Krom Schroder ZAI Operating Instructions Manual Download Page 4

GB-4

D

GB

F

NL

I

E

 

4

   

Connect the pilot gas supply line with Rp ¼ and 
the air supply line with Rp ½.

 

For connecting pilot gas and air supply lines 
with NPT thread, order the adapter set – see 
page 7 (Accessories).

Wiring

 DANGER

Electric shocks can be fatal!

 Before working 

on possible live components, ensure the unit is 
disconnected from the power supply.

 

For the ionization and ignition cables, use 
 unscreened high-voltage cable:

 

 FZLSi 1/7 -50 to +180°C (-58 to +356°F), 
Order No. 04250410, or   
FZLK 1/7 -5 to +80°C (23 to 176°F),   
Order No. 04250409.

 

Wire the burner as shown in the connection 
diagrams of the automatic burner control unit/

ignition transformer.

ZAI

I

Z

I

 = Flame rod

Z

 = Spark 

electrode

Screw for 
PE wire 

 

 Connect the PE wire for burner ground to the 

fastening lug on the burner insert.

ZKIH

I

Z

2

3

1

4

5

Tighten the PG cable gland.

 6 

 Tighten ionization and ignition cables with a 

torque of 5 Nm (slotted head screw), locking the 
electrode on the hexagon to prevent it twisting.

 

 Replace seal and cover and screw into place.

 

 Connect the PE wire for burner ground to the 

burner.

Leak test

 DANGER

Risk of explosion and poisoning! 

To ensure that 

there is no danger resulting from a leak, check the 
gas connections on the burner for leaks immediately 
after the burner has been put into operation.

ZAI

2

1

I

 = Flame rod

Z

 = Spark electrode
 = Screw for PE wire

Summary of Contents for ZAI

Page 1: ...ndicates potentially fatal situations WARNING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicia...

Page 2: ...mm gas nozzle for LPG 8 Cone olive only for ZAI K 9 Cap screw only for ZAI K 10 Enclosed documentation operating instructions Gas connection see type label D Osnabr ck Germany ZAI K ZKIH Type code ZK...

Page 3: ...strictor and a pressure tap be installed in both the gas and air supply line Order filter restrictor pressure tap pilot burner Distance between the restrictor and pressure tap and between pressure tap...

Page 4: ...diagrams of the automatic burner control unit ignition transformer ZAI I Z 1 2 3 I Flame rod Z Spark electrode Screw for PE wire 4 Connect the PE wire for burner ground to the fastening lug on the bur...

Page 5: ...rol unit 4 Adjust the burner DANGER Risk of explosion in case of CO being formed in the furnace chamber An incorrect change of the burner settings may change the gas air ratio and lead to unsafe opera...

Page 6: ...ition on a smooth working surface 2 1 1 2 2 10 11 12 Loosen the screws a turn 1 2 6 mm 22 mm 2 mm 1 2 9 mm 15 14 12 17 16 18 13 ZAI ZKIH Reconnect the electrode terminal bootl s Produce a maintenance...

Page 7: ...aning products Mechanical data ZAI Gas types natural gas LPG gaseous coke oven gas town gas and clean cold air Gas inlet pressure approx 10 60 mbar 4 24 WC depending on the gas type Condition on deliv...

Page 8: ...ons Disposal Components are to be disposed Declaration of Incorporation pursuant to 2006 42 EC Annex II No 1B The products Burners for gas ZAI and ZKIH are partly completed machines pursuant to Articl...

Reviews: