background image

Contents

Cert. Version 11.17 · Edition 05.22 · EN · 03251434

DE, EN, FR, NL, IT

, ES, DA, SV

, NO, PT

, EL, TR, CS, PL, RU, HU, ZH, JA – www

.docuthek.com

Pressure switches for air DL..H, DL..n

1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

2 Checking the usage . . . . . . . . . . . . . . . . . . . . . 2
3 Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

4 Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

5 Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
6 Function check. . . . . . . . . . . . . . . . . . . . . . . . . 5

7 Accessories  . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

8 Technical data  . . . . . . . . . . . . . . . . . . . . . . . . . 6
9 Designed lifetime  . . . . . . . . . . . . . . . . . . . . . . . 7

10 Certification  . . . . . . . . . . . . . . . . . . . . . . . . . . 7
11 Logistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
12 Disposal  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

1 sAFetY

1.1 Please read and keep in a safe place

 Please read through these instructions care-

fully before installing or operating. Following the installa-
tion, pass the instructions on to the operator. This unit 
must be installed and commissioned in accordance 
with the regulations and standards in force. These 
instructions can also be found at www.docuthek.com. 

1.2 explanation of symbols

 = Action 

 

= Instruction

1.3 Liability

We will not be held liable for damage resulting from 
non-observance of the instructions and non-com-
pliant use.

1.4 safety instructions

Information that is relevant for safety is indicated in the 
instructions as follows:

 DAnGeR

Indicates potentially fatal situations.

 WARnInG

Indicates possible danger to life and limb.

 CAUtIon

Indicates possible material damage.

All interventions may only be carried out by qualified 

gas technicians. Electrical interventions may only be 
carried out by qualified electricians.

1.5 Conversion, spare parts

All technical changes are prohibited. Only use OEM 

spare parts.

oPeRAtInG InstRUCtIons

Summary of Contents for DL H Series

Page 1: ...ed in accordance with the regulations and standards in force These instructions can also be found at www docuthek com 1 2 Explanation of symbols 1 2 3 a b c Action Instruction 1 3 Liability We will not be held liable for damage resulting from non observance of the instructions and non com pliant use 1 4 Safety instructions Information that is relevant for safety is indicated in the instructions as...

Page 2: ...2 6 3 4 5 1 Upper housing section with cover 2 Lower housing section 3 Hand wheel 4 M16 cable gland 5 Manual reset 6 Test key DL A 2 3 Type label DL CE 2 1 3 D 49018 Osnabrück Germany Max inlet pressure withstand pressure mains volt age ambient temperature enclosure see type label 3 INSTALLATION CAUTION Please observe the following to ensure that the unit is not damaged during installation Droppin...

Page 3: ...9 5 0 4 15 5 0 6 45 1 8 54 5 2 1 6 0 2 ø 3 x 16 ø 0 11 x 0 6 64 2 5 DL AH DL AN DL KH DL KN 28 5 1 1 M16 x 1 5 NPT Conduit 28 5 1 1 M16 x 1 5 NPT Conduit 3 3 Connecting the pressure line DL A upon delivery port 2 is closed off by a rub ber cap DL A 1 Rp 1 4 1 4 NPT 2 ø 4 75 x 1 mm 3 ø 4 75 x 1 mm 4 Rp 1 8 1 8 NPT 1 2 3 4 Te st Positive pressure port 1 or 2 Negative pressure port 3 after unscrewing...

Page 4: ...close when subject to falling pressure With the NO contact the NC contact is omitted COM 3 NC 1 NO 2 NO 2 NC 1 COM 3 L1 5 ADJUSTMENT The switching point is adjustable via hand wheel 1 Disconnect the system from the electrical power supply 2 Unscrew the housing cover Once the settings have been adjusted successfully fit the housing cover again Note the tightening torques see page 6 8 Technical data...

Page 5: ...a restrictor orifice contains non ferrous metals Hole diameter 0 2 mm Order No 75456321 Hole diameter 0 3 mm Order No 75441317 7 2 Z angle bracket 11 3 0 44 7 0 27 7 5 0 3 40 1 6 59 2 3 ø 5 5 0 22 ø 6 0 22 ø 4 2 0 17 10 0 39 1 0 04 For DL K Order No 74916158 For DL A Order No 74913661 7 3 Fastening set with screws U shape bracket M4 x 10 M4 x 12 50 1 97 47 5 1 87 75 2 95 30 1 18 20 0 79 25 0 98 45...

Page 6: ...8 TECHNICAL DATA 8 1 Ambient conditions Enclosure to IEC 60529 IP 54 IP 65 Permitted ambient temperature in operation 15 to 60 C 5 to 140 F Storage and transport temperatures 20 to 40 C 4 to 104 F Micro switch to EN 61058 1 Gas types air or flue gas no flammable gases no aggressive gases Icing condensation and dew in and on the unit are not permitted Safety class II to VDE 0106 1 This unit is not ...

Page 7: ...ucts must be replaced Designed lifetime based on date of manufacture in accordance with EN 13611 EN 1854 for DL H DL N 10 Jahre years You can find further explanations in the applicable rules and regulations and on the afecor website www afecor org This procedure applies to heating systems For ther moprocessing equipment observe local regulations 10 CERTIFICATION Declaration of conformity We the m...

Page 8: ...At the end of the product life number of op erating cycles reached dispose of the pack aging and product in a corresponding recycling centre Do not dispose of the unit with the usu al domestic refuse Do not burn the product On request old units may be returned carriage paid to the manufacturer in accordance with the relevant waste legislation requirements 2022 Elster GmbH We reserve the right to m...