Safety

Please read and keep in a safe place

 Please read through these instructions 

carefully before installing or operating. Following the 
installation, pass the instructions on to the opera-
tor. This unit must be installed and commissioned 
in accordance with the regulations and standards 
in force. These  instructions can also be found at 
www.docuthek.com.

Explanation of symbols

 • 

,  1 ,   ,  3 

... = Action

 

= Instruction

Liability

We will not be held liable for damage resulting from 
non-observance of the instructions and non-com-
pliant use.

Safety instructions

Information that is relevant for safety is indicated in 
the instructions as follows:

 DANGER

Indicates potentially fatal situations.

 WARNING

Indicates possible danger to life and limb.

 CAUTION

Indicates possible material damage.

All interventions may only be carried out by qualified 
gas technicians. Electrical interventions may only be 
carried out by qualified electricians.

Conversion, spare parts

All technical changes are prohibited. Only use OEM 
spare parts.

Transport

On receipt of the product, check that the delivery is 
complete (see Part designations). Report any trans-
port damage immediately. 

Storage

Store the product in a dry place. Ambient tempera-
ture: see Technical data.

Changes to edition 10.1

The following chapters have been changed:
– 

 New  layout: 
Installation 
Wiring 
Adjustment 
Accessories 
Technical data 
Declaration of conformity

Contents

Operating instructions

D

GB

F

NL

I

E

GB-1

035005

Translation from the German

Pressure switches for air DL..K

Pressure switches for air DL..K  . . . . . . . . . . . 1
Contents  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Checking the usage . . . . . . . . . . . . . . . . . . . . . 

Type code  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Part designations . . . . . . . . . . . . . . . . . . . . . . . . 2

Type label. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Wiring  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Adjustment  . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Accessories  . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Technical data  . . . . . . . . . . . . . . . . . . . . . . . . . 4

Declaration of conformity . . . . . . . . . . . . . . . . 4
Contact  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Safety

Contents

Summary of Contents for DL K Series

Page 1: ... limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Transport On receipt of the product check that the delivery is complete see Part designations Report any trans port dama...

Page 2: ...erwise there is a risk of icing of condensation at subzero temperatures the switching point shifting or corrosion in the device which can lead to malfunctions In the case of uneven ground secure the pres sure switch to the mounting plate or air duct with only two screws on the same side in order to avoid subjecting the pressure switch to me chanical stress Protect the connections against dirt or m...

Page 3: ... using the hand wheel and scale The switching pressure differs from the adjusted setpoint by a maximum of 15 when it has been set for increasing pressure and with a vertical diaphragm Type Adjusting range Pa Mean switching differential at min and max setting Pa Deviation from the switching point during testing pursuant to EN 1854 or by agreement min max min max DL 3 3K 20 330 8 20 7 Pa 15 DL 3 5K ...

Page 4: ...V min 0 01 A to 48 V DC max 1 A DL KT 30 240 V AC 50 60 Hz 5 A resistive or 0 5 A inductive cos ϕ 0 6 DL KTG 30 V AC DC 0 1 A resistive or 0 05 A inductive cos ϕ 0 6 Ambient temperatures DL K 15 to 85 C 5 to 185 F DL KT 40 to 60 C 40 to 140 F Line entrance M16 1 5 cable diameter 4 5 to 10 mm Enclosure to IEC 60529 IP 54 Diaphragm tempered LSR diaphragm system Max inlet pressure pu or differential ...