Installation at Site
21 of 52
Calio S
1157.8117/01-EN
NOTE
Installing check and shut-off elements in the system is recommended, depending on
the type of plant and pump. However, such elements must not obstruct proper
drainage or hinder disassembly of the pump.
ü
Suction lift lines have been laid with a rising slope, suction head lines with a
downward slope towards the pump.
ü
The nominal sizes of the piping are equal to or greater than the nominal sizes of
the pump nozzles.
ü
The piping has been anchored in close proximity to the pump and connected
without transmitting any stresses or strains.
1. Thoroughly clean, flush and blow through all vessels, piping and connections
(especially of new installations).
5.5 Fitting the enclosure/insulation
WARNING
The pump takes on same temperature as the fluid handled
Risk of burns!
▷
Insulate the pump casing. Fit protective equipment.
CAUTION
Heat build-up at motor housing and electronic system housing
Pump overheating!
▷
Do not insulate the motor housing and electronic system housing.
NOTE
Two-piece thermal insulation shell supplied for overall length ≥ 180 mm.
ü
The supplied thermal insulation shell is fitted for overall length ≥ 180 mm.
1. Insulate the enclosure using suitable materials or, if available, fit the supplied
thermal insulation shell to the pump casing.