7.4.2
Digital Input
No Item
Descriptions
1
DI-
□
Type
Set the operation type for digital input.
Setting range: None, Rec/Stop, Alarm Reset, Alarm ON, Capture
2
DI-
□
Status
Set digital input operation status.
(only when DI type is set as ‘Record/Stop’)
- Edge: When supplying digital input over 0.3 sec, the recording starts.
When re-supplying it, the recording stops.
- Level: When shorting digital input over 0.3 sec, the recording starts.
When opening it, the recording stops.
3
Alarm Reset
When DI type is set as ‘Alarm Reset’, select the desired relay to reset the
alarm.
4
Alarm ON
When DI type is set as ‘Alarm ON’, select the desired relay to turn ON the
alarm.
5
Relay-
□
Set alarm relay enable or disable.
Summary of Contents for KRN1000 SERIES