Control flame height
By default, the control flame height is set to the maximum and does not require manual
adjustment. The thermocouple head should be within reach of the control flame.
Gas outlet pressure regulation
1. Connect a pressure gauge to the outlet pressure measuring point (diameter 9
mm). To do this, first remove the screw in the connector and then connect the
measuring device.
2. Start the device.
3. The pressure regulator is located in the upper part of the controller housing. To
enable adjustment, remove the plastic plug (Fig. 21).
4. Turn the regulator screw to set the desired pressure on the main burner (high
flame). To increase the pressure, turn the regulator screw clockwise, or reduce it
by turning the screw counterclockwise.
5. After setting the proper pressure, secure the regulator screw by installing the
plastic plug.
6. If no other adjustments are required, disconnect the pressure gauge and secure
the outlet pressure measuring point connector.
If, despite the adjustment, the desired pressure has not been achieved, check the gas
supply pressure by connecting the pressure gauge to the input pressure measuring
point. If the inlet pressure is within the normal range, replace the controller; otherwise,
take the necessary steps to ensure proper gas pressure.
Fig. 21. Method of regulating the outlet pressure