Ecowatt
®
Drive K120 series
Function parameter list
-100-
Function
code
Name
Description
Default Modify
P10.37
Multi-step
time unit
selection
0: Second; the running time of each step is
counted in seconds;
1: Minute; the running time of each step is
counted in minutes.
0
◎
P11 group Protection parameters
Function
code
Name
Description
Default Modify
P11.00
Phase loss
protection
0x00–0x11
Ones place:
0: Disable input phase loss protection
1: Enable input phase loss protection
Tens place:
0: Disable output phase loss protection
1: Enable output phase loss protection
11
○
P11.01
Frequency
drop at
transient
power-off
0: Enable
1: Disable
0
○
P11.02
Frequency
drop ratio
at
transient
power-off
Setting range: 0.00Hz/s–P00.03 (max. output
frequency)
After the grid powers off, the bus voltage
drops to the frequency drop point at transient
power-off, the VFD begins to decrease the
running frequency based on P11.02, to make
the motor generate power again. The
returning power can maintain the bus
voltage to ensure a rated running of the VFD
until the VFD is powered on again.
Voltage degree
220V 380V 660V
Frequency drop
point at transient
power-off
260V 460V 800V
Note:
Adjust the parameter properly to avoid
the stopping caused by VFD protection
during the switching of the grid.
Disable the input phase loss protection
before enabling this function.
10.00Hz/s
○