Krom Schroder JSAV 50 Operating Instructions Manual Download Page 6

GB-6

D

GB

F

NL

I

E

Replacing the valve disc

 

The valve disc has to be replaced if the JSAV is 

leaking or has been damaged during resetting.

 

We recommend cleaning the O-ring seats and 

lightly greasing the O-rings with Klüber Nontrop 

ZB91 DIN before installation.

  

 Depressurize the system.

 

We also recommend replacing the entire seal set 
and the bellows when replacing the valve disc.

 

The seal set with bellows is available separately 

as a spare part.

 

Ensure that the JSAV is closed. The red “SHUT” 
mark must be visible. 

 

If the JSAV is open, apply pressure to the impulse 
line to close the valve.

  

 Detach the impulse and breather lines from the 

JSAV.

7

6

4

5

3

     Press the 

reset lever and 

turn until the 

valve disc is 

on top.

 WARNING

Risk of injury!

–   The spring wire is under high stress.

10

11

8

12

14

13

9

15

16

    Insert new 

O-rings from 

the seal set.

Press the 

spring wire 

into the notch 

in the plate.

 7 

  Follow the reverse procedure when reassembling 

using the new valve disc and the O-rings from 
the seal set.

 

To ensure that the valve disc is pushed onto 

the seat by the spring, the spring wire must be 
released from the notch in the plate and rest 
against the housing wall.

 8 

 Connect the impulse and breather lines.

 9 

 Check tightness and function, see page 3 

(Tightness test) and page 4 (Checking the 
function).

Summary of Contents for JSAV 50

Page 1: ...ions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 10 15 The following chapters have been changed Installation Setting the trip pressure pdo Certification Operating instructions D GB GB 1 03250885 Translation from ...

Page 2: ...trip pressure pdo ambient temperature see type label D 49018 Osnabrück Germany JSAV TS Pu max Who pdo AGo 10 Installation CAUTION Please observe the following to ensure that the JSAV is not damaged during installation Sealing material cuttings and other impurities must not be allowed to get into the housing We recommend installing a filter upstream of the JSAV in order to protect it against impuri...

Page 3: ...ial Ensure that there is sufficient tube length for the impulse line 0 Rp NPT Connecting the breather line Remove the plastic plug in the breather line connection and connect an Rp NPT pipe We recommend a pipe diameter of 12 x 1 5 mm 1 Install the breather line and seal with approved sealing material Route the breather line to a safe area 0 Rp NPT Tightness test WARNING An additional tightness tes...

Page 4: ...isc Ensure that the JSAV and outlet gas line are closed 1 Vent the system 2 Slowly open the manual valve at the inlet 3 The outlet pressure pd must not rise Setting the trip pressure pdo 1 Select the trip pressure pdo according to the outlet pressure pd of the pressure regulator 20 0 40 60 80 100 140 180 220 260 300 340 50 100 150 200 250 300 350 400 450 500 pd mbar p do mbar VSBV JSAV 2 Remove th...

Page 5: ... reset lever until the valve disc opens and clicks into place and the SHUT mark is no longer visible The red SHUT mark must not be visible once the valve disc has clicked into place The JSAV is ready for operation Replacing the measuring unit The measuring unit has to be replaced if the JSAV no longer opens or can no longer be reset We recommend cleaning the O ring seats and lightly greasing the O...

Page 6: ...e to the impulse line to close the valve 2 Detach the impulse and breather lines from the JSAV 7 6 4 5 3 Press the reset lever and turn until the valve disc is on top WARNING Risk of injury The spring wire is under high stress 10 11 8 12 14 13 9 15 16 Insert new O rings from the seal set Press the spring wire into the notch in the plate 17 Follow the reverse procedure when reassembling using the n...

Page 7: ...urther half a turn See the drawing labelled Contacts in the en closed position switch installation and connec tion instructions for measuring the switching point 9 Prevent the position switch from rotating using the fitted lock nut 10 Wire the position switch See the drawing labelled Contacts in the en closed position switch installation and connec tion instructions for the electrical wiring 11 Af...

Page 8: ... Part designa tions Report any transport damage immediately Storage Store the product in a dry and clean place Storage temperature see page 7 Technical data Storage time 6 months before using for the first time If stored for longer than this the overall service life will be reduced by the corresponding amount of extra storage time Packaging The packaging material is to be disposed of in ac cordanc...

Reviews: