background image

140

394149/D

RS-232 serial line connection using three wires

An RS-232 serial line connection using three (3) wires and NMEA datagrams is a
common way to connect the EK80 to external devices.

A

Local connection

B

Connection on remote device

C

Female 9-pin D-Subminiature connector

D

Male 9-pin D-Subminiature connector

Unless otherwise specified, this cable must be provided
by the installation shipyard. Note that this cable does
not support all the signals in the standard RS-232
specification.

Minimum cable requirements

Conductors

: 2 x 4 x 0.5 mm

2

Screen

: Overall braided

Voltage

: 60 V

Maximum outer diameter

: Defined by the plugs and/or the cable gland

If you need to install a very long cable, increase the cross section.

Related topics

Cable drawings and specifications, page 136
Cable layout and interconnections, page 85

Simrad EK80 Installation Manual

Summary of Contents for Simrad EK80

Page 1: ...kongsberg com simrad Simrad EK80 INSTALLATION MANUAL ...

Page 2: ......

Page 3: ...ion of other transceivers supported by the EK80 see the relevant publications For information about the practical use of the EK80 refer to the EK80 Reference Manual and or the EK80 context sensitive On line help Caution You must never set the EK80 to ping unless the transducer is submerged in water Most transducers are damaged beyond repair if they transmit in open air Prevent inadvertent use of t...

Page 4: ...as designed Improper use or maintenance may cause damage to the equipment and or injury to personnel You must be familiar with the contents of the appropriate manuals before attempting to operate or work on the equipment Kongsberg Maritime disclaims any responsibility for damage or injury caused by improper installation use or maintenance of the equipment Disclaimer Kongsberg Maritime AS endeavour...

Page 5: ...upply voltage requirements 37 Uninterruptible power supply UPS requirements 37 Cables and wiring requirements 38 Compass deviation requirements 38 Noise sources 38 Dry docking requirements 39 Requirement for classification approval 39 Network security 40 Support information 41 PREPARATIONS 43 Installation summary 44 About installation drawings 46 Tools equipment and consumables required for EK80 i...

Page 6: ...er 72 Installing the Enix Processor Unit 74 Installing the Ethernet switch 76 Mounting the WBT Cabinet 78 Mounting the drawers in the WBT Cabinet 81 Installing the transducer s 83 CABLE LAYOUT AND INTERCONNECTIONS 85 Read this first 86 Reducing electrical noise 86 Cable plans 88 About the cable plans 88 Topside cable plan 89 Sonar room cable plan with one transceiver 90 Sonar room cable plan with ...

Page 7: ...37 Ground cable 139 RS 232 serial line connection using three wires 140 RS 232 serial line connection using five wires 141 RS 422 serial line connection using five wires 142 RS 232 used as synchronization trigger input or output 143 RS 485 serial line connection using two or four wires 144 Moxa CP114EL I Serial line adapter 145 RJ45 High speed Ethernet cable 1000Base t 147 Battery power cable 148 ...

Page 8: ...Visual inspection of the Wide Band Transceiver WBT 193 Visual inspection of the WBT Cabinet 195 Visual inspection of the EC150 3C Power Supply Unit 197 Turning on the EK80 for the first time 199 Setting up summary 199 Installing the EK80 operational software 201 Turning on the EK80 to Passive mode 202 Obtaining and installing the software license 203 Defining the IP address on the Processor Unit n...

Page 9: ...d software versions 261 Verifying the communication with the course gyro 263 Verifying the communication with a navigation system GPS 265 Verifying the communication with speed log 267 Verifying the communication with the motion reference unit MRU 269 Verifying the communication with a synchronization system 271 Making a noise speed curve to determine vessel noise 273 Turning off the EK80 276 Inst...

Page 10: ...nd outline dimensions 296 WBT Cabinet weight and outline dimensions 297 Environmental requirements 298 Display environmental requirements 298 Processor Unit environmental requirements 298 Wide Band Transceiver WBT environmental requirements 299 LBG408A R2 Ethernet switch environmental requirements 299 WBT Cabinet environmental requirements 299 Compass safe distance 301 Display compass safe distanc...

Page 11: ...tation boxes after arrival 323 Specifications for storage prior to installation or use 324 Unpacking instructions 325 Unpacking standard parts and units 326 Unpacking mechanical units 327 Unpacking electronic and electromechanical units 328 Unpacking transducers 329 Specifications for storage after unpacking 330 Installation Manual ...

Page 12: ...10 394149 D Simrad EK80 ...

Page 13: ...ronic and mechanical products Installation instructions The instructions provided in this manual must be followed carefully to ensure optimal performance As a guide installation procedures are presented in the order they must be done The equipment described in this manual includes the complete system with relevant cabinets Units provided locally by the customer installation shipyard or local repre...

Page 14: ...he Drawing file chapter in this manual The source drawings normally in AutoCad format can be downloaded from our website https www kongsberg com ek80 Online information All end user manuals provided for operation and installation of your Simrad EK80 can be downloaded from our website https www kongsberg com ek80 Our website also provides information about other Simrad products Registered trademark...

Page 15: ...ant page 14 System description page 15 System diagram page 17 Main system units page 19 Scope of supply page 25 General safety rules page 36 Installation requirements page 37 Network security page 40 Support information page 41 Simrad EK80 ...

Page 16: ...ed When you do not use the EK80 turn off the display and the Processor Unit If you are not using the EK80 for a long period of time we recommend that you turn off the transceiver s When you are docking your vessel You must never turn on the EK80 when the ship is in dry dock The transducer s may be damaged if the EK80 transmits in open air To prevent inadvertent use of the EK80 pull out the mains p...

Page 17: ...ects Related topics Simrad EK80 page 13 Support information page 41 System description The Simrad EK80 is the most modern high end split beam scientific echo sounder in the scientific market Based on more than 60 years of research and development in close collaboration with leading marine scientists this wideband echo sounder system has succeeded the famous EK60 which became an international stand...

Page 18: ...ration The EK80 is specifically suited for permanent installation onboard a research vessel It is still compact and a natural choice for portable use The Simrad EK80 is well suited for a number of applications Assessment of fish biomass and distribution Species identification and discrimination Plankton research Habitat mapping Behavioral studies Environmental research Oil and gas detection The ec...

Page 19: ...o meet your operational and functional requirements Post processing software is provided by third party suppliers See our website for more information Unless otherwise specified in a contract the display and the Ethernet switch are not included in the standard delivery from Kongsberg Maritime These are commercial items that can be purchased locally A Display B Processor Unit C Ethernet switch D Wi...

Page 20: ... unit It can be used either as an acoustic Doppler current profiler ADCP instrument to measure water current or as a split beam echo sounder It can not operate these two functions simultaneously The ADCP hardware can be added to an existing EK80 system You can also use the EK80 as an exclusive ADCP instrument A Display B Processor Unit C Ethernet switch D Power Supply Unit E Simrad EC150 3C F Wide...

Page 21: ...0 software supports all display sizes The visual quality of the EK80 presentation depends on the quality of your graphic adapter and display Note The display is not a standard part of the EK80 delivery This is a commercial item that can be purchased locally The chosen display must be designed for maritime use and it must meet the minimum performance specifications You must also make sure that the ...

Page 22: ... to the ship s network you need two Ethernet adapters The Processor Unit is normally mounted on the bridge or in a scientific laboratory Note The Ethernet adapter communicating with the Wide Band Transceiver WBT must offer a Receive Buffers function This parameter must be set to its maximum value if more than one Wide Band Transceiver WBT is used The Processor Unit is not a standard part of the EK...

Page 23: ... electronics The receiver is designed for low noise and it can handle input signals spanning a very large instantaneous dynamic amplitude range All targets are correctly measured The transceiver operates within a large frequency band and supports single frequencies frequency sweep chirp and user defined wave forms The Wide Band Transceiver WBT is designed for applications where performance is the ...

Page 24: ...be The WBT Tube is a depth rated version of the highly efficient Wide Band Transceiver WBT used by marine research vessels all around the world The WBT Tube is contained in a pressure rated tube It is designed for long term use down to 4000 metres water depth Typical deployments include moorings subsea structures for environmental monitoring and probes The shape and pressure rating makes the WBT T...

Page 25: ...Several transducers fit into more than one category For more information about our transducers see our website https www kongsberg com simrad The installation of the transducer or transducers is not described in detail in this manual See the documentation provided with each transducer Related topics Main system units page 19 Simrad EK80 page 13 Simrad EC150 3C The Simrad EC150 3C is a 150 kHz phas...

Page 26: ...unting ring is welded into the hull plating The transducer can also be flush mounted in the same manner at the bottom of a blister or a drop keel The transducer cable penetrates the hull using a cable gland This cable gland consists of a bushing washers a rubber gasket and a packing nipple Related topics Main system units page 19 Simrad EK80 page 13 Simrad EK80 Installation Manual ...

Page 27: ...box WBT 10 30 kHz 402578 WBT 25 50 kHz 402579 WBT 45 90 kHz 402580 WBT 85 170 kHz 402581 WBT 150 300 kHz 402582 WBT 250 500 kHz 402583 Transceiver Unit Power Supply Unit Installation bracket for WBT Power supply Documentation Software Software license An order number is the unique identifier used when a unit or an item is ordered The number identifies a complete unit and relevant accessories packe...

Page 28: ... 394149 D Related topics Scope of supply page 25 Simrad EK80 page 13 385609 Processor Unit dimensions page 310 388697 Wide Band Transceiver WBT outline dimensions page 308 Simrad EK80 Installation Manual ...

Page 29: ...provided that the display meets the minimum requirements The chosen display must be designed for maritime use and it must meet the minimum performance specifications You must also make sure that the chosen display supports the video formats provided by the Processor Unit We suggest that you purchase a large high resolution display Kongsberg Maritime may provide a suitable display Display Order num...

Page 30: ...operating system requirements provided by Microsoft Note In this publication the computer is referred to as the Processor Unit A suitable computer may be provided with the EK80 Consult your local dealer or agent for more information Item Order number In the box Processor Unit 395236 Computer Software Power cable Serial line connectors and adapters An order number is the unique identifier used when...

Page 31: ...e of supply page 25 Simrad EK80 page 13 Motion Reference Unit MRU ADCP operations cannot take place without input from a motion reference unit MRU In order to operate correctly with the EC150 3C the EK80 requires input from a motion reference unit MRU Note Without the input from a motion reference sensor the EK80 will not be able to compensate for the vessel movements The input must be provided on...

Page 32: ... use this format no other formats are accepted Kongsberg Maritime may provide a suitable motion reference unit Consult your local dealer or agent for more information Motion Reference Unit MRU Order number In the box Seatex MRU Motion Reference Unit MRU Documentation An order number is the unique identifier used when a unit or an item is ordered The number identifies a complete unit and relevant a...

Page 33: ...en custom drawers and each of these will hold one Wide Band Transceiver WBT and its power supply An Ethernet switch and a power distributor panel are included the bottom of the cabinet The WBT Cabinet is delivered with six drawers Each WBT Drawer will hold one Wide Band Transceiver WBT The WBT Drawer is designed to fit into any commercial 19 inch rack The drawers can be ordered separately for use ...

Page 34: ...t your local dealer or agent for more information Related topics Additional optional items page 31 Scope of supply page 25 Simrad EK80 page 13 Minimum display requirements page 304 Global positioning system GPS A global positioning system GPS must be connected to the EK80 When a global positioning system GPS connected to the EK80 the vessel s current geographical position can be presented in the u...

Page 35: ...interface A course gyro is not a part of the EK80 delivery Note Without the input from a course gyro the EK80 will not be able to present correct navigational information In most cases a suitable course gyro is already installed on the vessel A global positioning system GPS with a compatible output format can also be used The course gyro interface requirements are Serial line Standard NMEA 0183 da...

Page 36: ... for motion data If you choose to use this format no other formats are accepted Kongsberg Maritime may provide a suitable motion reference unit Consult your local dealer or agent for more information Motion Reference Unit MRU Order number In the box Seatex MRU D Motion Reference Unit MRU Documentation An order number is the unique identifier used when a unit or an item is ordered The number identi...

Page 37: ...wer supply units are not included in the standard EK80 delivery These items must be purchased locally Several commercial types are available To choose the best power solution for your EK80 installation consider environmental conditions space available the availability and duration of the batteries and the power requirements of the EK80 Note Make sure that the Uninterruptible Power Supply UPS does ...

Page 38: ... EK80 system Use the main circuit breaker and label the breaker with a warning sign that informs others that maintenance or installation work is in progress on the system For safety reasons two persons must always be present during troubleshooting with power ON Read and understand the applicable first aid instructions related to electric shock Whenever maintenance is in progress it is essential th...

Page 39: ...or detailed requirements see the relevant data sheets and end user documentation Maximum transient voltage variations on the main switchboard s bus bars must not exceed 15 to 20 of the nominal voltage except under fault conditions Related topics Installation requirements page 37 Simrad EK80 page 13 Uninterruptible power supply UPS requirements We recommend that the EK80 system is powered using an ...

Page 40: ...pass Once the installation is complete the vessel must be swung with the EK80 in both operative and inoperative modes The shipowner and captain are responsible for updating the compass deviation table accordingly with regard to the vessel s national registry and corresponding maritime authority Related topics Installation requirements page 37 Simrad EK80 page 13 Noise sources The operational perfo...

Page 41: ...vessel s hull special considerations must be made prior to dry docking Make sure that ample clearance is provided under the transducers when you are placing the vessel in dry dock Do not place supporting blocks or structures in the vicinity of the transducers Note down the location of each transducer on the vessel s docking plan Prior to dry docking turn off the EK80 If necessary disengage the cir...

Page 42: ... information regarding the complete system installation on any vessel Systems provided by Kongsberg Maritime are regarded as stand alone offline systems They are stand alone even though they may be connected to a network for sensor interfaces and or data distribution Note No network safety applications are installed on Kongsberg Maritime computers The computers are therefore not protected against ...

Page 43: ...mrad com Spain Company name Simrad Spain S L U Address Partida Atalayes 20 03570 Villajoyosa Spain Telephone 34 966 810 149 Telefax 34 966 852 304 Website https www kongsberg com simrad E mail address simrad spain simrad com France Company name Simrad France Address 5 rue de Men Meur 29730 Guilvinec France Telephone 33 298 582 388 Telefax 33 298 582 388 Website https www kongsberg com simrad E mai...

Page 44: ...1 3359 Website https www kongsberg com simrad E mail address simrad asia simrad com Korea Company name Kongsberg Maritime Korea Ltd Address 1101 Harbor Tower 113 1 Nampodong 6 Ga Jung Gu Busan 600 046 Korea Telephone 82 51 242 9933 Telefax 82 51 242 9934 Website https www kongsberg com simrad E mail address simrad korea simrad com China Company name Kongsberg Maritime China Ltd Address 555 Chuanqi...

Page 45: ...age 44 About installation drawings page 46 Tools equipment and consumables required for EK80 installation page 46 Personnel qualifications page 47 Where to install the transducer page 48 Acoustic noise page 54 Vessel coordinate system page 61 Preparations ...

Page 46: ...as the relevant work standards and mounting procedures If required all documents provided by the shipyard for the physical installation of the EK80 must be approved by the vessel s national registry and corresponding maritime authority and or classification society Such approval must be obtained before the installation can begin The shipowner and shipyard doing the installation are responsible for...

Page 47: ...ed locally Installing the EK80 hardware units page 64 4 Install the cables between the EK80 system units Observe the relevant cable plan procedures as well as the general requirements for cabling This is described in the Cable layout and interconnections chapter Observe the relevant cable plan procedures as well as the general requirements for cabling Cable layout and interconnections page 85 5 In...

Page 48: ...rom our website Most documents are available in PDF and or AutoCad DWG formats https www kongsberg com simrad Related topics Preparations page 43 Tools equipment and consumables required for EK80 installation In order to do the EK80 installation all necessary tools and equipment for mechanical work cabinet installation and electrical wiring must be available It is not practical to provide a detail...

Page 49: ... craftsmen must be available Naval architects Welders Electricians Project manager Note The quality of the welding is critical to the safety of the vessel Welding must only be done by a certified welder If applicable the final installation welds must be approved by the vessel s national registry the corresponding maritime authority and or classification society Observe the relevant rules and regul...

Page 50: ...a safe distance from bow thruster s page 51 Summary and general recommendations page 52 Mount the transducer deep In order to achieve the best possible EK80 performance mount the transducer as deep as possible under the vessel s hull There are several reasons for this recommendation Flow noise Consider the situations when the vessel is unloaded and pitching in heavy seas The vessel is riding high ...

Page 51: ...sed by slamming Related topics Where to install the transducer page 48 Preparations page 43 Avoid protruding objects near the transducer Objects protruding from the hull will generate turbulence and flow noise This will reduce the EK80 performance Protruding objects may be zinc anodes transducers or even the vessel s keel Holes and pipe outlets are also important noise sources as well as rough sur...

Page 52: ... layer increases in thickness when it becomes turbulent The boundary layer is thin in the forward part of the vessel hull and increases as it moves aft The thickness depends on ships speed and on the roughness of the hull All objects sticking out from the hull or dents in the hull will disturb the flow and will increase the thickness of the boundary layer When the flow speed is high the turbulence...

Page 53: ...rations page 43 Mount the transducer at a safe distance from bow thruster s Bow thruster propellers are extremely noisy When you decide where to place the transducer you must consider the noise created by most bow thrusters When in operation the noise and cavitation bubbles created by the thruster may make your EK80 Wide band scientific echo sounder useless almost no matter where the transducer is...

Page 54: ...nsducer face For this reason the recommended transducer location is normally in the fore part of the hull well ahead of the noise created by the bow wave The maximum distance from the bow is normally equal to one third of the total water line length of the hull Note Mounting the transducer more than 10 15 meters from the bow may cause problems with the turbulent flow A Transducer B Inclination ang...

Page 55: ... B Transducer location This applies to the vessel in normal trim and speed Important The transducer must not have a negative inclination angle compared to water flow Do not place a transducer in the vicinity of protruding objects and especially not close behind them Make sure that the surface of the resulting installation is as smooth and streamlined as possible Related topics Where to install the...

Page 56: ...ntributing to the performance of the hydroacoustic equipment used on board a vessel are The quality and properties of the transmitted signal The quality of the receiving system The operational settings made during operation The properties of the target s The signal to noise ratio The majority of these factors can neither be controlled nor improved by means of installation methods or transducer loc...

Page 57: ...g types of noise Self noise Ambient noise Electrical noise Reverberation Fishing gear noise A The transducer can pick up noise from Biological disturbances Interference Cavitation Propeller noise Flow noise Acoustic noise from other hydroacoustic systems B The transducer cable is long and may pick up electric noise from generators pumps cooling systems and other electric or electromechanical devic...

Page 58: ...ern vessels are normally equipped with a lot of electric instruments such as hydroacoustic systems radars navigation systems and communication equipment Any electric instruments may in some cases cause electrical interference and noise International regulations and certifications are used to control and reduce this but even these are limited if the electrical systems are poorly installed and or ma...

Page 59: ...iscrete frequency while all other flow noise will have a wide frequency spectrum Image from U S Navy in the public domain Flow noise The upper water layers of the sea contain a myriad of small air bubbles created by the breaking waves When the hull moves through water it will cause a disturbance and this will generate friction The friction zone is called the flow boundary layer The flow in this bo...

Page 60: ...itude Interference usually refers to the interaction of waves that are correlated or coherent with each other either because they come from the same source or because they have the same or nearly the same frequency Interference effects can be observed with all types of waves for example light radio acoustic surface water waves or matter waves https en wikipedia org wiki Wave_interference April 201...

Page 61: ... or sensitive electronic circuitry At higher frequencies where rather wide bandwidths are necessary the noise from components transistors or other analogue electronic may be a limiting factor Related topics Acoustic noise page 54 Preparations page 43 Some means to reduce acoustic noise Several factors are contributing to the performance of the hydroacoustic equipment used on board a vessel Careful...

Page 62: ...ines and equipment must be fixed to rigid foundations to avoid vibrations Any hull structure that may vibrate should be damped or coated to reduce the vibrations The use of shock absorbers or floating rafts may sometimes reduce this noise The structure borne noise may be reduced by isolation for example by providing vibration clamping between the transducer and the hull structure Reducing propelle...

Page 63: ... boxes other potential noise sources Make sure that all units are properly grounded Use shielded cables with correct grounding Separate the EK80 cables from other cables with high voltages large currents or transients Place all high voltage power cables in metal conduits If you more than one Wide Band Transceiver WBT install these in such a way that the transducer cables have the maximum distance ...

Page 64: ...sitive value for X means that a sensor or a reference point is located ahead of the reference point origin B The Y axis is the transverse direction of the vessel and in parallel with the deck A positive value for Y means that a sensor or a reference point is located on the starboard side of the reference point origin C The Z axis is vertical and in parallel with the mast A positive value for Z mea...

Page 65: ...zontal distances from a single reference point the origin The physical location of the motion reference unit MRU is often the most important sensor to define For many systems the vessel heading is also a critical measurement Illustration In this example a second reference point has been established It is defined with three positive offset values for X Y and Z All values are positive because the ne...

Page 66: ...r WBT in a 19 rack page 67 Installing the WBT Power Supply page 69 Installing the display page 71 Installing a commercial computer page 72 Installing the Enix Processor Unit page 74 Installing the Ethernet switch page 76 Mounting the WBT Cabinet page 78 Mounting the drawers in the WBT Cabinet page 81 Installing the transducer s page 83 Simrad EK80 Installation Manual ...

Page 67: ...rise the normal tools for electronic and electromechanical tasks This includes different screwdriver types pliers spanners a cable stripper a soldering iron etc Each tool must be provided in various sizes We recommend that all tools are demagnetized to protect your equipment Context The unit can be mounted in any direction and on any surface provided that the environmental requirements are met Not...

Page 68: ...ble to avoid overheating f Make sure that the installation method allows for the physical vibration movements and forces normally experienced on a vessel Note In order to allow for future maintenance we recommend to mount the unit with its cables and connectors available for easy access 3 Make sure that the chosen location meets the installation requirements 4 Place the Wide Band Transceiver WBT i...

Page 69: ...ansceiver must be installed on a dedicated drawer in the rack A Mounting bolts for the Wide Band Transceiver WBT B Mounting bracket not used C Holes for fastening and securing the cables D Mounting bolts for the drawer assembly E Mounting bolts for the drawer Note Ensure maximum physical distance between the Wide Band Transceiver WBT and the Power Supply Unit This is important to reduce noise Plac...

Page 70: ...ration movements and forces normally experienced on a vessel Note In order to allow for future maintenance we recommend to mount the unit with its cables and connectors available for easy access 3 Make sure that the chosen location meets the installation requirements 4 Place the Wide Band Transceiver WBT on the WBT Drawer 5 Mount the transceiver and the power supply using the brackets bolts and nu...

Page 71: ...the unit You can mount it on a bulkhead using the optional wall bracket You can mount it using any means available These points must all be considered to reduce electrical noise on an EK80 system If you more than one Wide Band Transceiver WBT install these in such a way that the transducer cables have the maximum distance to the power and Ethernet cables Ensure maximum physical distance between th...

Page 72: ...itable bolts or screws b Place the power supply in the bracket so that the small lamp is visible 6 Desktop installation a Place the unit in a suitable location b Position and fasten the unit using the bracket and the mounting screws 7 Ad hoc installation a Place the unit in a suitable location horizontally or vertically b Position and fasten the unit using any means available 8 Connect the cables ...

Page 73: ...cation and the necessary tools 2 Observe the installation requirements a Check the installation requirements provided by the manufacturer b Position the display so that it is best protected from glare which reduces readability c Observe the compass safe distance d Make sure that enough space is made available for maintenance purposes e Make sure that adequate ventilation is available to avoid over...

Page 74: ... computer refer to the manual supplied by the manufacturer Note Make sure that the chosen computer meets the EK80 requirements The design and construction must allow for marine use and the computer must be able to withstand the movements and vibrations normally experienced on a vessel Verify that you have easy access to cables and connectors and that the computer can be installed in a safe and sec...

Page 75: ... front and rear mounted connectors and devices It is also important that you allow for easy access to all the cables and enough space for inspection maintenance and parts replacement If relevant make sure that the space allows you to open the computer for unobstructed access to its internal parts Note Make sure that you can access both the rear and front side of the computer after it has been inst...

Page 76: ...ough the computer chassis B Each rail provides two holes for mounting to a flat surface C Remove this bolt to release the rail from the bottom plate Context If you intend to mount the Enix Processor Unit in a 19 rack you can disregard this procedure However you may then wish to remove the bottom plate and shock absorbers as described in this procedure as these will not be required Procedure 1 Prep...

Page 77: ...een installed 5 Install the computer a Turn the Processor Unit cabinet upside down and remove the bottom plate A with the shock absorbers b Observe the four holes in the shock absorbers and the bottom plate B c Using the bottom plate as a template mark the position of the mounting bolts on the foundation d Mount the bottom plate back on the Processor Unit cabinet e Disassemble the two base rails f...

Page 78: ...l tools are demagnetized to protect your equipment A suitable location for Ethernet switch must be defined prior to installation If you place the unit on the bridge observe the compass safe distance Procedure 1 Prepare the location and the necessary tools 2 Observe the installation requirements a Check the installation requirements provided by the manufacturer b Observe the compass safe distance c...

Page 79: ...les make sure that they are all properly secured and able to withstand the vibration and movements of the vessel Related topics Installing the EK80 hardware units page 64 Equipment handling page 320 Compass safe distance page 301 Installing the EK80 hardware units ...

Page 80: ...re required for this task Power drill Welding equipment We recommend that you install the WBT Cabinet before you install the WBT Drawers and the transceivers Illustration Use bulkhead support bracket s to make installation easier Place the cabinet on U shaped steel profiles to make more room for the cables Context The cabinet is installed using shock absorbers It is mounted on the deck and secured...

Page 81: ...etween the Wide Band Transceiver WBT and the Power Supply Unit This is important to reduce noise Place the power supplies on a dedicated drawer at the bottom of the cabinet How to install the cables in the WBT Cabinet is described on drawing 444425 The drawing can be downloaded from our website The drawing is also included on the EK80 USB Procedure 1 Prepare the installation of the cabinet a Obser...

Page 82: ...ion drawings i If relevant design and manufacture bulkhead support bracket s and or U shaped steel profiles Note The use of U shaped profiles and bulkhead support bracket s is optional 2 Mount the U shaped profiles a Design manufacture and mount the U shaped steel profiles b Make sure that the profiles can withstand the full weight of the cabinet c Make the required mounting holes to accept the bo...

Page 83: ...drawers in the WBT Cabinet The WBT Cabinet can contain maximum seven custom drawers Each drawer will hold one Wide Band Transceiver WBT and its power supply The drawer is mounted in the same way as any other equipment designed for 19 racks using standard tools Prerequisites You must be equipped with a standard set of tools This tool set must comprise the normal tools for electronic and electromech...

Page 84: ...of the cabinet How to install the cables in the WBT Cabinet is described on drawing 444425 The drawing can be downloaded from our website The drawing is also included on the EK80 USB Procedure 1 Decide where in the cabinet you wish to mount the drawers 2 Mount each drawer using six bolts on each side D 3 Pull out the drawer 4 Remove the bracket B 5 Mount the Wide Band Transceiver WBT using the bol...

Page 85: ...must be based on The vessel drawings The shape and properties of the hull Make sure that all possible considerations are made to reduce noise 2 Based on the shape of the transducer housing and the mounting devices available determine the installation method 3 Design manufacture and mount the necessary fairing installation blister keel box and or tank that is required to mount the transducer 4 Desi...

Page 86: ...84 394149 D Related topics Installing the EK80 hardware units page 64 Equipment handling page 320 Compass safe distance page 301 Simrad EK80 Installation Manual ...

Page 87: ... page 86 Cable plans page 88 List of EK80 cables page 94 Installing the EK80 cables page 97 Connections to specific hardware items page 110 Setting up the EK80 in a synchronized system page 126 Cable drawings and specifications page 136 Basic cable requirements page 167 Cable layout and interconnections ...

Page 88: ...d by Kongsberg Maritime as a part of the EK80 delivery They may also be included with third party items that are used with the EK80 All electronic installations and corresponding wiring must be in accordance with the vessel s national registry and corresponding maritime authority and or classification society Note It is very important that all cables are properly installed and correctly terminated...

Page 89: ...nding Separate the EK80 cables from other cables with high voltages large currents or transients Place all high voltage power cables in metal conduits If you more than one Wide Band Transceiver WBT install these in such a way that the transducer cables have the maximum distance to the power and Ethernet cables Ensure maximum physical distance between the Wide Band Transceiver WBT and the Power Sup...

Page 90: ...ceiver setup with two Wide Band Transceiver WBT units Standard transceiver setup with a WBT Cabinet Standard transceiver setup with EC150 3C units for acoustic Doppler current profiler ADCP functionality The Wide Band Transceiver WBT used by the Simrad EK80 can be set up to work with maximum four 4 operational frequencies This means that you can use four single frequency single beam transducers tw...

Page 91: ...ystem or commercial cables These cables are provided with the EK80 delivery or the relevant item It is very important that high quality Ethernet cables are used You must use CAT 5E STP Shielded Twisted Pair quality or better If you use cables with lower bandwidth capacity you will reduce the EK80 performance Do not connect the Processor Unit to the Wide Band Transceiver WBT using an existing local...

Page 92: ...more Wide Band Transceiver WBT units may be used in the complete EK80 system An Ethernet switch is required if more than one Wide Band Transceiver WBT is used Cables identified with an asterisk are system or commercial cables These cables are provided with the EK80 delivery or the relevant item One transducer cable marked with a dual asterisk is provided with each transducer Related topics Cable p...

Page 93: ... one or more Wide Band Transceiver WBT units may be used in the complete EK80 system An Ethernet switch is required if more than one Wide Band Transceiver WBT is used Cables identified with an asterisk are system or commercial cables These cables are provided with the EK80 delivery or the relevant item One transducer cable marked with a dual asterisk is provided with each transducer Related topics...

Page 94: ...le is required for connection to AC mains The transducer cables one for each transducer normally exit the cabinet through the its bottom Cables identified with an asterisk are system or commercial cables These cables are provided with the EK80 delivery or the relevant item One transducer cable marked with a dual asterisk is provided with each transducer Related topics Cable plans page 88 Cable lay...

Page 95: ...80 delivery It is very important that a high quality Ethernet cable is used You must use CAT 5E STP Shielded Twisted Pair quality or better If you use a cable with lower bandwidth capacity you will reduce the EK80 performance The transducer cable is 40 metres long The cable can not be extended The cable can be cut to match the installation requirements Make sure that the cable length is minimum 15...

Page 96: ...und 1 x 6 mm2 Video cable From Processor Unit to display C5 This is a commercial cable The display cable is often physically attached to the display and terminated in the computer end with a male connector If the cable is not attached it is normally provided with the display C6 Computer cable From Processor Unit to keyboard C7 Computer cable From Processor Unit to mouse or another similar device C...

Page 97: ...ransducer C21 AC power cable From WBT Cabinet to AC power outlet 2 x 1 5 mm2 1 5 mm2 Ground C22 24 Not used AC power cable From Ethernet switch to AC power outlet 2 x 1 5 mm2 1 5 mm2 Ground C25 The power cable on the Ethernet switch may comprise a separate power supply C26 29 Not used EC150 3C cables Cable Type From To Minimum requirements Ethernet cable From Power Supply Unit to Processor Unit CA...

Page 98: ... capacity you will reduce the EK80 performance Do not connect the Processor Unit to the Wide Band Transceiver WBT using an existing local area network LAN The grounding cable for the WBT Cabinet is not listed The grounding cable is a special braided wire that is physically connected to the cabinet It is connected to vessel ground by means of the cabinet s shock absorbers More than one serial line ...

Page 99: ...includes different screwdriver types pliers spanners a cable stripper a soldering iron etc Each tool must be provided in various sizes We recommend that all tools are demagnetized to protect your equipment Depending on the tasks at hand additional tools may be required Refer to the cable plans and the list of cables Detailed information about cable specifications termination and connectors are pro...

Page 100: ... socket page 137 2 Connect the ground cables a If applicable connect the ground cable from the display to vessel ground C3 b Connect the ground cable from the Processor Unit to vessel ground C4 These cables must be provided by the installation shipyard For more information see the cable details Ground cable page 139 3 Connect the video cable from the Processor Unit to the display C5 The display ca...

Page 101: ... used in the complete EK80 system An Ethernet switch is required if more than one Wide Band Transceiver WBT is used For more information see the cable details RJ45 High speed Ethernet cable 1000Base t page 147 7 Connect the Ethernet cable from the Processor Unit to the local area network LAN C9 For more information see the cable details RJ45 High speed Ethernet cable 1000Base t page 147 8 Connect ...

Page 102: ...le length is between 1 5 and 2 meters If this is too short you must use an extension cable not recommended mount a new power outlet within range or make your own power cable with sufficient length For more information see the cable details AC power cable using IEC C13 inline socket page 137 2 Connect the ground cables If a WBT Cabinet is used a Verify that ground strap from the WBT Cabinet to vess...

Page 103: ...onnect the transducer cables from each transducer to the relevant Wide Band Transceiver WBT Related topics Installing the EK80 cables page 97 Cable layout and interconnections page 85 Cable layout and interconnections ...

Page 104: ... signals C Video cable D Serial cables From Processor Unit to external device s C10 E Serial cables From Processor Unit to external device s C10 F Ethernet cable From Processor Unit to Wide Band Transceiver WBT C8 Only the top Ethernet socket is used to communicate with the Wide Band Transceiver WBT It is very important that a high quality Ethernet cable is used You must use CAT 5E STP Shielded Tw...

Page 105: ... the left Ethernet socket on the connection panel Do not use the adapter in Slot F M USB Universal Serial Bus sockets From Processor Unit to keyboard C6 From Processor Unit to mouse or another similar device C7 N Audio cable Not used Related topics Installing the EK80 cables page 97 Cable layout and interconnections page 85 Cable layout and interconnections ...

Page 106: ...net cable From Wide Band Transceiver WBT to Processor Unit C8 D DC power cable From Wide Band Transceiver WBT to Power Supply Unit C16 E Auxiliary connector for synchronization Optional The Wide Band Transceiver WBT can be powered by a large capacity battery The battery must be placed close to the Wide Band Transceiver WBT to minimize power loss in the cable Related topics Installing the EK80 cabl...

Page 107: ...erminated above the water line With a steel conduit the installation will satisfy the European Union regulations for electromagnetic compatibility EMC interference Without a steel conduit there is a risk of reduced EK80 performance Steel conduit quality and shielding The steel conduit must be unbroken and watertight from the transducer to above the water line From there the cable can be pulled fur...

Page 108: ...106 394149 D Related topics Installing the EK80 cables page 97 Cable layout and interconnections page 85 Simrad EK80 Installation Manual ...

Page 109: ...y tools and instruments required must be available The installation shipyard must prepare detailed drawings of the electrical system and identify each cable You must be equipped with a standard set of tools This tool set must comprise the normal tools for electronic and electromechanical tasks This includes different screwdriver types pliers spanners a cable stripper a soldering iron etc Each tool...

Page 110: ...completely 4 Remove the insulation from the transducer cable Connect the individual wires to the terminal block 5 Remove the insulation from the extension cable Connect the individual wires to the terminal block 6 Make sure that you have connected the wires 1 1 and that the colours match 7 Connect the cable screens to the cable glands in the junction box Related topics Splicing the transducer cabl...

Page 111: ...lands 4 Remove the insulation from the transducer cable Connect the individual wires to the terminal block 5 Remove the insulation from the extension cable Connect the individual wires to the terminal block 6 Make sure that you have connected the wires 1 1 and that the colours match 7 Connect the screens from both cables together 8 Make sure that the cable screens do not have any electrical connec...

Page 112: ...cal user B Remote user C KVM Receiver D KVM Transmitter E Processor Unit F The communication between the two operating positions is made using an Ethernet cable The KVM Keyboard Video Mouse technology offers a simple way to remote control the EK80 from a secondary position In a typical situation KVM units allow you to use the EK80 from the bridge even though the EK80 Processor Unit and main operat...

Page 113: ...ousing unit can be installed on a desktop on the bulkhead or in a 19 rack using dedicated adapters KVM Modular Receiver board Each KVM Modular Receiver board is mounted in a dedicated housing unit at the remote operating position The receiver distributes the video signal to the display and allows you to connect a keyboard and a mouse KVM Modular Transmitter board Each KVM Modular Transmitter board...

Page 114: ...ine Apart from the variety of output ports the two sets of Mini DP and DVI outputs allow old systems to be upgraded directly to multi display solutions The ER93F Graphic Card uses the embedded E6760 graphics chip from AMD and incorporates 128 bit 1GB GDDR5 memory in MCM BGA packaging Industrial grade passive electronic components are used throughout the entire card and it has been tested between 2...

Page 115: ...ay using a DVI to VGA adapter you must use the left output D Graphic output resolutions The following output resolutions are provided Mini DisplayPort Maximum resolution 2560 x 1600 px HDMI Maximum resolution 1920 x 1200 px DVI I D Maximum resolution 2560 x 1600 px VGA using adapter Maximum resolution 2048 x 1536 px Tip To learn more about the various video standards explore these Wikipedia pages ...

Page 116: ...de using a converter cable with four 9 pin male D subminiature connectors The converter cable is supplied with the Processor Unit Manufacturer Moxa Manufacturer s website https www moxa com Serial line support The serial adapter supports the following interface formats Port 1 RS 232 RS 422 RS 485 Port 2 RS 232 RS 422 RS 485 Port 3 RS 232 RS 422 RS 485 Port 4 RS 232 RS 422 RS 485 In order to set up...

Page 117: ...ections easier 9 pin D Subminiature connectors with screw terminals are included in the delivery Nuts to establish firm connections are also provided Pin configuration Moxa CP114EL I connectors Adapter cable Pin RS 232 RS 422 RS 485 4 wire RS 485 2 wire 1 DCD TXD A TXD A 2 RxD TXD B TXD B 3 TxD RXD B RXD B Data B 4 DTR RXD A RXD A Data A 5 Ground Ground Ground Ground 6 DSR 7 RTS 8 CTS 9 Related to...

Page 118: ...or certified maintenance technicians and service engineers from Kongsberg Maritime or from a certified dealer distributor or agent It is assumed that you are familiar with the Windows operating systems computer technology and interface principles We strongly advise our end users not to alter the parameters described Procedure 1 Select Start Control Panel System 2 On the left side select Device Man...

Page 119: ...meters offered change only the Interface parameter to the required format Leave the other settings with their default values 7 Click OK repeatedly to save you settings and exit the utility Related topics Cable plans page 88 Processor Unit serial adapter page 114 Cable layout and interconnections page 85 Cable layout and interconnections ...

Page 120: ...tter description The Øverland UPC 3005 is a serial line splitter with one input and eight outputs UPC 3005 is a serial line splitter with 1 signal input 3 x RS 232 and 5 x RS 422 outputs The powersupply and both signal inputs are galvanic isolated from the outputs All outputs are Short Circuit Protected Information from the manufacturer s website copied January 2017 The serial line splitter is fit...

Page 121: ...nstallation The serial line splitter is fitted with a DIN rail for easy mounting and replacement Outline dimensions Length 130 mm Width 80 mm Height 50 mm Note This information was copied from the manufacturer s documentation The technical specifications may be changed without prior notice To ensure that your information is correct always consult the manufacturer s own documents Related topics Ser...

Page 122: ...0 VDC B Input C Outputs 3 x RS 232 D Outputs 5 x RS 422 Note This information was copied from the manufacturer s documentation The technical specifications may be changed without prior notice To ensure that your information is correct always consult the manufacturer s own documents Related topics Serial line splitter Øverland UPC 3005 page 118 Cable plans page 88 Cable layout and interconnections ...

Page 123: ...394149 D 121 UPC 3005 Dimensions Related topics Serial line splitter Øverland UPC 3005 page 118 Cable plans page 88 Cable layout and interconnections page 85 Cable layout and interconnections ...

Page 124: ...ial line splitter description The Øverland UPC 5000P is a serial line splitter with two separate inputs and fifteen outputs Dual power input with autoswitch The two inputs A and B are separated with A as the primary input If there is data on both A and B inputs input A is used Input B is used only if input A is idle The power supply and both signal inputs are galvanic isolated from the outputs All...

Page 125: ... 422 Maximum 50 mA 5 x RS 232 All outputs from the serial line splitter are short circuit protected For Current Loop input 100 Ω Parallel Installation The serial line splitter is fitted with a DIN rail for easy mounting and replacement Outline dimensions Length 128 mm Width 128 mm Height 50 mm Note This information was copied from the manufacturer s documentation The technical specifications may b...

Page 126: ...by internal strap C Input D Power requirements 15 30 VDC E Outputs 10 x RS 422 Note This information was copied from the manufacturer s documentation The technical specifications may be changed without prior notice To ensure that your information is correct always consult the manufacturer s own documents Related topics Serial line splitter Øverland UPC 5000P page 122 Cable plans page 88 Cable layo...

Page 127: ...394149 D 125 UPC 5000P Dimensions Related topics Serial line splitter Øverland UPC 5000P page 122 Cable plans page 88 Cable layout and interconnections page 85 Cable layout and interconnections ...

Page 128: ...m that controls all the transmissions In physics interference is the phenomenon in which two waves superpose each other to form a resultant wave of greater or lower amplitude Interference usually refers to the interaction of waves that are correlated or coherent with each other either because they come from the same source or because they have the same or nearly the same frequency Interference eff...

Page 129: ...f any trigger signals arriving at the synchronization port The Synchronization Delay setting is not applicable when synchronization is switched off Master Master mode is used if the EK80 is going to act as the controlling unit in a synchronized system The peripheral hydroacoustic system s are only permitted to transmit when enabled by the EK80 When Master mode is selected the EK80 will run using i...

Page 130: ...K80 sets the Ready To Send RTS signal to a logic high to indicate that it is ready for the next ping Master mode When the EK80 is Master in a system the synchronization can either take place in Free running mode or in Wait for slave mode Synchronization in Free running mode When in Free running mode the EK80 will ping as fast as possible setting its Ready to Send RTS signal to a logic high at star...

Page 131: ...ure connector Note RS 422 communication ports can not be used for synchronization purposes The port you wish to use must be set to RS 232 Related topics Setting up the EK80 in a synchronized system page 126 Cable layout and interconnections page 85 Synchronization using the Auxiliary socket on the transceiver The Auxiliary socket on the Wide Band Transceiver WBT offers a trigger input signal for t...

Page 132: ...ut Future use Pin number 5 6 7 Signal Digital ground Not used Not used The parameters on the Synchronization page allow you to choose which communication port to use for the physical connection to the external system and which synchronization mode to use The Synchronization page is located in the Installation dialog box on the Setup menu Note If you use more than one Wide Band Transceiver WBT in y...

Page 133: ... hydroacoustic system is installed on a vessel interference may occur To avoid interference you have these options The systems are all connected to a common synchronization system One of the acoustic systems is set up as master and controls the transmissions on the other systems The EK80 offers functionality for remote transmit synchronization It can be set up to operate in either Master or Slave ...

Page 134: ... side 5 On the left side of the Installation dialog box select Synchronization 6 Select Synchronization Mode Stand alone Synchronization is turned off This synchronization mode is used if the EK80 is working by itself and with no synchronization required This is the default setting The EK80 operates using its internal ping interval parameters independent of any trigger signals arriving at the sync...

Page 135: ... delay will only work when the synchronization is set up using a serial port Slave In Slave mode the EK80 waits for the delay time after the external trigger signal has arrived before transmitting the ping This is often referred to as a post trigger 8 From the list of ports available select Synchronization Port This is the interface port currently used to transmit or receive synchronization signal...

Page 136: ...equipment Depending on the tasks at hand additional tools may be required Context The Auxiliary socket on the Wide Band Transceiver WBT can be used to interface an external synchronization system The socket fits a Conxall 7 pin Mini Con X shielded plug The connections are made on pins 2 3 and 5 The plug can be ordered from the manufacturer or purchased from Kongsberg Maritime Use part number 38756...

Page 137: ...elect Installation Observe that the Installation dialog box opens This dialog box contains a number of pages selected from the menu on the left side 5 On the left side of the Installation dialog box select Synchronization 6 From the list of ports available select Transceiver Auxiliary Port 7 Observe that when Transceiver Auxiliary Port is selected only Slave synchronization mode is permitted Slave...

Page 138: ...dapter page 145 RJ45 High speed Ethernet cable 1000Base t page 147 Battery power cable page 148 K Sync interface to generic RS 232 synchronization input page 148 Simrad TU40 interface to generic RS 232 synchronization input page 151 Auxiliary connector for synchronization page 153 Single beam low power transducer connection to a circular transducer socket page 154 Split beam transducer connection ...

Page 139: ...erminated with an female IEC C13 inline socket The AC mains end is terminated in an AC connector suitable for the local standard and or the output sockets on an uninterruptible power supply UPS If this is not the case you must replace the AC connector The typical cable length is between 1 5 and 2 meters If this is too short you must use an extension cable not recommended mount a new power outlet w...

Page 140: ... 2 x 1 5 mm2 1 5 mm2 Ground Screen None Voltage 750 V Maximum outer diameter Defined by the plugs and or the cable gland Related topics Cable drawings and specifications page 136 Cable layout and interconnections page 85 Simrad EK80 Installation Manual ...

Page 141: ...n between the cabinet and the bulkhead It is normally provided with a green yellow colour The grounding cable must be connected to vessel ground in the fuse box or other common grounding point Minimum cable requirements Conductors 1 x 6 mm2 Screen None Voltage 60 V Maximum outer diameter Not applicable Related topics Cable drawings and specifications page 136 Cable layout and interconnections page...

Page 142: ...otherwise specified this cable must be provided by the installation shipyard Note that this cable does not support all the signals in the standard RS 232 specification Minimum cable requirements Conductors 2 x 4 x 0 5 mm2 Screen Overall braided Voltage 60 V Maximum outer diameter Defined by the plugs and or the cable gland If you need to install a very long cable increase the cross section Related...

Page 143: ...ied this cable must be provided by the installation shipyard Note that this cable does not support all the signals in the standard RS 232 specification Minimum cable requirements Conductors 2 x 4 x 0 5 mm2 Screen Overall braided Voltage 60 V Maximum outer diameter Defined by the plugs and or the cable gland If you need to install a very long cable increase the cross section Related topics Cable dr...

Page 144: ...e 9 pin D Subminiature connector Unless otherwise specified this cable must be provided by the installation shipyard Minimum cable requirements Conductors 2 x 5 x 0 5 mm2 Screen Overall braided Voltage 60 V Maximum outer diameter Defined by the plugs and or the cable gland If you wish to use RS 422 or RS 485 serial communication use a cable with twisted pairs If you need to install a very long cab...

Page 145: ...res or controls transmit receive synchronization Note that this cable does not support all the signals in the standard RS 232 specification Note This synchronization method can only be used with RS 232 communication You can only connect two systems together Unless otherwise specified this cable must be provided by the installation shipyard Minimum cable requirements Conductors 2 x 4 x 0 5 mm2 Scre...

Page 146: ... manufacturer C Female 9 pin D Subminiature connector D Male 9 pin D Subminiature connector Unless otherwise specified this cable must be provided by the installation shipyard Minimum cable requirements Conductors 2 x 5 x 0 5 mm2 Screen Overall braided Voltage 60 V Maximum outer diameter Defined by the plugs and or the cable gland Use a cable with twisted pairs If you need to install a very long c...

Page 147: ...erwise specified this cable must be provided by the installation shipyard If you wish to use RS 422 or RS 485 serial communication use a cable with twisted pairs Note Observe that long runs of unshielded cable will pick up noise easily This is because the RS 232 signals are not balanced Maximum length for an RS 232 serial cable is typically 60 meters with 2400 bps data rate however this depends on...

Page 148: ...RXD A Data A 5 Ground Ground Ground Ground 6 DSR 7 RTS 8 CTS 9 Minimum cable requirements Conductors 2 x 5 x 0 5 mm2 Screen Overall braided Voltage 60 V Maximum outer diameter Defined by the plugs and or the cable gland If you wish to use RS 422 or RS 485 serial communication use a cable with twisted pairs If you need to install a very long cable increase the cross section Related topics Cable dra...

Page 149: ...ailable commercially in different lengths colours and categories Normally CAT 5E and CAT 6 cables are used in local area networks with bandwidths exceeding 100 Mbit Minimum cable requirements It is very important that high quality Ethernet cables are used You must use CAT 5E quality or better If you use cables with lower bandwidth capacity you will reduce the EK80 performance Related topics Cable ...

Page 150: ... 4SG 520 Pin configuration Pin number 1 2 3 4 Voltage 12 VDC 0 VDC 0 VDC 12 VDC Minimum cable requirements Conductors 2 x 1 5 mm2 Screen None Voltage 60 V Maximum outer diameter Not applicable Related topics Cable drawings and specifications page 136 Cable layout and interconnections page 85 K Sync interface to generic RS 232 synchronization input For transmission synchronization purposes the K Sy...

Page 151: ...is a return signal from the hydroacoustic system that is synchronized The Ready to Transmit RTT signal means that the hydroacoustic system is ready for the next trigger 4 Trigger In This signal is received from the system that needs to be synchronized Trigger In is active while the system is transmitting 5 Ground Mandatory This ground is connected to pin 2 inside the IO Module 6 Not used A Local c...

Page 152: ...his cable must be provided by the installation shipyard Minimum cable requirements Conductors 2 x 5 x 0 5 mm2 Screen Overall braided Voltage 60 V Maximum outer diameter Defined by the plugs and or the cable gland If you need to install a very long cable increase the cross section Related topics Cable drawings and specifications page 136 Cable layout and interconnections page 85 Simrad EK80 Install...

Page 153: ...le and a solid state relay module Pin Signal Trigger Unit Signal description Screen Green Screen A Cable screen Input RTT B Ready to Transmit Ready to Transmit RTT is a return signal from the hydroacoustic system that is synchronized The Ready to Transmit RTT signal means that the hydroacoustic system is ready for the next trigger Ground Ground C Signal ground Output Trigger Out D This signal is t...

Page 154: ...erwise specified this cable must be provided by the installation shipyard If you need to install a very long cable increase the cross section Conductors 2 x 2 x 0 5 mm2 Screen Overall braided Voltage 60 V Maximum outer diameter Defined by the plugs and or the cable gland Related topics Cable drawings and specifications page 136 Cable layout and interconnections page 85 Simrad EK80 Installation Man...

Page 155: ...art number 387563 Manufacturer Switchcraft Conxall Manufacturer s website http www conxall com True manufacturer s part number SF6282 7SG 520 Pin number 1 2 3 4 Signal Future use Synchronization Output Synchronization Input Future use Pin number 5 6 7 Signal Digital ground Not used Not used Minimum cable requirements Conductors 4 x 0 5 mm2 Screen Overall braided Voltage 60 V Maximum outer diameter...

Page 156: ...in Amphenol socket As seen towards the socket face view The cable screen must be connected to the housing on the transducer plug Note The black wires in the transducer cable are not for grounding You must never connect these together You must never connect any of them to vessel ground If you need to extend the transducer cable you must splice it correctly This is very important as any splice is ve...

Page 157: ...ansducer to sockets H and J on the 12 pin Amphenol socket For additional licenses connect as follows License 1 License 2 License 3 License 4 H J E F C D A B Minimum cable requirements Not applicable If you need an extension cable contact your dealer or Kongsberg Maritime for support Related topics Cable drawings and specifications page 136 Cable layout and interconnections page 85 201575 Transduce...

Page 158: ...s correctly installed with the sectors positioned as shown in the illustration seen from above Each sector is connected to a dedicated transceiver channel In this context the phrase transceiver channel is used to describe one single pathway through the transceiver This pathway contains one transmitter one preamplifier and the necessary transmit receive switching circuitry Note We strongly recommen...

Page 159: ...d with white text on each black conductor These are numbered 1 to 4 to identify the transducer sectors The numbers on the black conductors are the same as four sectors as seen in the illustration and table The different numbers are quite small and you may need a magnifying glass to see them Note Since the white conductors are not numbered it is very important to find the pairs that are twisted tog...

Page 160: ... you must splice it correctly This is very important as any splice is very vulnerable for noise Cable can be spliced using two different methods Splicing using a grounded junction box Splicing using a junction box that is isolated from vessel s ground Refer to the dedicated procedures Minimum cable requirements Not applicable If you need an extension cable contact your dealer or Kongsberg Maritime...

Page 161: ... with the sectors positioned as shown in the illustration seen from above Each sector is connected to a dedicated transceiver channel In this context the phrase transceiver channel is used to describe one single pathway through the transceiver This pathway contains one transmitter one preamplifier and the necessary transmit receive switching circuitry Note We strongly recommend that you install th...

Page 162: ...rs are defined by small numbers marked with white text on each black conductor These are numbered 1 to 4 to identify the transducer sectors The numbers on the black conductors are the same as four sectors as seen in the illustration and table The different numbers are quite small and you may need a magnifying glass to see them Note Since the white conductors are not numbered it is very important t...

Page 163: ... to the context sensitive on line help Illustration The connector is seen from the solder side Splicing the transducer cable If you need to extend the transducer cable you must splice it correctly This is very important as any splice is very vulnerable for noise Cable can be spliced using two different methods Splicing using a grounded junction box Splicing using a junction box that is isolated fr...

Page 164: ...adequate protection must be provided to support the transducer cable Burton connector The Burton connector used on the cable is an 8 pin Series 55 The 5500 Series is an extremely rugged and reliable underwater electrical connector It is the standard Burton connector series with pins in the receptacles and sockets in the plugs The pin and socket relationship is due to the fact that in most applicat...

Page 165: ...tion 1 Sector 1 H 4 Sector 1 J Aft starboard 2 Sector 2 E 5 Sector 2 F Aft port 3 Sector 3 C 6 Sector 3 D Fore port 7 Sector 4 A 8 Sector 4 B Fore starboard Related topics Cable drawings and specifications page 136 Cable layout and interconnections page 85 Cable layout and interconnections ...

Page 166: ...cables do not support all the signals in the standard RS 232 specification Observe that long runs of unshielded cable will pick up noise easily This is because the RS 232 signals are not balanced Even though a standard exist for RS 232 pin configuration certain manufacturer may still choose their own connector pins for the various signals used In order to make the RS 232 connection to your periphe...

Page 167: ...fers data transmission speeds of 35 Mbit s up to 10 m and 100 kbit s at 1200 m Since it uses a differential balanced line over twisted pair like RS 422 it can span relatively large distances typically up maximum 1200 m In contrast to RS 422 which has a single driver circuit which cannot be switched off RS 485 drivers need to be put in transmit mode explicitly by asserting a signal to the driver Th...

Page 168: ...ires page 141 RS 422 serial line connection using five wires page 142 RS 232 used as synchronization trigger input or output page 143 RS 485 serial line connection using two or four wires page 144 Moxa CP114EL I Serial line adapter page 145 Cable layout and interconnections page 85 Simrad EK80 Installation Manual ...

Page 169: ...tenance and repair 1 Wherever possible cable trays must be straight accessible and placed so as to avoid possible contamination by condensation and dripping liquids oil etc They must be installed away from sources of heat and must be protected against physical damage Suitable shields must be provided where cables are installed in the vicinity of heat sources 2 Unless it is absolutely unavoidable c...

Page 170: ...ately screened Suitable screening can be established using sheathing braiding or other suitable material In such a situation flexible cables should be screened wherever possible It is important that cables other than those supplying services to the equipment installed in a radio room are not installed through a radio room high power switch gear or other potential sources of interference Cables whi...

Page 171: ... the entire length of all cable coverings particularly at joints and splices In no case should the shielding of cables be used as the only means of grounding cables or units Metallic casings pipes and conduits must be grounded and when fitted with joints these must be mechanically and electrically grounded locally Related topics Basic cable requirements page 167 Cable layout and interconnections p...

Page 172: ...c cable requirements page 167 Cable layout and interconnections page 85 Cable glands and termination procedures Cable glands are used to attach and secure the end of a cable to the equipment Cable glands may also be used for sealing cables passing through bulkheads or gland plates Related topics Basic cable requirements page 167 Cable layout and interconnections page 85 About cable glands Cable gl...

Page 173: ...pedia org wiki Cable_gland February 2014 Related topics Basic cable requirements page 167 Cable glands and termination procedures page 170 Cable layout and interconnections page 85 Preparing cables for termination Whenever a cable shall penetrate a cabinet or a bulkhead using a cable gland the termination of the cable must be prepared Prerequisites Electrical installations can only be done by cert...

Page 174: ...en installed in conduits Measure the maximum length of cable required to reach from the final cable clip outside the cabinet to the terminal block s inside the cabinet Add 20 cm and remove the excess cable b If the cable has not been installed in conduits Measure the maximum length of wire required to reach from the cable gland to the terminal block s inside the cabinet Add 20 cm and mark the cabl...

Page 175: ...slack cable inside the cabinet prepare and connect the cable cores to the appropriate terminals and or plugs within or onto the cabinet 2 Secure the cable using cable clips 3 Check the terminal connections against the wiring diagram to ensure they are correct Follow the same procedure for all the cables and cable glands 4 Check the cabinet to ensure all tools and rubbish are removed then close the...

Page 176: ...t prepare detailed drawings of the electrical system and identify each cable Illustration Sealing system example the finished assembly Context Only a brief description of the sealing system will be presented here Further information with relevant technical specifications and installation descriptions must be obtained from the manufacturer Roxtec modules Image from Roxtec website The illustrations ...

Page 177: ...ealing is to be used under water both pressure and material requirements must be taken into consideration 2 Mount the frame 3 Pull the cable s through the frame In most cases the opening will be large enough to accept the plugs on the cables 4 Secure each cable with a square sealing module 5 Adjust the module to fit the cable s outer diameter 6 When the required number of modules are installed tig...

Page 178: ...sition and calibrate the sensors and each transduceron your vessel Topics Quality assurance of EK80 data page 177 Surveying the transducer and the navigation sensors page 179 Dimensional survey accuracy requirements for ADCP operations page 181 Dimensional survey accuracy requirements for echo sounding operations page 182 Vessel coordinate system page 182 Simrad EK80 Installation Manual ...

Page 179: ...ock The first calibration is normally done at sea during the Sea Acceptance Test We strongly recommend that calibration is repeated before and after each survey This is important for achieving high quality measurement results Alignment The alignment tasks required for EK80 include Measure and adjust the transducer to ensure that it has been mounted horizontally within the given tolerances Measure ...

Page 180: ... Place it in the coordinate system Note Determining the relative positions and orientations of the sensors and the transducer with high accuracy is important This requires professional surveying done by qualified and trained personnel using proven equipment and methods for maritime dimensional surveying We recommend that you use third party consultants with well proven experience with vessel dimen...

Page 181: ...rmining the relative positions and orientations of the sensors and the transducer with high accuracy is important This requires professional surveying done by qualified and trained personnel using proven equipment and methods for maritime dimensional surveying We recommend that you use third party consultants with well proven experience with vessel dimensional control Sufficient time and satisfact...

Page 182: ...ation angles of the motion reference unit MRU 7 Measure the physical location and rotation angles of the heading sensor 8 Measure the physical location and rotation angles of the global positioning system GPS antenna 9 Measure the physical location and rotation angles of other relevant sensors or sensor antennas Result All results from the dimensional survey measurements must be summarized in a re...

Page 183: ...rmined from considerations on how they contribute to the total EK80 accuracy Any errors in these measurements should not contribute significantly to depth or position errors in the soundings Note The given accuracies are maximum values If easily achievable better accuracies should be obtained Transducer Position x y 0 05 m Position z 0 02 m Pitch 0 10 Roll 0 025 Heading 0 1 Motion Reference Unit M...

Page 184: ...ally mounted high above the superstructure while a motion sensor is located close to the vessel s centre of gravity Both of these are physically positioned far away from the transducer on a depth sensor which may be located closer to the bow Very often the information from one sensor depends on data from an other It is then important that the relevant measurements are compensated for these relativ...

Page 185: ... physical locations of the vessel s sensors radar and positioning system antennas echo sounder and sonar transducers motion reference units etc are referenced to the origin In most cases the location of the vessel s official origin has been defined by the designer or shipyard This origin is normally identified with a physical marking and also shown on the vessel drawings Frequently used locations ...

Page 186: ...d It is defined with three positive offset values for X Y and Z All values are positive because the new reference point is in front of and below the origin and on the starboard side The accuracy of the three numerical values for X Y and Z defines the accuracy of the sensor data If you require a high accuracy for example for underwater positioning underwater mapping or scientific measurements you m...

Page 187: ... use page 188 Turning on the EK80 for the first time page 199 Installing and troubleshooting Network Time Protocol NTP page 214 Configuring the EK80 for normal operation page 224 Interfacing peripheral equipment page 228 Test procedures page 256 Turning off the EK80 page 276 Installation remarks page 278 Setting to work ...

Page 188: ...pecific tasks described and in the given order Many tasks here are explained in more detail in separate procedures Note The installation shipyard must provide all necessary design and installation drawings as well as the relevant work standards and mounting procedures Procedure 1 Do a thorough visual inspection to verify that the EK80 is ready for operational use a Verify that all hardware have be...

Page 189: ... devices navigation sensors and other peripherals To provide correct information the EK80 needs to communicate with external devices All these interfaces must be set up in the EK80 user interface Interfacing peripheral equipment page 228 4 Make sure that the EK80 is fully operational To make sure that the EK80 fulfils all operational and functional requirements specific tests are provided Test pro...

Page 190: ...er from the vessel s mains supply Before you apply AC power to any EK80 unit you must verify that the voltage is correct Prerequisites The EK80 hardware units are installed as specified in this manual The EK80 is turned off You need the following equipment Multimeter Procedure For each EK80 unit that operates on AC mains 1 Make sure that the unit is connected to AC mains 2 Make sure that the relev...

Page 191: ... described in the Cable layout and interconnections chapter Refer to the cable plan the cable list and the basic cable requirements Procedure 1 For each cable in use on the EK80 a Make sure that the cable is installed as specified in the Cable layout and interconnections chapter Pay special attention to signal cables These must not be installed too close to power cables b Make sure that the termin...

Page 192: ... when the display is provided by Kongsberg Maritime as a part of the EK80 delivery Procedure 1 Make sure that the display is installed in the correct location and that it is suitably orientated with respect to ambient light conditions and reflections 2 Make sure that the physical installation of the unit has been completed a Make sure that the structure to which the display is fastened is substant...

Page 193: ...ddition to any incidental electrical contact made by the mounting lugs on the unit b Use a standard multimeter to check that the resistance between the unit and the ship s ground is approximately 0 zero Ω 5 Make sure that cable installation has been completed a Make sure that all cables leading to and from the unit have been properly mounted and secured b Make sure that enough slack has been provi...

Page 194: ...t and to insert and remove USB flash drives c If applicable Make sure that ample ventilation is provided to avoid overheating d Make sure that ample space is provided around the unit to allow for maintenance and replacement of parts e Make sure that the bolts screws or studs that have been used are all of the correct size f Make sure that the correct flat and shake proof washers have been used g M...

Page 195: ...sy access for maintenance and replacement of parts The Processor Unit is free from scratches dents or other physical damage Free access to all the connectors on the Processor Unit is provided All cables are properly mounted with enough slack The Processor Unit can be fully opened for access to the internal parts The Processor Unit is properly earthed Date and signature Related topics Making sure t...

Page 196: ...with the correct preservation medium to prevent corrosion 3 Make sure that the unit is not physically damaged and that the surfaces and paint work are clean without dents or scratches The physical handling during the installation may have caused some minor scratches to the surfaces or paint work This can be accepted However if rough handling has caused serious damage this must be recorded with a w...

Page 197: ...n of the WBT Cabinet A visual inspection of the WBT Cabinet is required to verify that it has not been physically damaged during the installation Prerequisites The EK80 hardware units are installed as specified in this manual The EK80 is turned off You need the following equipment Multimeter Procedure 1 Make sure that the WBT Cabinet is installed in the correct location and that it is suitably ori...

Page 198: ... USB 4 Make sure that the cabinet is not physically damaged and that the paint work is clean without dents or scratches The physical handling during the installation may have caused some minor scratches to the surfaces or paint work This can be accepted However if rough handling has caused serious damage this must be recorded with a written statement and necessary photos so that corrective actions...

Page 199: ...de the EK80 with the necessary power for operation The Power Supply Unit also controls the Ethernet communication between the transducer and the Processor Unit as well as the synchronization with peripheral devices Procedure 1 Verify that the Power Supply Unit is installed in the correct location and that it is suitably oriented for easy maintenance and replacement of parts 2 Make sure that the ph...

Page 200: ...at all cables leading to and from the unit have been properly mounted and secured b Make sure that enough slack has been provided on each cable to allow for maintenance and replacement 7 Make sure that the unit is fitted with the correct fuse Rating 6 3 A 230 VAC Result Requirements Results The Power Supply Unit is correctly installed with easy access for maintenance and replacement of parts The P...

Page 201: ...be put to use it must be set up for operation Prerequisites The EK80 Wide band scientific echo sounder system units have all been installed according to the instructions provided All cables have been connected and verified All system units have been inspected The EK80 operational software is available The EK80 software license is available Caution You must never set the EK80 to ping unless the tra...

Page 202: ...ceiver a high performance Ethernet switch must be used Note It is very important that high quality Ethernet cables are used You must use CAT 5E STP Shielded Twisted Pair quality or better If you use cables with lower bandwidth capacity you will reduce the EK80 performance 5 Start the EK80 6 On the Software License page install the software license s 7 On the Transducer page install each transducer...

Page 203: ...he Processor Unit You need this to install the software If you purchased your own computer you must verify that it meets the technical requirements for use with the EK80 Do this before you install the software Procedure 1 Turn on the Processor Unit 2 Switch off any firewall applications 3 Insert the EK80 software media 4 Use a file manager application on the Processor Unit to access the software f...

Page 204: ...so we will leave it in Passive mode Prerequisites This procedure assumes that the entire EK80 installation has been inspected All power sources have been measured and verified All system cables and connectors have been checked and tested The EK80 has been installed on the Processor Unit Context The program is not automatically started when the Processor Unit is turned on Once the operating system ...

Page 205: ...ense string and install it on your Processor Unit Without a license you will not be able to communicate with the transceiver Prerequisites This procedure assumes that the EK80 operating software has been successfully installed on the Processor Unit Context The software license is a 32 character hexadecimal string based on the transceiver s serial number It defines several key parameters that contr...

Page 206: ...act our support department directly You can use the following e mail address purchase order simrad com Once the software license string s have been returned to you most likely by e mail you can install the licenses into the software 3 On the Setup menu select Installation Observe that the Installation dialog box opens This dialog box contains a number of pages selected from the menu on the left si...

Page 207: ...port used to communicate with the transceiver s The EK80 automatically assigns an IP address to each transceiver when they are turned off and on Prerequisites This procedure is made for the Microsoft Windows 10 operating system It is assumed that you are familiar with this operating system Context As long as you do not change the Processor Unit to another computer or replace the network adapter in...

Page 208: ...es within the selected IP range Related topics Turning on the EK80 for the first time page 199 Setting to work page 185 Installing one or more transducers The transducers you wish to use with the EK80 must be installed as a part of the software configuration Which transducers to use depends on the number of transceivers in your system and the licenses you have for these Unless you replace a broken...

Page 209: ... the Installation dialog box select Transducer Installation 4 Select the transducer you wish to install from the Model list Note Make sure that you select a transducer that is supported by your current license 5 Insert the serial number This serial number is very important because you will need it as a reference identification when the EK80 is calibrated Some new Simrad transducers with built in i...

Page 210: ...r for current profiling The information is not used to adjust for installation misalignments but will be included in the RAW files for post processing purposes a Obtain the rotation angle information from the personnel that installed the transducer b Insert the values Specify an angle in degrees to compensate for any deviation from the X axis fore and aft direction in the coordinate system Specify...

Page 211: ...rovided The transducer is added to the list in the Installed Transducers box 12 Repeat for each transducer that you wish to install 13 Continue your work in the Installation dialog box or select OK to close it Result Once a transducer has been installed it is listed in the Installed Transducers box To see the information you have collected about the transducer select the relevant transducer in the...

Page 212: ...ery time the page is opened the EK80 software automatically performs a search on the Ethernet network for transceivers The list in the upper part on the Transceiver Installation page shows you an overview of the transceivers and channels that are currently available In this context the phrase channel is used as a common term to identify the combination of transceiver transducer and operating frequ...

Page 213: ...r the relevant frequency channels change to Installed Tip If no transceivers are listed 1 Select Browse in the Transceiver Browsing box and open the Local IP Address box 2 Select the correct address for the Ethernet adapter you are using Select Apply This will make the EK80 search the network for available transceivers 3 Turn each transceiver off and on The EK80 automatically assigns an IP address...

Page 214: ...e operating system to adjust the screen resolution Prerequisites This procedure is made for the Microsoft Windows 7 and 10 operating systems It is assumed that you are familiar with these operating systems Context As a general recommendation you should set the screen resolution as high as possible This will allow you more space in the EK80 presentation to offer more detailed information The physic...

Page 215: ...rating system a In the bottom left corner of your desktop select the Windows Start button b On the menu select Settings c Observe that the Windows Settings dialog box opens d Select System in the top left corner of the Windows Settings dialog box e On the left side of the dialog box select Display f Change the display settings 1 Make sure that the correct display is shown 2 Change the resolution t...

Page 216: ...rotocol that enables you to synchronize the clocks on devices over a network It uses one or more NTP servers to maintain a highly accurate time and allows clients to query for this time When clients query the server they automatically adjust their own internal clocks to mirror the NTP server The Network Time Protocol NTP application must be installed on the EK80 Processor Unit Prerequisites To dow...

Page 217: ...d and install the latest release of the NTP application NTP for Windows XP and newer with IPv6 support Example ntp 4 2 8p14 win32 setup exe 4 Select I agree for license agreement 5 Keep the suggested Destination Folder for Installation Location Select Next to continue 6 Select Installation Components Setting to work ...

Page 218: ...TP Dameon NTP Tools NTP Documentation Create Start menu Select Next to continue 7 Select configuration file settings Select the following options by checking the check boxes Location of configuration file C Program Files x86 NTP etc ntp conf Simrad EK80 Installation Manual ...

Page 219: ... resort reference Stratum 12 Select Next to continue 8 Select No for not reviewing the generated config file 9 Select service settings in the Setting up NTP servicepage Select the following options by checking the check boxes SYSTEM account Start NTP service automatically Disable other Time Services eventually installed e g W32Time other NTP flavours Start NTP service right after installation Allo...

Page 220: ...g outside the preset tolerances are highlighted in the user interface Prerequisites To download the software you need a computer connected to the Internet Context The NTP Time Server Monitor allows you to configure and control the local NTP service The current status of the local NTP service as well as external NTP services are displayed The NTP Timer server monitor software controls and oversees ...

Page 221: ...ce ntp conf can be edited within this program https www meinbergglobal com english sw ntp server monitor htm June 2020 Note The screen captures are taken from software version 1 04 The manufacturer may change these in later releases Procedure 1 Open a web browser 2 Type the following URL in the address field https www meinbergglobal com english sw ntp server monitor htm 3 Download and install the ...

Page 222: ...4 Select Destination Folder C Program Files x86 meinberg ntp_time_server_monitor Select Next to continue 5 Type the name of the Program Manager Group Meinberg Select Next to continue Simrad EK80 Installation Manual ...

Page 223: ...394149 D 221 6 Start the installation by selecting Next 7 Select Finish to close the wizard Setting to work ...

Page 224: ... then follow the instructions of the MRU manufacturer to synchronize the MRU to the Ship Master clock Related topics Installing and troubleshooting Network Time Protocol NTP page 214 Troubleshooting the Network Time Protocol NTP service The Network Time Protocol NTP service may in some cases malfunction or even stop Context The EK80 installation program adds a firewall rule to allow for NTP commun...

Page 225: ...0 NTP server and the client s Tip You can use Wireshark https www wireshark org This is a network protocol analyser Wireshark allows you to see your network activities at a microscopic level Related topics Installing and troubleshooting Network Time Protocol NTP page 214 Setting to work ...

Page 226: ...sed for all other text on the EK80 The EK80 help may not be available for the language you choose If your language is not supported the English help is provided Procedure 1 Open the Setup menu 2 Select the middle of the Language button to open the list of available options 3 Select the language you wish to use Result All the texts in the user interface are changed to the selected language The cont...

Page 227: ...that the Installation dialog box opens This dialog box contains a number of pages selected from the menu on the left side 2 On the left side of the Installation dialog box select Units Observe that the Units page opens 3 Adjust the setting to fit your requirements 4 At the bottom of the page select Apply to save your settings 5 Continue your work in the Installation dialog box or select OK to clos...

Page 228: ...t the Output dialog box opens This dialog box contains a number of pages selected from the menu on the left side 3 In the Output dialog box select File Setup 4 On the File Setup page define the recording parameters a Define the output directory for the recorded files In order to change the output directory both Record RAW and Record Processed recording must be set to Off The same folder is used fo...

Page 229: ...with CW pulses Select Complex samples to use the default data format Select Power Angle to reduce the file sizes Select Reduced sampling rate Power Angle samples to minimize the file sizes Note Unless you choose Complex samples your RAW data files will contain less information The Motion Data Recording function allows you to control how often the motion data are saved in the raw data file 5 At the...

Page 230: ...en the EK80 and the Simrad TD50 page 254 Installing navigation sensors and other sensors For the EK80 to use and offer correct navigational information one or more external sensors must be connected Typical sensors are those providing navigational information heading speed or geographical position To set up the communication parameters on the serial and LAN ports use the I O Setup page To select w...

Page 231: ... b Set up the relevant serial or Ethernet LAN communication parameters c At the bottom of the page select Apply to save your settings d On the left side of the Installation dialog box select Sensor Installation e Select the type of sensor you want to interface and define the relevant parameters f Select Add to save the new sensor interface you have defined g On the left side of the Installation di...

Page 232: ...to set up and monitor the communication ports Select the port you want to work with and then select one of the buttons below the list Tip The Sensors page in the BITE Built In Test Equipment dialog box provides an overview of all the communication lines and sensors in use All relevant status information is provided You open the BITE dialog box from the Setup menu When you work in the Installation ...

Page 233: ...ion system GPS For the EK80 to use and offer correct navigational information one or more external sensors must be connected Typical sensors are those providing navigational information heading speed or geographical position To select which sensors to install use the Sensor Installation page Your current position is shown on the top bar if you have enabled this in the Display Options dialog box Pr...

Page 234: ...tal length of the serial line cable does not exceed approximately 50 meters If a longer cable is required you may need to use buffer amplifiers If the Processor Unit is not fitted with a suitable serial line connector use a USB to serial converter Several types are commercially available Note that most USB to serial converters will introduce some latency They may also introduce be jitter in the co...

Page 235: ...e EK80 is directly related to the accuracy of the information you enter on the Sensor Installation page a Select the offset value on the X axis fore and aft direction from the Ship Origin Adjust with a positive value for X if the sensor is located ahead of the ship origin b Select the offset value on the Y axis athwartship from the Ship Origin Adjust with a positive value for Y if the sensor is lo...

Page 236: ... accuracy etc the numerical values provided can be different from one sensor to another Several sensor are provided on the Sensor Configuration page one for each type of information Select the sensor you wish to configure in the Sensor list For each type you can define a priority sensor by rearranging the datagrams in a list You can also define manual values in case a sensor is unserviceable or no...

Page 237: ...ation dialog box or select OK to close it Related topics Interfacing peripheral equipment page 228 Setting up a serial or LAN Ethernet port for annotation input Several different annotation types may be added to the echograms or other views They are displayed on the views if this annotation feature is enabled You can add annotations manually or import information as datagrams using a serial or LAN...

Page 238: ...tup menu select Installation Observe that the Installation dialog box opens This dialog box contains a number of pages selected from the menu on the left side 3 On the left side of the Installation dialog box select Sensor Installation 4 Select Annotations to import information from the peripheral system 5 Select the port you wish to use serial or LAN 6 If you want to check the communication param...

Page 239: ...must be set up correctly Prerequisites This procedure assumes that You have a vacant interface port on your Processor Unit You are familiar with NMEA and other relevant datagram formats You know how to set up the parameters for serial and local area network LAN communication The interface port is set up with the correct communication parameters The EK80 system is turned on and operates normally Th...

Page 240: ...n the Setup menu select Installation Observe that the Installation dialog box opens This dialog box contains a number of pages selected from the menu on the left side 4 On the left side of the Installation dialog box select Sensor Installation 5 Select PI50 to import information from a catch monitoring system 6 Select the port you wish to use serial or LAN 7 If you want to check the communication ...

Page 241: ...terface to work the communication parameters must be set up correctly Prerequisites This procedure assumes that You have a vacant interface port on your Processor Unit You are familiar with NMEA and other relevant datagram formats You know how to set up the parameters for serial and local area network LAN communication The interface port is set up with the correct communication parameters The EK80...

Page 242: ... the Setup menu select Installation Observe that the Installation dialog box opens This dialog box contains a number of pages selected from the menu on the left side 4 On the left side of the Installation dialog box select Sensor Installation 5 Select ITI FS to import information from a trawl system 6 Select the port you wish to use serial or LAN 7 If you want to check the communication parameters...

Page 243: ... unit MRU The information from a motion reference unit MRU normally heave roll and pitch information is imported into the EK80 to increase the accuracy of the echo data Prerequisites This procedure assumes that You have a vacant interface port on your Processor Unit You are familiar with NMEA and other relevant datagram formats You know how to set up the parameters for serial and local area networ...

Page 244: ...ntroduce some latency They may also introduce be jitter in the communication The amount of jitter depends on the quality of the converter 2 Open the Setup menu 3 On the Setup menu select Installation Observe that the Installation dialog box opens This dialog box contains a number of pages selected from the menu on the left side 4 On the left side of the Installation dialog box select Sensor Instal...

Page 245: ...cated ahead of the ship origin b Select the offset value on the Y axis athwartship from the Ship Origin Adjust with a positive value for Y if the sensor is located on the starboard side of the ship origin c Select the offset value on the Z axis vertical from the Ship Origin Adjust with a positive value for Z if the sensor is located under the ship origin 13 Select Add to save the new sensor interf...

Page 246: ...or to an available serial communication port on your Processor Unit This is described in the Cable layout and interconnections chapter Observe the applicable requirements related to cabling Make sure that the total length of the serial line cable does not exceed approximately 50 meters If a longer cable is required you may need to use buffer amplifiers If the Processor Unit is not fitted with a su...

Page 247: ...specify a dedicated talker ID 12 Select Add to save the new sensor interface you have defined The sensor interface is added to the Installed Sensors list on the Sensor Installation page 13 Select Apply and then Close to save all the parameters and close the Installation dialog box Related topics Interfacing peripheral equipment page 228 Setting up depth output to an external system The EK80 can ex...

Page 248: ...roduce be jitter in the communication The amount of jitter depends on the quality of the converter 2 Open the Operation menu 3 Select Output Observe that the Output dialog box opens This dialog box contains a number of pages selected from the menu on the left side 4 On the left side of the Outputs dialog box select I O Setup Observe that the I O Setup page opens 5 Observe that the available serial...

Page 249: ...ta and one for outgoing messages Tx Data Use these boxes and your knowledge of the data communication to investigate the datagrams The Port Monitor dialog box is a tool for debugging purposes It is neither required nor intended for normal operation of the EK80 11 Select Apply and then Close to save all the parameters and close the Output dialog box Related topics Interfacing peripheral equipment p...

Page 250: ...of the serial line cable does not exceed approximately 50 meters If a longer cable is required you may need to use buffer amplifiers If the Processor Unit is not fitted with a suitable serial line connector use a USB to serial converter Several types are commercially available Note that most USB to serial converters will introduce some latency They may also introduce be jitter in the communication...

Page 251: ...our EK80 must be active and transmitting information to the peripheral system The Port Monitor dialog box provides one text box for incoming messages Rx Data and one for outgoing messages Tx Data Use these boxes and your knowledge of the data communication to investigate the datagrams The Port Monitor dialog box is a tool for debugging purposes It is neither required nor intended for normal operat...

Page 252: ...fers an Auxiliary port that can be used for synchronisation purposes This synchronization method may be more stable that the traditional CTS RTS connection to a serial port The Synchronization Delay functionality is unavailable if you use the Auxiliary port on your Wide Band Transceiver WBT to synchronize the EK80 When you work in the Installation dialog box you must always select Apply to save th...

Page 253: ...he Synchronization Delay setting is not applicable when synchronization is switched off Master Master mode is used if the EK80 is going to act as the controlling unit in a synchronized system The peripheral hydroacoustic system s are only permitted to transmit when enabled by the EK80 When Master mode is selected the EK80 will run using its internal ping interval parameters and send trigger signal...

Page 254: ...n signals It must be an RS 232 serial port Since the synchronization function only uses the Request To Send RTS and Clear To Send CTS signals on a serial port you can use a port that is already used for other purposes For the same reason you do not need to define any baud rate 9 At the bottom of the page select Apply to save your settings 10 Continue your work in the Installation dialog box or sel...

Page 255: ...er 5 6 7 Signal Digital ground Not used Not used The parameters on the Synchronization page allow you to choose which communication port to use for the physical connection to the external system and which synchronization mode to use The Synchronization page is located in the Installation dialog box on the Setup menu Note If you use more than one Wide Band Transceiver WBT in your EK80 system all sy...

Page 256: ...t for example an echo sounder or sonar or even a dedicated synchronization system 8 At the bottom of the page select Apply to save your settings 9 Continue your work in the Installation dialog box or select OK to close it Related topics Setting up the EK80 in a synchronized system page 126 Cable layout and interconnections page 85 Interfacing peripheral equipment page 228 Setting up the interface ...

Page 257: ... page a Select the Local IP Address This is the Internet Protocol IP address of the Ethernet interface adapter located in your Processor Unit b Keep the present value in Local Port 4 Select Remote Control then Application Information to open the page 5 Provide relevant application information 6 At the bottom of the page select Apply to save your settings 7 Select OK to close the dialog box Related...

Page 258: ...age 261 Verifying the communication with the course gyro page 263 Verifying the communication with a navigation system GPS page 265 Verifying the communication with speed log page 267 Verifying the communication with the motion reference unit MRU page 269 Verifying the communication with a synchronization system page 271 Making a noise speed curve to determine vessel noise page 273 Simrad EK80 Ins...

Page 259: ...d if it transmits in open air Procedure 1 Make sure that the EK80 units have been set up to operate with the supply voltage you have available 2 Make sure that the transducer cables are not installed close to power cables 3 Turn all EK80 system units on 4 Make sure that the power LED on the Wide Band Transceiver WBT is lit 5 On the Processor Unit desktop double click the EK80 icon to start the pro...

Page 260: ...ducer and operating frequency a On the left side of the Installation dialog box select Transceiver b Make sure that all applicable transceivers and transducers are connected and operational c For each transceiver this is indicated by the green label with text Installed 9 Open the Operation menu 10 Set Operation to Normal 11 Set Range to Auto 12 Make sure that you can see the seafloor in each echog...

Page 261: ...ve operating mode Low noise is a key factor for high quality and reliable measurements The performance of the EK80 will always be limited by different noise sources The noise is measured while the EK80 operates in Passive mode with the transmit pulses disabled Prerequisites The EK80 hardware units are installed as specified in this manual The EK80 system is turned on and operates normally Caution ...

Page 262: ...from other vessels dockyard workers or machinery will cause unreliable test results If you do this tests in a busy harbour or with noise sources present the sensitive receivers will detect all the noise in the nearby waters Neither tools nor instruments are required Context It is essential that the noise signature is as low as possible Your EK80 must be set to Passive mode Procedure 1 To select Pa...

Page 263: ...quirements Results The noise levels are recorded Date and signature Related topics Test procedures page 256 Reading the transceiver hardware and software versions The firmware and software versions in use by each transceiver are required for a unique identification of the EK80 system at the time of the test The Transceiver Installation page in the EK80 user interface contains all relevant informat...

Page 264: ...ect Installation Observe that the Installation dialog box opens This dialog box contains a number of pages selected from the menu on the left side 3 On the left side select Transceiver 4 Make sure that all applicable transceivers and transducers are connected and operational For each transceiver this is indicated by the green label with text Installed 5 Repeat this cycle for each Wide Band Transce...

Page 265: ...a communication port on the EK80 The sensor is turned on and in normal operation The interface port is set up with the correct communication parameters You are familiar with NMEA and other relevant datagram formats You know how to set up the parameters for serial and local area network LAN communication All relevant vessel drawings installation reports and or measurement results are available The ...

Page 266: ...enu on the left side 3 On the left side of the Installation dialog box select Sensor Installation a Select the relevant sensor in the Installed Sensors list b Make sure that the correct installation parameters are used for the sensor 4 On the left side of the Installation dialog box select Sensor Configuration a Select the relevant sensor in the Sensor list b Make sure that the correct parameters ...

Page 267: ...evant datagram formats You know how to set up the parameters for serial and local area network LAN communication All relevant vessel drawings installation reports and or measurement results are available The EK80 system is turned on and operates normally The vessel is berthed or at sea Neither tools nor instruments are required For connections and communication parameters see the relevant end user...

Page 268: ...eft side of the Installation dialog box select Sensor Installation a Select the relevant sensor in the Installed Sensors list b Make sure that the correct installation parameters are used for the sensor 4 On the left side of the Installation dialog box select Sensor Configuration a Select the relevant sensor in the Sensor list b Make sure that the correct parameters are used for sensor configurati...

Page 269: ...nual The sensor is connected to a communication port on the EK80 The sensor is turned on and in normal operation The interface port is set up with the correct communication parameters You are familiar with NMEA and other relevant datagram formats You know how to set up the parameters for serial and local area network LAN communication All relevant vessel drawings installation reports and or measur...

Page 270: ...enu on the left side 3 On the left side of the Installation dialog box select Sensor Installation a Select the relevant sensor in the Installed Sensors list b Make sure that the correct installation parameters are used for the sensor 4 On the left side of the Installation dialog box select Sensor Configuration a Select the relevant sensor in the Sensor list b Make sure that the correct parameters ...

Page 271: ...n the EK80 The sensor is turned on and in normal operation The interface port is set up with the correct communication parameters You are familiar with NMEA and other relevant datagram formats You know how to set up the parameters for serial and local area network LAN communication All relevant vessel drawings installation reports and or measurement results are available The EK80 system is turned ...

Page 272: ...llation parameters for the motion sensor offset and rotation are correct The physical location of the sensor X Y and Z offsets must be extracted from the detailed vessel drawings or from the reports provided by the personnel that did the actual installation The information about the installation angles must be extracted from the reports provided by the personnel that did or measured up the actual ...

Page 273: ...quency range You do not need to do this test if the EK80 shall only operate in Standalone mode Prerequisites The EK80 is installed as specified in this manual To make sure that the the interface is functional a relevant synchronization system must be connected to the EK80 The EK80 system is turned on and operates normally For slave operation a remote system for example K Sync or Simrad TU40 must b...

Page 274: ...is connected b On the Setup menu select Installation c Select Synchronization d Record the communication parameters in the result table e Select synchronization mode f Select the synchronization delay g Make sure that the EK80 operates normally when triggered by the remote synchronization system Result Sensor Source system Port Synchronization Requirements Results The external synchronization syst...

Page 275: ...ou must make five measurements for each vessel speed and then calculate the average noise You must measure the noise for each single channel but you can do all these measurements simultaneously Tip If you record all the raw data during the noise test you can repeat the test later using the replay file You may then use more than five noise samples for each vessel speed to make a more accurate curve...

Page 276: ... When all the measurements have been made type the data speed and noise into a spreadsheet to create the curve 6 Save the data using a unique file name that identifies context date time and vessel Attach the data file to the electronic copy of the test report 7 Measure the flow noise versus the vessel speed For each channel a Start raw data recording b Ask the bridge to increase the vessel speed t...

Page 277: ... report Result Speed Noise Speed M1 M2 M3 M4 M5 Average 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Channel Sea state Use this table to record the values Alternatively you can type the values straight into a spreadsheet Make the necessary copies so that you have one table for each channel Speed Flow noise Speed M1 20 18 16 14 12 10 Setting to work ...

Page 278: ...se the EK80 program by selecting Exit on the top bar Context When you do not use the EK80 turn off the display and the Processor Unit If you are not using the EK80 for a long period of time we recommend that you turn off the Wide Band Transceiver WBT Use the on off switch on the power supply or disengage the circuit breakers Procedure 1 Select Exit on the top bar Observe that the EK80 program clos...

Page 279: ...lly 3 Turn off the display If required refer to the instructions provided by the display manufacturer 4 Turn off each transceiver The Wide Band Transceiver WBT is not fitted with an on off switch You can leave the unit permanently turned on If you are not using the EK80 for a long period of time turn off or disconnect the power supply Setting to work ...

Page 280: ...ation has been fully completed and all functional tests have been made to full satisfaction representatives from each party must sign Vessel Customer Place and date Comments Signatures Installation done by Company Position Date and signature Installation accepted by Company Position Date and signature Simrad EK80 Installation Manual ...

Page 281: ...ons page 280 Interface specifications page 281 Power requirements page 292 Weights and outline dimensions page 295 Environmental requirements page 298 Compass safe distance page 301 Minimum computer requirements page 303 Minimum display requirements page 304 Technical specifications ...

Page 282: ...ts several different transceiver units The information is mainly prepared for EK80 installations on a vessel One or more Wide Band Transceiver WBT units are provided For technical specifications about other transceivers supported by the EK80 see the relevant publications Note At Kongsberg Maritime we are continuously working to improve the quality and performance of our products The technical spec...

Page 283: ...m formats for catch monitoring information page 286 Supported datagram formats for sound speed sensors page 287 Supported datagram formats for speed log information page 288 Supported datagram formats for temperature information page 288 Supported datagram formats for water level offset information page 289 Supported formats for processed data to output page 289 Supported formats for processed dat...

Page 284: ...ed relative to the water and over the ground Related topics Interface specifications page 281 Technical specifications page 279 Supported datagram formats for drop keel offset information If your vessel is equipped with a drop keel the operating depth of the transducer face will vary This variation affects the position of the transducer in the vessel s coordinate system To make accurate measuremen...

Page 285: ...ion NMEA GLL The NMEA GLL datagram transfers the latitude and longitude of vessel position the time of the position fix and the current status from a global positioning system GPS NMEA GGA The NMEA GGA datagram transfers time position and fix related data from a global positioning system GPS NMEA GGK The NMEA GGK datagram is used to decode the PTNL Time Position Type and DOP Dilution of Precision ...

Page 286: ...ees magnetic The datagram is no longer recommended for use in new designs It is often replaced by the NMEA HDG telegram NMEA HDG The NMEA HDG datagram provides heading from a magnetic sensor If this reading is corrected for deviation it produces the magnetic heading If it is offset by variation it provides the true heading NMEA THS The NMEA THS datagram provides the true vessel heading The datagra...

Page 287: ...ing and water depth of the trawl sensor as well as its distance from the vessel The bearing resolution is 1 degree The Simrad ITI measures the depth differently from the range and the bearing If the ITI only knows the range and the bearing the depth field is empty Simrad TPT Simrad TPT is a proprietary datagram format created by Kongsberg Maritime to provide the true bearing and water depth of the...

Page 288: ...ed topics Interface specifications page 281 Technical specifications page 279 Supported datagram formats for palette control On some vessels the EK80 is used as an integrated part of a large information system In such cases the host system may offer a common palette control This allows you to select a common colour scheme skin used in all the presentations The EK80 supports the following datagram ...

Page 289: ... the type and configuration of PS and PI sensors used by a Simrad catch monitoring system Related topics Interface specifications page 281 Technical specifications page 279 Supported datagram formats for sound speed sensors The Profile page in the Environment dialog box shows the current sound speed profile You can select a new profile provided by a CTD Conductivity Temperature Depth sensor The EK...

Page 290: ...ram contains multi layer water current data This includes the depth and speed of the current Related topics Interface specifications page 281 Technical specifications page 279 Supported datagram formats for temperature information The navigational information on the top bar may include a read out of the current water temperature If a suitable sensor is connected to the EK80 Processor Unit the top ...

Page 291: ... communication port Use Processed Data to Output to define which processed data formats to export and which communication port to use This page is located in the Output dialog box The following formats are supported XYZ file format This is processed and interpolated xyz data in ASCII format The XYZ datagram is a navigational datagram showing the position and depth of a single channel ZMQ Beam Velo...

Page 292: ...The NMEA VTG datagram contains the actual course and speed relative to the ground CP1 Current Profile The CP1 Current Profile datagram is a proprietary format created by Kongsberg Maritime The datagram exports the velocity of the water current from the seafloor and from a selection of depth layers in the water column Related topics Interface specifications page 281 Technical specifications page 27...

Page 293: ...Council for the Exploration of the Sea EK80 uses the format NetCDF4 where the number refers to the version of the format This version includes groups and subgroups into the format BOT The BOT file format is a proprietary file format designed by Kongsberg Maritime to contain configuration and depth information The BOT data file contains a set of datagrams The datagram sequence is not fixed It depen...

Page 294: ... For more information refer to the end user documentation provided by the manufacturer Related topics Power requirements page 292 Technical specifications page 279 Processor Unit power requirements Model EK80 Processor Unit Enix Voltage requirement 115 230 VAC Single phase Nominal voltage Maximum voltage deviation 15 Maximum transient 20 of nominal voltage recovery time 3 s Power consumption 500 W...

Page 295: ...supply Voltage requirement 115 230 VAC 47 to 63 Hz single phase nominal Maximum voltage deviation 15 Maximum transient 20 of nominal voltage recovery time 3 s Power consumption 100 VA Approximately Related topics Power requirements page 292 Technical specifications page 279 LBG408A R2 Ethernet switch power requirements The technical specifications are those valid for the Ethernet switch that was d...

Page 296: ...To ensure that your information is correct always consult the manufacturer s own documents Related topics Power requirements page 292 Technical specifications page 279 WBT Cabinet power requirements Make and model Simrad WBT Cabinet Power requirements Not applicable Related topics Power requirements page 292 Technical specifications page 279 Simrad EK80 Installation Manual ...

Page 297: ...tured by Kongsberg Maritime For more information refer to the end user documentation provided by the manufacturer Related topics Weights and outline dimensions page 295 Technical specifications page 279 Processor Unit weight and outline dimensions Make and model EK80 Processor Unit Enix Outline dimensions Depth 385 mm Width 479 6 mm Will fit in a 19 rack Height 177 mm Weight 16 kg Approximately Th...

Page 298: ...time as a part of the EK80 delivery For specifications related to a locally purchased Ethernet switch refer to the documentation provided with the unit Manufacturer Black Box Manufacturer s website http www blackbox co uk Make and model Black Box LBG408A R2 Outline dimensions Depth 123 mm Width 228 mm Height 44 mm Weight 0 9 kg Approximately For additional details refer to the technical specificat...

Page 299: ...h 757 mm With shock absorbers Width 607 mm Height 1350 mm With shock absorbers Weight Empty 80 kg Approximately With seven WBT units 150 kg Approximately Related topics Weights and outline dimensions page 295 Technical specifications page 279 400930 WBT Cabinet outline dimensions page 314 Technical specifications ...

Page 300: ...ured by Kongsberg Maritime For more information refer to the end user documentation provided by the manufacturer Related topics Environmental requirements page 298 Technical specifications page 279 Processor Unit environmental requirements Model EK80 Processor Unit Enix Operating temperature 15 to 55 C Storage temperature 20 to 70 C Relative humidity 10 to 95 relative non condensing Certificates I...

Page 301: ...cally purchased Ethernet switch refer to the documentation provided with the unit Manufacturer Black Box Manufacturer s website http www blackbox co uk Make and model Black Box LBG408A R2 Operating temperature 0 to 45 C Storage temperature 20 to 90 C Relative humidity 10 to 90 relative non condensing For additional details refer to the technical specifications provided by the manufacturer Note Thi...

Page 302: ...300 394149 D Related topics Environmental requirements page 298 Technical specifications page 279 Simrad EK80 Installation Manual ...

Page 303: ...ply It is not manufactured by Kongsberg Maritime For more information refer to the end user documentation provided by the manufacturer Related topics Compass safe distance page 301 Technical specifications page 279 Processor Unit compass safe distance Model EK80 Processor Unit Enix Standard compass 200 cm Other compass 140 cm The technical specifications are those valid for the computer that provi...

Page 304: ...ns related to a locally purchased Ethernet switch refer to the documentation provided with the unit Manufacturer Black Box Manufacturer s website http www blackbox co uk Make and model Black Box LBG408A R2 Standard compass Not specified For additional details refer to the technical specifications provided by the manufacturer Note This information was copied from the manufacturer s documentation To...

Page 305: ...ts and cables and a safe installation A laptop computer may be used as long as it meets the functional and technical requirements The minimum technical requirements are Processor Intel I7 or better An equivalent type from another manufacturer can also be used Memory minimum capacity 4 GB Hard disk If you wish to record large amounts of EK80 data make sure that you have enough space on your hard di...

Page 306: ...twork LAN The Ethernet adapter communicating with the Wide Band Transceiver WBT must offer a Receive Buffers function This parameter must be set to its maximum value if more than one Wide Band Transceiver WBT is used Related topics Technical specifications page 279 Minimum display requirements Unless specifically ordered the EK80 is not provided with a display The display must then be purchased lo...

Page 307: ...t may offer video output on several formats Investigate your options before you purchase a display Physical screen size The screen size depends on personal and or operational preferences The EK80 software supports 16 9 displays Tip If you use the EK80 with many transceivers you may find it useful with a large high resolution display Related topics Technical specifications page 279 Technical specif...

Page 308: ...drawing file page 307 388697 Wide Band Transceiver WBT outline dimensions page 308 385609 Processor Unit dimensions page 310 400930 WBT Cabinet outline dimensions page 314 201575 Transducer connector assembly and wiring page 318 Simrad EK80 Installation Manual ...

Page 309: ...nd documents are not available from our website These can be downloaded from the Simrad Dealer Club https www kongsberg com sdc The installation shipyard must provide all necessary design and installation drawings as well as the relevant work standards and mounting procedures If required all documents provided by the shipyard for the physical installation of the EK80 must be approved by the vessel...

Page 310: ...308 394149 D 388697 Wide Band Transceiver WBT outline dimensions Download the source drawing from the EK80 pages on https www kongsberg com sim rad Simrad EK80 Installation Manual ...

Page 311: ...394149 D 309 Related topics Drawing file page 306 Simrad EK80 page 13 Installing the EK80 hardware units page 64 Technical specifications page 279 Drawing file ...

Page 312: ...310 394149 D 385609 Processor Unit dimensions Download the source drawing from the EK80 pages on https www kongsberg com sim rad Simrad EK80 Installation Manual ...

Page 313: ...394149 D 311 Drawing file ...

Page 314: ...312 394149 D Simrad EK80 Installation Manual ...

Page 315: ...394149 D 313 Related topics Drawing file page 306 Simrad EK80 page 13 Installing the EK80 hardware units page 64 Technical specifications page 279 Drawing file ...

Page 316: ...314 394149 D 400930 WBT Cabinet outline dimensions Download the source drawing from the EK80 pages on https www kongsberg com sim rad Simrad EK80 Installation Manual ...

Page 317: ...394149 D 315 Drawing file ...

Page 318: ...316 394149 D Simrad EK80 Installation Manual ...

Page 319: ...394149 D 317 Related topics Drawing file page 306 Simrad EK80 page 13 Installing the EK80 hardware units page 64 Technical specifications page 279 Drawing file ...

Page 320: ...318 394149 D 201575 Transducer connector assembly and wiring Simrad EK80 Installation Manual ...

Page 321: ...394149 D 319 Related topics Drawing file page 306 Simrad EK80 page 13 Installing the EK80 hardware units page 64 Technical specifications page 279 Drawing file ...

Page 322: ...ase box is used to describe all kinds of cases wooden or cardboard boxes etc used to hold the unit Topics Transporting Kongsberg Maritime equipment page 321 Lifting units and transportation boxes page 322 Inspection of units and transportation boxes after arrival page 323 Specifications for storage prior to installation or use page 324 Unpacking instructions page 325 Specifications for storage aft...

Page 323: ...lations must be investigated by the packer shipper before the unit is dispatched Procedure 1 Ensure that all local transportation is done according to the same specifications as for the initial delivery 2 Make sure that the box containing the unit is kept dry at all times and sheltered from the weather It must not be subjected to shocks excessive vibration or other rough handling The box will norm...

Page 324: ...r unit before you attempt to lift it 2 Make sure that you have the relevant lifting apparatus required and that this equipment is approved and certified for the load 3 If you need to use a crane a Check the applicable weight certificate for the crane b Check the security of the lifting lugs c If the unit to be lifted is provided with dedicated lifting lugs make sure that all available lugs are use...

Page 325: ...xes plastic bags and or pallets for physical damage Look for signs of dropping immersion in water or other mishandling 2 If external damage is detected open the box to check its contents Request that a representative of the carrier to be present while the box is opened so any transportation damage can be identified and documented 3 If a unit has been damaged prepare an inspection report stating th...

Page 326: ... a unit is damaged prepare an inspection report stating the condition of the unit and the actions taken Describe the damage and collect photographic evidence if possible Re preserve the equipment b If the unit is not damaged check the humidity absorbing material If required dry or replace the bags then re pack the unit according to the packing instructions 7 If a box has been opened make sure that...

Page 327: ...rotection the box to be used for storage and transportation must be lined on all walls base and lid using minimum 5 cm thick polyurethane or polystyrene foam Most system units can normally be stored in temperatures between 30 C and 70 C Refer to the relevant technical specifications for details Note Unless otherwise specified transducers and hydrophones must not be stored in temperatures below 10 ...

Page 328: ...tive of the carrier to be present while the box is opened so any transportation damage can be identified and documented 3 If a unit has been damaged prepare an inspection report stating the condition of the unit and actions taken Describe the damage and collect photographic evidence if possible Return the inspection report to Kongsberg Maritime as soon as possible 2 Place the box on a stable work ...

Page 329: ...actions may damage the transducer beyond repair Observe these transducer handling rules Do not activate the transducer when it is out of the water Do not lift the transducer by the cable Do not step on the transducer cable Do not handle the transducer roughly Avoid impacts Do not expose the transducer to direct sunlight or excessive heat Do not use high pressure water sandblasting metal tools or s...

Page 330: ...t boards and other electronic units will always be wrapped in a clear plastic protective bag and the bag will be sealed Procedure 1 Lift the unit in its protective bag out of the transport box Note You must never use the cables to lift or carry a unit 2 Place it in a stable position on the floor or on the workbench 3 Inspect the unit for damage a If a unit has been damaged prepare an inspection re...

Page 331: ... transducer must always be handled as a delicate instrument Incorrect actions may damage the transducer beyond repair Observe these transducer handling rules Do not activate the transducer when it is out of the water Do not lift the transducer by the cable Do not step on the transducer cable Do not handle the transducer roughly Avoid impacts Do not expose the transducer to direct sunlight or exces...

Page 332: ...re the unit was packed These must then be reconnected during the installation procedure Units containing batteries are marked Caution Units containing lithium or alkaline batteries must be handled separately and with care Such units are marked accordingly Do not attempt to recharge such batteries open them or dispose of them by incineration Refer to the applicable product data sheets or battery ha...

Page 333: ...394149 D 331 Note Unless otherwise specified transducers and hydrophones must not be stored in temperatures below 10 C and above 50 C Equipment handling ...

Page 334: ...ents of global positioning system 181 dimensional survey measurements of heading sensor 181 dimensional survey measurements of motion reference unit 181 dimensional survey measurements of transducer 181 acoustic noise about 54 ambient noise 58 bow thrusters 51 cavitation 48 51 57 contributing factors 54 electrical noise 56 59 fishing gear noise 59 flow noise 48 57 installation requirements 38 inte...

Page 335: ...e terminations 169 cable trays 167 grounding 169 identification 170 physical protection 168 radio frequency interference 168 cable sealing multi diameter 174 cable specifications RS 232 140 141 RS 422 142 serial line used for synchronization 143 cable terminations requirements 169 cable trays requirements 167 cables about cable glands 170 connection requirements 169 grounding requirements 169 iden...

Page 336: ...imensions drawing 310 overview 20 power requirements 292 purpose 20 required item 28 scope of supply 28 visual inspection 192 weight 295 conduit steel minimum dimensions 105 transducer cables 105 conduits cable requirements 167 configuring sensor interface 234 connect transducer cable to the transceiver 154 156 159 connection Ethernet cable 147 RS 232 serial cable 140 141 RS 422 serial cable 142 R...

Page 337: ...ring depth and distance 285 TSS1 motion data 286 VBW vessel speed 288 290 VHW vessel heading and speed 288 290 VLW travelled distance 282 VTG time date position and course 283 288 290 ZDA day month year and local time zone 283 ZMQ Beam velocity 289 datagram formats annotation data 281 catch monitoring information 286 depth information 283 distance information 282 drop keel information 282 gyro inf...

Page 338: ...d com 12 DPT datagram format 283 289 drawing ac power cable 137 computer outline dimensions 310 dc power cable 148 Ethernet cable RJ45 147 Moxa CP114EL I serial adapter 114 145 Øverland UPC 3005 Serial line splitter 121 Øverland UPC 5000P Serial line splitter 125 Processor Unit outline dimensions 310 RS 232 serial line cable 140 141 RS 422 serial line cable 142 RS 485 serial line cable 144 serial ...

Page 339: ... preferences for data recording 226 formats processed data to file 290 processed data to output 289 functional diagram 17 Furuno GPhve datagram format 286 G general requirements supply power 37 general safety rules 36 GGA datagram format 283 GGK datagram format 283 GLL datagram format 283 global positioning system accuracy requirements for dimensional survey measurements 181 interface requirements...

Page 340: ...e a noise speed curve to determine vessel noise 273 measure noise in passive mode 259 mount the drawers in the WBT Cabinet 81 mount the WBT Cabinet 78 obtain and install the software license 203 prepare a cable for termination 171 secure and terminate a cable 173 select measurement units 225 select menu language 224 set to work 186 set up summary 199 set up depth output 245 set up synchronization ...

Page 341: ...assification society 39 cables and wiring 38 compass deviation 38 dry docking 39 environmental 298 humidity 298 noise sources 38 temperature 298 uninterruptible power supply 37 installing WBT Cabinet 78 WBT Cabinet drawers 81 instructions installation 11 unpacking 325 interconnection cables list 94 interface motion reference unit MRU setup 241 setting up depth output 245 setting up GPS interface 2...

Page 342: ...tting up synchronization 131 249 synchronization mode 127 measurement units selecting 225 measuring noise in passive mode 259 mechanical drawings about 307 download 46 mechanical unit unpacking 327 menu language select 224 minimize effect boundary water layer 50 minimum dimensions steel conduit 105 minimum requirements computer 303 display 304 steel conduit 105 uninterruptible power supply 35 mode...

Page 343: ... RMC time date position course 283 THS true heading 284 VBW vessel speed 288 290 VHW vessel heading and speed 288 290 VLW travelled distance 282 VTG time date position and course 283 288 290 ZDA day month year and local time zone 283 NMEA datagrams gyro information 284 heading information 284 NMEA DBS datagram format 289 NMEA DBT datagram format 289 NMEA DDC datagram format 286 NMEA DPT datagram f...

Page 344: ...erial line splitter 125 Processor Unit 310 output setting up depth output 245 Øverland UPC 3005 connections 120 description 118 outline dimensions drawing 121 technical specifications 119 Øverland UPC 5000P connections 124 description 122 outline dimensions drawing 125 technical specifications 123 overview computer 20 display 19 Ethernet switch 21 installation tasks 44 Processor Unit 20 transceive...

Page 345: ...aring a cable for termination 171 securing and terminating a cable 173 selecting measurement units 225 selecting menu language 224 setting to work 186 setting up depth output 245 setting up summary 199 setting up synchronization 131 249 setting up the catch sensor interface 237 setting up the GPS interface 232 setting up the motion reference unit MRU interface 241 setting up the navigation sensor ...

Page 346: ...aw data recording 226 reminder before you power up 14 important 14 support if something breaks down 14 when the system not in use 14 when you are docking your vessel 14 when you wish to switch off 14 Request To Send used in synchronization 143 Request To Send RTS synchronization using Clear To Send CTS and Request To Send RTS signals 129 required item computer 28 display 27 Ethernet switch 29 moti...

Page 347: ...r 34 speed log 33 transducer 28 uninterruptible power supply 35 screen resolution adjusting 212 securing cable 173 security network 40 selecting measurement units 225 self noise acoustic noise 56 sensor configuring 234 Sensor Configuration page configuring the sensor interface 234 Sensor Installation page installing navigation and other sensors summary 228 interfacing a navigation sensor 232 seria...

Page 348: ...al line cable 144 serial line used for synchronization 143 storage after unpacking 330 storage prior to installation 324 technical 280 vessel ground cable 139 weight 295 speed information datagram formats 288 speed log interface requirements 33 optional item 33 recommended item 33 scope of supply 33 verifying the interface 267 splicing transducer cable 107 standalone synchronization mode 127 stand...

Page 349: ...stance 301 outline dimensions 295 Øverland UPC 3005 Serial line splitter 119 Øverland UPC 5000P Serial line splitter 123 weight 295 technical support offices 41 Teledyne TSS1 datagram format 286 temperature requirements 298 temperature information datagram formats 288 termination cable 173 preparing cable 171 terminations cable requirements 169 this manual purpose 11 target audience 11 THS datagra...

Page 350: ...r head 329 a transducer 329 an electronic or electromechanical unit 328 instructions 325 standard parts and units 326 UPC 3005 connections 120 description 118 outline dimensions drawing 121 technical specifications 119 UPC 5000P connections 124 description 122 outline dimensions drawing 125 technical specifications 123 UPS installation requirements 37 minimum requirements 35 optional item 35 recom...

Page 351: ...et 297 Wide Band Transceiver WBT 296 when not in use important reminder 14 Wide Band Transceiver synchronisation using Auxiliary port 134 252 Wide Band Transceiver WBT cable plan 90 92 compass safe distance 301 connectors 104 description 21 environmental requirements 299 installation 65 67 introduction 21 outline dimensions 296 308 overview 21 power requirements 293 power supply installation 69 pu...

Page 352: ... 2020 Kongsberg Maritime ISBN 978 82 8066 182 1 ...

Page 353: ......

Page 354: ...Installation Manual Simrad EK80 ...

Reviews: