![KSB BOA-CVP H Installation & Operating Manual Download Page 33](http://html1.mh-extra.com/html/ksb/boa-cvp-h/boa-cvp-h_installation-and-operating-manual_2006429033.webp)
9 Related Documents
33 of 40
BOA-H Mat P
9.2 Maximum permissible closing pressures
Table 12:
Fluid approaches the valve disc in closing direction; p2 = 0 bar
DN
Actuator:
PA-N300
PA-N540
Spring range [bar]:
1,6 - 2,8
2,0 - 3,7
Control pressure required [bar]:
2,9
3,8
Stem seal:
Graphite gland
packing
PTFE V-packing
Graphite gland
packing
PTFE V-packing
Stroke [mm]
Kvs value [m
3
/h]
[bar]
[bar]
[bar]
[bar]
20
7,5
8,3
25,0
25,0
-
-
25
7,5
13,0
25,0
25,0
-
-
32
11,0
19,9
25,0
25,0
-
-
40
12,0
27,1
24,3
25,0
-
-
50
13,5
42,0
15,6
17,2
25,0
25,0
65
17,0
75,1
8,6
9,8
24,8
25,0
80
20,5
116,7
5,5
6,2
16,4
17,1
100
25,5
172,3
3,3
3,6
10,4
10,8
125
33,0
270,0
-
-
6,4
6,7
150
38,0
393,0
-
-
4,3
4,5
9.3 Dimensions and weights of BOA-H Mat P globe valve
BOA-H Mat P
Table 13:
Dimensions [mm] and weights [kg]
PN
DN
b
d
2
d
6
D
h
1
h
2
k
l
n
[kg]
16
20
16
M39
14
105
153,5
101,0
75
150
4
6,3
25
16
M39
14
115
164,5
107,0
85
160
4
6,9
32
18
M39
19
140
216,0
146,0
100
180
4
10,4
40
18
M39
19
150
226,0
151,0
110
200
4
11,6
50
20
M39
19
165
227,0
144,5
125
230
4
13,8
65
20
M50
19
185
272,5
180,0
145
290
4
22,3
80
22
M50
19
200
284,0
184,0
160
310
8
28,4
100
24
M50
19
220
328,0
218,0
180
350
8
38,4
125
26
M50
19
250
384,5
259,5
210
400
8
60,5
Summary of Contents for BOA-CVP H