6 Commissioning/Start-up/Shutdown
26 of 36
BOA-Control PIC
7138.8/01-EN
6.1.3 Setting the volume flow rate
DN 10 - 50
Fig. 10:
Adjusting ring for presetting the volume flow rate
1. Turn the blue plastic cap 580.1 anti-clockwise to remove it from the bonnet.
2. Loosen the locking device (locknut) by approx. one full turn.
3. Turn the adjusting ring until the required value is set. Do not exceed the
operating range (1-5). For the relationship between the volume flow rate and
the values shown on the adjusting ring refer to (
4. Tighten the locking device to prevent the preset value being changed
inadvertently.
5. Fit the blue plastic cap 580.1 again to prevent contamination.
6. Turn the blue plastic cap 580.1 clockwise until it lightly touches the stem end.
CAUTION
Unintentional closing of valve when setting the volume flow rate
No throughflow!
▷
When fitting the blue plastic cap only turn it until it lightly touches the stem
end.
▷
Do not tighten the blue plastic cap up to the stop.
DN 65 - 150
Preregolazione. Calcolare la percentuale della port
ata desiderata rispelto alla portata
massima, indicata nella tabella Qmax. Sbloccare il
fermo F, ruotare il volantino e portare
l'indicatore P in corrispondenza del valore % calco
lato. Bloccare il fermo F.
Preset. Calculate the percentage of the desired flo
w rate on maximum flowrate shown in
table Qmax. Unlock the stop knob F, turn the handwheel and move the indicator P to
meet the calculated % value. Lock the stop knob F.
Istruzioni_EKOFLUX.PI_Istruzione comando manuale (r iduttore)
modif. 22/01/2019
F
S
Q
P
Fig. 11:
Setting the volume flow rate DN 65 - 150
Markings are provided on the manual gearbox to simplify presetting the required
volume flow rate. The maximum volume flow rate Qmax per nominal size in in m³/h
is indicated in a table (Q) and as a percentage on the rotating disc (S).
1. Check the locking device. Loosing it, if necessary, by turning the knurled thumb
screw (F).
2. Set the required volume flow rate by turning the handwheel on the manual
gearbox. Turn the indication until the arrow (P) points at the required
percentage on the disc (S). For presettings in percent refer to (
3. Activate the locking device by turning the knurled thumb screw (F).