D.5
Start Permit Led is not OK (F0025)
NOTE! When the elevator runs, the voltage is normally 0V and Start Permit Led is ON. When the
elevator is standing, the voltage is normally 230VAC and Start Permit Led is OFF.
Step
Check
Possible cause
Action
1
When the Start
Permit Led is ON
and the elevator is
standing at a floor,
the voltage measured at XD1
pin 3 on LCE230 / LCEADO
board is 0V?
Proceed to Step 1a.
a
The voltage at the
V3F16L/XS3 pin 3 is
230VAC?
Defective cable between XD1
and XS3 or loose connection.
Ensure that cable pins
make contact.
Replace the cable if it
is defective.
b
The voltage at the
V3F16L/XS3 pin 3 is
also 0V?
The problem is in the drive side.
Replace the defective
V3F16L.
2
When the Start
Permit Led is ON
and the elevator is
standing at a floor,
the voltage measured between
XD1 pin 3 is 230VAC?
Defective or loose flat cable
between LCE230 / LCEADO
and LCECPUnc, defective
LCE230 / LCEADO or
LCECPUnc.
Replace the defective
component.
3
When the Start
Permit Led is OFF
and the elevator is
standing at a floor,
the voltage measured between
XD1 pin 3 is 0V?
Defective or loose flat cable
between LCE230 / LCEADO
and LCECPUnc, defective
LCE230, LCEADO or
LCECPUnc.
Replace the defective
component.