56
8.6. Battery CONNECTION
Be careful!
Only use properly insulated tools to prevent accidental electric
shock or short circuits. If insulated tools are not available, use
electrical tape to cover the entire exposed metal surfaces of the
available tools except their tips.
Be careful!
The plug connector must be connected only by trained
electricians.
Be careful!
The plug connector must be connected only by trained
electricians.
Be careful!
A two-pole DC circuit breaker with over-current protection
(voltage rating not less than 600 V and current rating not less
than 40 A) should be installed between the inverter and the
battery.
8.6.1 Connecting the Power Cable
All power cables are equipped with water-proof direct plug-in connectors, which match
the battery terminals at the box of the inverter.
Connect terminals on the battery side according to the following figure. If you have any questions,
please contact customer service personnel