Acces s ing data v ia PRO F I BUS
36
Operating manual for PROFIBUS fieldbus | DOC01185928-0008 | 2016-12 | V1.8 EN
4.2.2
Process data In which can be parameterised
The remaining 4 process variables (2 – 6) can be parameterised with the help of the INVEORpc tool
using parameters 6.110 to 6.113. The available process variables of the parameter settings can be
found in the following table.
Seri
al
no.
Data type
SW
vers.
Designation
Unit
Description
0
DWORD
*
03.02
Digital relay outputs
1
Control of outputs:
Bit 0 = Dig Out 1
(Parameter 4.150 = 25)
Bit 1 = Dig Out 2
(Parameter 4.170 = 25)
Bit 2 = Relay 1
(Parameter 4.190 = 25)
Bit 3 = Relay 2
(Parameter 4.210 = 25)
Bit 4 = Virt Out 1
(Parameter 4.230 = 25)
1
REAL
03.02
Analogue Out 1
V
Control of analogue output
2
DWORD
03.04
Customised
input variable 1
1
Customised input variable
soft PLC (32 bit)
4
REAL
03.04
Customised
input variable 2 / PID
actual value
-
Customised input variable
soft PLC
5
REAL
03.04
Customised
input variable 3
-
Customised input variable
soft PLC
6
REAL
03.04
Customised
input variable 4
-
Customised input variable
soft PLC
Tab.: 7 Process data In which can be parameterised
* DWORD data type corresponds to UINT32 = 4 bytes
4.3
Non-cyclic data access / parameters
IMPORTANT INFORMATION
Only parameters with an access level of 2 or less can be accessed
(see list of parameters in operating manual).
Access for both reading and writing is possible.
IMPORTANT INFORMATION
You will find detailed information about the parameters in the "Parameters" chapter of the
"INVEOR drive controller" operating manual.