2

 DEVICE DESCRIPTION 

OPTIBAR 5060

www.krohne.com

04/2021 - 4003591803 - AD OPTIBAR 5060 Exia R03 en

2.5  Protection types

The pressure transmitter is designed with protection type intrinsic safety, protection level "ia" 

according to EN 60079-11 or IEC 60079-11.

The marking according to ATEX is:

II 1G, 1/2G, 2G Ex ia IIC T6…T1 Ga, Ga/Gb, Gb

The marking according to IECEx is:

Ex ia IIC T6...T1 Ga, Ga/Gb, Gb

The marking contains the following information:

II

Explosion protection, group II

1

Equipment category 1

G

Gas explosion protection

Ex ia

Intrinsically safe, level of protection "ia"

IIC

Gas group, suitable for gas groups IIC, IIB and IIA 

1/2

Equipment category 1/2

2

Equipment category 2

Ga

EPL, suitable for zone 0

Ga/Gb

EPL, suitable for zone 0 / zone 1

Gb

EPL, suitable for zone 1

T6...T1

Temperature class, suitable for temperature classes T6...T1

Table 2-1: Protection types

Summary of Contents for OPTIBAR 5060 eDP

Page 1: ...essure transmitter Category ATEX II 1G 1 2G 2G Ex ia IIC T6 T1 Ga Ga Gb Gb IECEx Ex ia IIC T6 T1 Ga Ga Gb Gb OPTIBAR 5060 Supplementary Instructions KROHNE 04 2021 4003591803 AD OPTIBAR 5060 Exia R03...

Page 2: ...ata 13 2 7 1 With electronics Z 4 20 mA H 4 20 mA HART A 4 20 mA HART with SIL qualification 13 2 7 2 With electronics P Profibus PA F Foundation Fieldbus 16 2 7 3 With electronics S or T for electron...

Page 3: ...rocess connection element a probe and the pressure measuring cell with optionally connected diaphragm seal As an option the display and adjustment module can also be integrated The OPTIBAR 5060 VGK5 6...

Page 4: ...is The X after the certificate number refers to special conditions for safe use of the device which have been listed in these instructions If needed the IEC certificate can be downloaded from the man...

Page 5: ...following identification plate can be found Figure 2 1 Example for an ATEX nameplate for an OPTIBAR 5060 1 Observe the instructions 2 Marking of notified body and CE marking 3 Hardware version 4 Produ...

Page 6: ...5060 1 Observe the instructions 2 Hardware version 3 Product name and type code 4 Permissible temperature range 5 Nominal range Permissible process pressure 6 Electronics power supply and signal outpu...

Page 7: ...the explosion protection according to directive 2014 34 EU ATEX regardless of the zone assignment is not applicable due to the lack of key safety data 2 4 Equipment category Category 1G equipment EPL...

Page 8: ...Gb The marking according to IECEx is Ex ia IIC T6 T1 Ga Ga Gb Gb The marking contains the following information II Explosion protection group II 1 Equipment category 1 G Gas explosion protection Ex ia...

Page 9: ...ring equipment category 1 2G EPL Ga Gb the process pressure of the media must be between 0 8 1 1 bar With the stated permissible ambient temperatures the 80 consideration of section 6 4 2 EN 1127 1 is...

Page 10: ...nics zone 1 Product temperature range sensor zone 1 T6 50 39 C 58 102 2 F 50 39 C 58 102 2 F T5 50 70 C 58 158 F 50 100 C 58 212 F T4 50 50 C 58 122 F 50 135 C 58 275 F T3 T2 T1 50 50 C 58 122 F 50 20...

Page 11: ...use as equipment of category 2G or zone 1 OPTIBAR PC 5060 130 C 266 F Figure 2 3 Temperature derating process temperature version 130 C 266 F 1 Ambient temperature housing 2 Process temperature OPTIB...

Page 12: ...ramic measuring cell process temperature max 150 C 302 F 4 Metallic ceramic measuring cell process temperature max 180 C 356 F 5 Metallic ceramic measuring cell process temperature max 200 C 393 F 6 P...

Page 13: ...rmanently mounted connection cable Li 0 62 H m must be taken into account additionally Table 2 7 Electrical data for OPTIBAR 5060 with integrated electronics Z H or A version with single chamber housi...

Page 14: ...ances Ci when using the supplied connection cable between OPTIBAR 5060 VGK5 6 D A W V C U 0 H T and OPTIBAR 5060 with electronics S or T Li 0 62 H m Ci wire wire 150 pF m Ci wire shield 270 pF m 1 In...

Page 15: ...AR 5060 VGK5 6 D A W V C U 0 H T with integrated electronics Z 4 20 mA H 4 20 mA HART or A 4 20 mA HART with SIL qualification version with double chamber housing D W or R Circuit for the display and...

Page 16: ...cally safe circuit Maximum values Ui 17 5 V Ii 500 mA Pi 5 5 W The equipment is suitable for connection to a fieldbus system according to the FISCO model EN 60079 11 e g Profibus PA or Ui 24 V Ii 250...

Page 17: ...to a certified intrinsically safe circuit Maximum values Ui 17 5 V Ii 500 mA Pi 5 5 W The equipment is suitable for connection to a fieldbus system according to the FISCO model EN 60079 11 e g Profib...

Page 18: ...owing cable inductances Li and cable capacitances Ci when using the supplied connection cable between OPTIBAR 5060 VGK5 6 D A W V C U 0 H T and OPTIBAR 5060 with electronics S or T Li 0 62 H m Ci wire...

Page 19: ...PTIBAR 5060 VGK5 6 D A W V C U 0 H T with integrated electronics P Profibus PA F Foundation Fieldbus version with double chamber housing D W or R Circuit for the display and adjustment module spring c...

Page 20: ...chamber housing version Supply and signal circuit terminals 5 6 7 8 in the electronics compartment In protection type intrinsic safety Ex ia IIC For connection to the intrinsically safe circuit of an...

Page 21: ...effective inner inductance Li is Li 5 H In the version with permanently mounted connection cable Li 0 62 H m must be taken into account additionally Supply and signal circuit II Terminals 7 8 in Ex i...

Page 22: ...quipment category 1G or 1 2G it is preferable to connect the OPTIBAR 5060 VGK5 6 D A W V C U 0 H T to appropriate equipment with galvanically isolated intrinsically safe circuits OPTIBAR 5060 VGK5 6 D...

Page 23: ...ls and the supplementary instructions must be observed at all times Install pressure transmitters so that they are not in a pneumatic flow excessive dust deposits over 5 mm and complete dust coverage...

Page 24: ...necessary analogue a suitable overvoltage arrester must be connected in front as protection against voltage surges according to EN 60079 14 or IEC 60079 14 section 12 3 4 3 Grounding To avoid the dang...

Page 25: ...r consideration of other tank installations and flow conditions in the tank This applies especially to suspension pressure transmitters and versions with distance tube lengths over 3 m 4 7 Setup with...

Page 26: ...5 NOTES 26 OPTIBAR 5060 www krohne com 04 2021 4003591803 AD OPTIBAR 5060 Exia R03 en...

Page 27: ...NOTES 5 27 OPTIBAR 5060 www krohne com 04 2021 4003591803 AD OPTIBAR 5060 Exia R03 en...

Page 28: ...solutions Engineering commissioning calibration maintenance and training services Head Office KROHNE Messtechnik GmbH Ludwig Krohne Str 5 47058 Duisburg Germany Tel 49 203 301 0 Fax 49 203 301 10389...