Krom Schroder VAS Series Operating Instructions Manual Download Page 13

GB-13

D

GB

F

NL

I

E

Seal set for sizes 1 – 

 

When retrofitting accessories or a second  valVario 
control or when servicing, we  recommend 

 replacing the seals.

C

A B

C

E

D

 

Order No. for  
size 1: Order No. 74921988, 
size 2: Order No. 74921989, 
size 3: Order No. 74921990.

 

Scope of delivery:

 

A

  1 x double block seal,

 B

  1 x retaining frame, 

 

C

  2 x O-rings (flange), 

 

D

   2 x O-rings (pressure switch), 

for pressure test point/screw plug:

 E

   2 x sealing rings (flat sealing), 2 x profiled 

sealing rings.

Cable gland with pressure equalization 

element

 

To avoid the formation of condensation, the cable 

gland with pressure equalization element can be 
used instead of the standard M20 cable gland. 

The diaphragm in the gland is designed to ven-

tilate the device, without allowing water to enter.

 

1 x cable gland, Order No.: 74924686

Technical data

Ambient conditions

Icing, condensation and dew in and on the unit are 
not permitted.

Avoid direct sunlight or radiation from red-hot 

surfaces on the unit. Note the maximum medium 
and ambient temperatures!

Avoid corrosive influences, e.g. salty ambient air 

or SO

2

.

The unit may only be stored/installed in enclosed 

rooms/buildings.

The unit is suitable for a maximum installation 

height of 2000 m AMSL.

Ambient temperature:

-20 to +60°C (-4 to +140°F), no condensation 

permitted.
Long-term use in the upper ambient temperature 
range accelerates the ageing of the elastomer ma-
terials and reduces the service life (please contact 
manufacturer).
Storage temperature: -20 to +40°C (-4 to +104°F).
Enclosure: IP 65.

This unit is not suitable for cleaning with a high-

pressure cleaner and/or cleaning products.

Mechanical data

Gas types: natural gas, LPG (gaseous), biogas 
(max. 0.1 %-by-vol. H

2

S) or clean air; other types 

of gas on request. The gas must be clean and dry 
in all temperature conditions and must not contain 
condensate.
Medium temperature = ambient temperature.
CE and FM approved, UL listed, max. inlet pres-
sure p

u

: 500 mbar (7 psig).

FM approved, non operational pressure: 700 mbar 
(10 psig).

ANSI/CSA approved: 350 mbar (5 psig).

Flow adjustment limits the maximum flow rate to 
between approx. 20 and 100%. On VAS 1 – 3, the 
setting can be monitored on an indicator.

Adjustment of the start gas rate: 0 to approx. 70%.

Opening times:
VAS../N quick opening: ≤ 1 s;
VAS../L slow opening: up to 10 s.
Closing time:
VAS../N, VAS../L quick closing: < 1 s.
Switching frequency:
VAS../N: max. 30 x per minute.
VAS../L: there must be a period of 20 seconds 
between switching off and on again so that the 
damping is fully effective.
Safety valve: Class A, Group 2 pursuant to 
EN 13611 and EN 161.
Factory Mutual (FM) Research Class: 7400 and 

7411, 

ANSI Z21.21 and CSA 6.5.

Summary of Contents for VAS Series

Page 1: ...Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 10 17 The following c...

Page 2: ...ve is not damaged during installation and operation Sealing material and dirt e g thread cuttings must not be allowed to get into the valve hous ing A filter must be installed upstream of every sys te...

Page 3: ...lenoid valve VAS 1 a DN 25 differential pressure orifice with outlet opening d 30 mm 1 18 must be inserted at the outlet of the pressure regulator In the case of pressure regulator VAx 115 or VAx 120...

Page 4: ...ing Type 2 the en closure openings shall be closed with fittings rated UL Type 2 3 3R 3RX 3S 3SX 3X 4X 5 6 6P 12 12K or 13 Gas solenoid valves shall be protected by a branch circuit protective device...

Page 5: ...re is a risk of interference between valve voltage and proof of closure switch voltage To make wiring easier the connection terminal for the proof of closure switch can be removed 1 3 2 LV1 N 1 3 2 LV...

Page 6: ...if the adjusting screw is overturned Setting the start gas rate on VAS L VCS L The start gas rate can be set by turning the damping unit a maximum of 5 turns There must be a period of 20 seconds betwe...

Page 7: ...VAS 2 3 use the small seal from the actuator adapter set and only one of the large seals VAS 1 3 10 11 Slide seal under the second groove 12 Position new actuator 13 Follow the reverse procedure when...

Page 8: ...4 5 3 10 9 Maintenance CAUTION In order to ensure smooth operation check the tightness and function of the VAS Once per year twice per year in the case of biogas check for internal and external tight...

Page 9: ...ion from the switching point during testing pursuant to EN 1854 Gas pressure switches 15 Bypass pilot gas valves 1 Disconnect the system from the electrical power supply 2 Shut off the gas supply 3 Pr...

Page 10: ...10 mm 0 39 at the outlet of the main valve if the bypass valve s outlet flange is designed as a blind flange For the pilot gas valve insert sealing plug F at the outlet of the main valve if the pilot...

Page 11: ...s piloto ppna bypass eller t ndgasven tilen pne bypass eller tenn gassventilen Otev t obto kov ventil nebo zapalovac plynov ventil Otworzy zaw r obej ciowy lub zaw r gazu zap onowego Tightness control...

Page 12: ...nnect the system from the electrical power supply Shut off the gas supply 16 5 4 3 8 7 6 9 10 13 12 11 15 14 In both connection boxes push through the knock out for the cable gland set then remove the...

Page 13: ...AMSL Ambient temperature 20 to 60 C 4 to 140 F no condensation permitted Long term use in the upper ambient temperature range accelerates the ageing of the elastomer ma terials and reduces the servic...

Page 14: ...3 A VAS G 12 30 V DC 2 mA 0 1 A Switching frequency of proof of closure switch max 5 x per minute Switching current A Switching cycles cos 1 cos 0 6 0 1 500 000 500 000 0 5 300 000 250 000 1 200 000 1...

Page 15: ...in ac cordance with local regulations Disposal Components are to be disposed of separately in accordance with local regulations Certification Declaration of conformity We the manufacturer hereby decl...

Page 16: ...earch Class 7400 and 7411 Safety overpressure slam shut valves Designed for applications pursuant to NFPA 85 and NFPA 86 ANSI CSA approved Canadian Standards Association ANSI Z21 21 and CSA 6 5 UL lis...

Reviews: