Setting up wallbox in the KSEM
© 2022 KOSTAL Solar Electric GmbH
78
7.3 ENECTOR with KOSTAL Smart Energy Meter
for blackout protection (house connection
monitoring)
If the ENECTOR is connected to a KOSTAL Smart Energy Meter and this is only to be used
for blackout protection (house connection monitoring), the RS485 interface used must be
configured in the KOSTAL Smart Energy Meter.
Only then can the ENECTOR read data from the KOSTAL Smart Energy Meter.
Do this by performing the following steps:
1.
Call up the online interface of the KOSTAL Smart Energy Meter.
2.
Call up the Modbus configuration under
Modbus settings
.
3.
Activate the RS485 interface connected to the ENECTOR (e.g.
RS485 B)
.
Select the
User-defined
value under
Presettings
and configure the following settings
under
Advanced.
Parameter
Value
Interface
RS485 B
Presetting
User-defined
Mode
Slave
Slave address
2
Baud rate
57600
Data bits
8
Parity
None
Stop bit
2
1.
Press the
Save
button to adopt the settings.
✔
The interface to the ENECTOR has been set up in the KOSTAL Smart Energy Meter.