02/2019 - MA OPTIWAVE-M 7400 C R01 en
4
OPERATION
OPTIWAVE-M 7400 C
4.4
Further information on device configuration in Program mode
4.4.1
Standard setup
Use this procedure (menu item A4.1 Standard Setup) to change the length unit, tank type, tank height
(this includes the stilling well diameter and stilling well height if Tank Type is set to "Stilling Well"),
current output variable, 0% range, 100% range, current output range and error function. Values and
parameters that can be changed are shown between the
«
...
»
marks in the illustrations that follow.
Push the keypad buttons in the correct sequence:
CAUTION!
Make sure that you do this procedure before you use the device. The settings in this procedure have an
effect on the performance of the device.
INFORMATION!
Current output and LCD display settings
When you do the Standard setup procedure, the measurement value on the first measurement page of
the LCD display (in Normal mode) automatically uses settings with the same parameters and values as
the current output settings (measurement variable, 0% range and 100% range). The first measurement
page shows "one value and bar" by default. If you must show one or more measurement values that are
different to the transmitted output signal, change the settings in the C6.4 1st Meas. Page and C6.5
2nd Meas. Page menus. For more data, refer to Function description on page 38
–
table C. Full Setup
menu (C6 Display).
Procedure
Screen
Steps
Description
•
2 × [>], 2 × [ ] and [>].
Default screen.
Enter Program mode and go to menu item A3
Login.
•
If it is the default password: 2 × [>], 5 ×
[
], [>] and 8 × [
]
•
[
^
] to confirm.
Enter the password used at this time for the
"Expert" access level. If it is the default
password, enter "0058".
•
[ ] and 2 × [>]
•
[
] or [
] for the selection of the
length unit (m, Cst., in, ft, mm or
cm).
•
[
^
] to confirm.
Push these buttons to start the Standard
Setup procedure.
Length unit. Make a selection from the list of
parameters.