Pressure switches for air DL..A, DL..K

1 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

2 Checking the usage . . . . . . . . . . . . . . . . . . . . . 2
3 Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

4 Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

5 Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
6 Function check. . . . . . . . . . . . . . . . . . . . . . . . . 6

7 Accessories  . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

8 Technical data  . . . . . . . . . . . . . . . . . . . . . . . . . 7
9 Designed lifetime  . . . . . . . . . . . . . . . . . . . . . . . 7

10 Certification  . . . . . . . . . . . . . . . . . . . . . . . . . . 8
11 Logistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
12 Disposal  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

1 sAFetY

1.1 Please read and keep in a safe place

 Please read through these instructions care-

fully before installing or operating. Following the installa-
tion, pass the instructions on to the operator. This unit 
must be installed and commissioned in accordance 
with the regulations and standards in force. These 
instructions can also be found at www.docuthek.com. 

1.2 explanation of symbols

 = Action 

 

= Instruction

1.3 Liability

We will not be held liable for damage resulting from 
non-observance of the instructions and non-com-
pliant use.

1.4 safety instructions

Information that is relevant for safety is indicated in the 
instructions as follows:

 DAnGeR

Indicates potentially fatal situations.

 WARnInG

Indicates possible danger to life and limb.

 CAUtIon

Indicates possible material damage.

All interventions may only be carried out by qualified 

gas technicians. Electrical interventions may only be 
carried out by qualified electricians.

1.5 Conversion, spare parts

All technical changes are prohibited. Only use OEM 

spare parts.

oPeRAtInG InstRUCtIons

Summary of Contents for DL A Series

Page 1: ...in accordance with the regulations and standards in force These instructions can also be found at www docuthek com 1 2 Explanation of symbols 1 2 3 a b c Action Instruction 1 3 Liability We will not be held liable for damage resulting from non observance of the instructions and non com pliant use 1 4 Safety instructions Information that is relevant for safety is indicated in the instructions as fo...

Page 2: ...re mains volt age ambient temperature enclosure see type label 3 INSTALLATION CAUTION Please observe the following to ensure that the unit is not damaged during installation Dropping the device can cause permanent damage In this event replace the entire device and associated modules before use Use approved sealing material only Condensation must not be allowed to get into the housing If possible i...

Page 3: ...5 x 8 mm DL A Ø 3 5 x 8 mm Ø 4 x 8 mm DL 3K Ø 2 7 x 8 mm Ø 3 x 8 mm DL 3K Ø 3 5 x 8 mm Ø 4 x 8 mm DL 5 150K Ø 3 x 16 mm Ø 3 5 x 16 mm 49 5 1 9 44 5 1 7 ø 2 7 x 8 0 11 x 0 3 ø 3 5 x 8 0 14 x 0 3 ø 6 1 ø 0 24 DL A Rp DL AT NPT DL 1 5A DL 3A DL 3K 49 5 1 9 44 5 1 7 ø 2 7 x 8 ø 0 11 x 0 3 ø 3 5 x 8 ø 0 14 x 0 3 DL A Rp DL AT NPT DL 5 150A 9 5 0 4 9 5 0 4 15 5 0 6 45 1 8 54 5 2 1 6 0 2 ø 3 x 16 ø 0 11 ...

Page 4: ...his power rating or higher power rating CAUTION To ensure that the DL is not damaged during operation note the switching capacity see page 7 8 Technical data In the case of low switching capacities such as 24 V 8 mA for example we recommend using an RC mod ule 22 Ω 1 μF in air containing silicone or oil NO C 1 µF R 22 Ω 2 NC 1 COM 3 1 Disconnect the system from the electrical power supply 2 3 4 5 ...

Page 5: ...x DL 1 5A 0 5 1 5 50 0 1 0 16 DL 3A DL 3K 0 2 3 50 0 1 0 16 DL 3AT DL 3KT 0 3 3 150 0 1 0 16 DL 5A DL 5K 0 4 6 300 0 2 0 3 DL 5AT DL 5KT 0 5 5 300 0 2 0 3 DL 10A DL 10K DL 10AT DL 10KT 1 10 300 0 25 0 4 DL 30A DL 30K 2 5 30 300 0 35 0 9 Adjusting range1 mbar Max inlet pres sure2 mbar Mean switching differential3 mbar min max min max DL 50A DL 50K DL 50AT DL 50KT 2 5 50 300 0 8 1 5 DL 150A DL 150K ...

Page 6: ...0430 230 V AC I 0 6 mA Order No 74920429 Pilot lamp blue 110 120 V AC I 1 2 mA Order No 74916121 230 V AC I 0 6 mA Order No 74916122 1 2 3 4 NC 1 COM 3 NO NO 2 N NO 2 NC 1 COM 3 L1 N NC 1 COM 3 NO NC 2 N NO 2 NC 1 COM 3 L1 N 7 2 Red green pilot LED for 24 V DC AC or for 110 V AC to 230 V AC 24 V DC I 16 mA 24 V AC I 8 mA Order No 74921089 110 V AC to 230 V AC Order No 74923275 1 2 3 4 NC 1 COM 3 N...

Page 7: ...mponent Tightening torque Ncm Cover screws 65 M16 x 1 5 cable gland 50 Clamping terminal screws 80 Rp 1 8 connection on upper housing section 250 Rp 1 4 1 4 NPT connection on lower housing section 600 8 3 Electrical data Line entrance M16 x 1 5 1 2 NPT conduit clamping range diameters of 4 to 10 mm Type of connection screw terminals cable diameter 0 5 to 1 8 mm AWG 24 to AWG 13 8 3 1 Switching cap...

Page 8: ...mage on the unit or packaging without delay Check that the delivery is complete Storage Storage temperature see page 7 8 Technical data Storage is subject to the ambient conditions described Storage time 6 months in the original packaging before using for the first time If stored for longer than this the overall service life will be reduced by the corresponding amount of extra storage time 12 DISP...