Checking the usage

The bus module BCM 400 is used as a communica-

tion interface for burner control units BCU 4xx for 
connection to a fieldbus interface via PROFINET or 
EtherNet/IP.
Networking via the fieldbus enables BCU 4xx units 
to be controlled and monitored by an automation 
system (e.g. PLC). The communications network 
must be protected against unauthorized access.

This function is only guaranteed when used within the 

specified limits – see page 5 (Technical data). Any 
other use is considered as non-compliant.

Type code

Code

Description

BCM

Bus module

400

Series 400

S0 

S

Standard communication 

SafetyLink

B 

B 

B 

B4

PROFIBUS DP 

PROFINET 

EtherNet/IP 

Modbus TCP

/ 

/

9-pin D-Sub 

Two RJ45 sockets

-0 

-

– 

Three-point step control via bus

Part designations

4

5

2

3

7

8

1

BCM../3 with RJ45 sockets

RJ45 socket (port P1) for connecting to the 

bus communications system

RJ45 socket (port P2) for connecting to the 

bus communications system

4

Green LED 

(to indicate a connection: off = no connection, 

on = connection, flashing = data transfer)

5

Yellow LED 

(to indicate the transfer rate: on = 100 Mbit, 

off = 10 Mbit)

7

Code switches

8

Type label

MAC address (

A

) and ambient temperature (

B + C

) – 

see type label.

Elster GmbH

Osnabrück, Made in Germany

-

A

B

C

Installation

  

 Disconnect the BCU from the electrical power supply.

  

 Open the cover of the BCU.

  

 Insert the bus module in the slot provided.

Replacement

  

 Disconnect the BCU from the electrical power 

supply.

  

 Open the cover of the BCU.

  

 Remove the connection plug from the power 

and bus module.

 4 

 Remove the modules in the following order to 

facilitate handling:

 

.

 Power module,

 

.

 Bus module.

2.

1.

 

Installation of the modules in reverse order.

Summary of Contents for BCM 400 B2 Series

Page 1: ...uations WARNING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 04 19 The following chapters have been changed C...

Page 2: ...trol via bus Part designations 4 5 2 3 7 8 1 1 BCM 3 with RJ45 sockets 2 RJ45 socket port P1 for connecting to the bus communications system 3 RJ45 socket port P2 for connecting to the bus communications system 4 Green LED to indicate a connection off no connection on connection flashing data transfer 5 Yellow LED to indicate the transfer rate on 100 Mbit off 10 Mbit 7 Code switches 8 Type label M...

Page 3: ...s may only be allocated once within the fieldbus system PROFINET a device within the fieldbus system can be identified using the subscriber flash test display shows 00 with alternately highlighted segments For instructions on commissioning the control unit see operating instructions Burner control unit BCU 46x 480 If the fault message 1 to 4 flashes in the control unit s display fieldbus communica...

Page 4: ...et on the code switches must be identical to the address xxx entered in the automation system s network configuration After the code switch settings have been changed the control unit must be switched off and on again to enable the new address setting 5 Start the network communication The BCU powers up If the IP address is valid the program can be started Parameter A080 2 Fieldbus communication wi...

Page 5: ...assigned in the engineering tool or replace it with an individual name e g Furnacezone1 Check whether the device name name in the network configuration is the same as the device name saved in the control unit Check the value of parameter A080 and adjust it if necessary 4 The display on the control unit blinks and indicates 4 The controller is set to Stop Start the controller E E The display on the...

Page 6: ...ee page 5 Technical data Transport is subject to the ambient conditions de scribed Report any transport damage on the unit or packag ing without delay Check that the delivery is complete see page 2 Part designations Storage Storage temperature see page 5 Technical data Storage is subject to the ambient conditions de scribed Storage time 6 months before using for the first time If stored for longer...

Reviews: