Quick Start

For initial set up, we strongly recommend that you also refer to the relevant manual! 

05/2020 – 

4008215802

 – QS OPTITEMP TT 12 R R01 en 

OPTITEMP TT 12 R 

Programmable 2-wire transmitter

For Pt100 and Pt1000 input

 

Installation, assembly, start-up and maintenance may only be performed by appropriately trained personnel. 
Check the nameplate for operating conditions. 

Instruments must not be connected to power supply before reading instructions described in the manual. 

The responsibility as to the suitability, intended use of this device rests solely with the operator. 

For complete documentation (manuals, supplementary manuals, data sheets and certificates) please refer to 

www.krohne.com/Downloads

.  

1 Installation 

The TT 12 R is designed to be mounted on a 35 mm DIN Rail according to EN 60715 / DIN 50022.

Connect input, output and power supply according to “Electrical connection”.

The transmitter is configured from a mobile device via NFC

®

 communication, by using the app

OPTICHECK Temperature Mobile. The app is avaiable for free download on App Store and
Google Play

.

Ambient temperature 

Transmitter 

T

min.

 

T

max.

 

 [°C] 

[ °F] 

 [°C] 

[ °F] 

TT 12 R 

-40

-40

+85

+185

Factory settings 

Input 

Pt100 3W, 0 to 100 °C (equivalent to 212°F) 

Output 

4 to 20 mA 

Filtering level 

Response time 0.9 s 

Sensor error indication 

Upscale 

.

 

1. Fix the upper part of the transmitter onto the rail.

2. Press the lower part of the transmitter against the rail.

3. To remove the transmitter, use a screwdriver and bend the locking under the transmitter

 downwards. 

The cable is connected using a spring-cage connection. 
In order to minimize measuring errors ensure that  
the cable is securely fastened. 

1. Insert a screwdriver into the opening

 

above the

connection terminal block.

2. Insert the wire into the corresponding

connection terminal block.

Mounting and removal of the transmitter 

Springcage connection 