![Kraft Powercon PRX 110/16 Manual Download Page 13](http://html.mh-extra.com/html/kraft-powercon/prx-110-16/prx-110-16_manual_2000158013.webp)
13
KraftPowercon Sweden AB, Hjalmar Petris väg 49, 352 46 Växjö, Sweden, Tel: 0470-705200, Fax: 0470-705201,
www.kraftpowercon.com
6
INSTALLATION INSTRUCTIONS
6.1
SAFETY INSTRUCTIONS
WARNING!
This product contains dangerous voltage that when touched can cause electric shock, burns
or death. Protective earth must always be connected in a reliable way to avoid the risk of live parts in the
equipment in the event of faults. No live parts are permitted during installation. The product must be
installed by qualified personnel (see
) section.
WARNING!
Check both before and after setting-up that the equipment does not have any mechanical
damage. Check that the equipment and individual rectifier modules have the intended rated voltage.
Cables for input and output power must be correctly dimensioned to avoid fire hazard.
6.2
GENERAL
Installation of the parts that belong to the monitoring unit are not dealt with in this manual. For
complete installation instructions these instructions should therefore be used in combination
with the installation instructions included in the
Manual for monitoring unit PCM2
.
6.3
STORAGE AND PROTECTION
Storage is to be in a dry area and at a temperature that does not exceed the -40 to +70 °C range.
6.4
MOUNTING
The equipment is designed for wall mounting indoors in a room that is dry, clean and free from
conductive dust. In order to guarantee free air flow for all ventilation openings, at least 25mm
of free space should be left on each side.
The rear plate of the equipment has four mounting holes shaped as keyholes.
In order to fit the key hole, the screw should have a diameter of a max of 6
mm and the screw head diameter 9.5 - 13.5 mm. See also dimension diagram
Before mounting, the cover must be removed and the rectifier modules
removed temporarily, partly because the two upper mounting holes are only accessible via the
opening for the rectifier modules but also by considerably lower weight.
Attention!
Loosen the earth wire on the underside of the device before removing the cover. Do
not forget to restore the earth wire when the cover put back.
WARNING!
The equipment may cause personal injury or damage to property if dropped. Use secure
lifting aids where appropriate. Make sure the mounting screws and their attachments to the wall can
easily and safely handle the weight of the equipment.