Checking the usage
Burner control units BCU 460, 465 and 480 are de-
signed to control, ignite and monitor gas burners in
intermittent or continuous operation. They replace
the local control cabinet. Air and gas flow monitoring
as an option.
The outputs for controlling the burners, e.g. for ac-
tuator and valves, are activated via the replaceable
power module LM 400. All the parameters required
for operation are saved on the integrated parameter
chip card.
BCU 460, BCU 465
For directly ignited burners of unlimited capacity.
BCU 480
For pilot and main burners of unlimited capacity. Pilot
and main burners can be monitored independently.
LM..F0
Power module without air control interface.
LM..F1, LM..F3
Power module with air control interfaces to connect
an air valve (LM..F3) or actuator IC 40 (LM..F1).
This function is only guaranteed when used within the
specified limits – see page 29 (Technical data). Any
other use is considered as non-compliant.
Type code
Code
Description
BCU 4
Series 4 burner control unit
60
65
80
Series 460
Series 465
Series 480
Q
W
Mains voltage: 120 V AC, 50/60 Hz
230 V AC, 50/60 Hz
1
2
3
8
Ignition transformer duty cycle: 100%
20%
100%
33%
P0
P1
P2
P3
P6
P7
Flange plate: none
standard
M32
industrial plug connector, 16-pin
Profibus
conduit
C0
C1
C2
No valve proving system
With TC and POC valve proving system
With POC valve proving system
D0
D1
D2
No high temperature operation
For high temperature operation
Flameless operation
0
1
2
3
Input functions: none
auxiliary gas
LDS
auxiliary gas and LDS
0
1
2
3
Pressure switches: none
air pressure switch
gas pressure switch
air and gas pressure switch
K0
K1
K2
No connection plugs
Connection plugs with screw terminals
Connection plugs with spring force
terminals
E0
E1
Energy supply: via safety interlocks
via L1
Code
Description
LM
Power module
400
For series 4
Q
W
Mains voltage: 120 V AC, 50/60 Hz
230 V AC, 50/60 Hz
F0
F1
F3
Air actuator: none
with IC 40 interface
with air valve control
O0
O1
O2
Optional outputs: none
not fail-safe
fail-safe
E0
E1
Energy supply: via safety interlocks
via L1
K0
K1
K2
No connection plugs
Connection plugs with screw terminals
Connection plugs with spring force
terminals