0000
Protocol ID
2 Bytes, 0000 = Modbus protocol
0004
Length Field
2 Bytes, number of following bytes
FF
Unit ID
1 Byte, FF = Master device
02
Function Code
1 Byte, 02 = Read
01
Data Length
1 Byte, Data Length
FF
Data
1 Byte, Binary of 0xFF is "1111 1111", 1 is closed, 0 is open
Take the case of acquisition 2 channels DO as an example. The command is as follows:
0x 000100000006FF0100640002
Command
Field
Description
0001
Transaction ID
2 Bytes, identification of a Modbus Request/Response transaction
0000
Protocol ID
2 Bytes, 0000 = Modbus protocol
0006
Length Field
2 Bytes, number of following bytes
FF
Unit ID
1 Byte, 0xFF = Master device
01
Function Code
1 Byte, 01 = Read
0064
Starting Address
2 Bytes, address of the first register
0002
Quantity of Registers
2 Bytes, the number of required registers
Assuming the DO1 status is closed and the DO2 status is open. The command returned by the device is as follows:
0x000100000004FF010101
Command
Field
Description
0001
Transaction
ID
2 Bytes, identification of a Modbus Request/Response transaction
0000
Protocol ID
2 Bytes, 0000 = Modbus protocol
0004
Length Field
2 Bytes, number of following bytes
FF
Unit ID
1 Byte, 0xFF = Master device
C2000-A2-SDD8020-DD3 User Manual
26 / 33