background image

DOMEKT REGO

 

200VE(W)-B(K)

Series Air Handling Units Installation

 and Maintenance Service Manual

EN

Summary of Contents for DOMEKT ReGO 200VE-B

Page 1: ...DOMEKT ReGO 200VE W B K Series Air Handling Units Installation and Maintenance Service Manual EN ...

Page 2: ...ed collection point or to an authorised collection site for recycling waste electrical and electronic equipment EEE Improper handling of this type of waste could have a possible negative impact on the environment and human health due to potentially hazardous substances that are generally associated with EEE At the same time your cooperation in the correct disposal of this product will contribute t...

Page 3: ...d be carried out only in conformity with the instruc tions specified herein below If main cable is damaged only manufacturer service team or trained technician must change it in order to avoid accidents Transportation The air handling units are ready for transit and storage 1 a b Pictures The unit is packed to prevent damage of the external and internal parts of the unit dust and moisture penetrat...

Page 4: ...transit and the advice note checked to ensure that all items have been received If damage or delivery shortages are discovered the carrier should be immediately informed AMALVA should be notified within three days of receipt with a written confirmation sent within seven days AMALVA can accept no responsibility for damage by unloading from carrier or for subsequent damage on site If the unit is not...

Page 5: ...REGO 200VE W is equipped with a rotary heat exchanger air filters an electric air heater fans and automation control system to ensure safe and efficient operation of the unit Before you open the door the unit must be switched off and the fans must have been given time to stop up to 3 minutes The unit contains heating elements that must not be touched when they are hot To maintain a good indoor cli...

Page 6: ...n the units of left inspec tion side To have the unit of right inspection side it is necessary replace position of the doors due to hanging the furniture or decorative panel see picture 6 Inslallation of kitchen hood Air handling unit is mounted on the kitchen hood Kitchen hood 1 REGO 200VE W 2 Kitchen hood 3 Screw for hood connection srew M4x16 base in set of unit 4 Picture 5 Picture We reserve t...

Page 7: ...furniture or decorative panel Marking Description REGO 200VE W BK AC EC C4 F pcs 1 Wall plug KWP nylon 8x50 screw 4 5x50 5 2 REGO 200VE 00 014 Mounting bracket 1 3 REGO 200VE 00 011 Unit bracket 1 4 Self tapping screw 4 2x13 16 5 Wall plug KWP nylon 6x35 screw 3 5x35 2 6 Bracket for front cover 4260 2 293 Z AGVA 4 7 Screw 2 5x16 ZnG with cone head 16 8 Screw M4x16 for kitchen hood connection 4 ...

Page 8: ...escription REGO 200VE W B AC EC C4 F pcs 1 REGO 200VE 00 014 Mounting bracket 1 2 Wall plug KWP nylon 8x50 screw 9 3 REGO 200VE 00 011 Unit bracket 1 4 Self tapping screw 4 2x13 16 5 REGO 200VE 00 015 Bracket 1 6 REGO 200VE 00 016 Bracket 1 7 M6 DIN 125 A Washer 6 8 M 4x16 DIN 7985 Screw 9 Bracket for front cover 4260 2 293 Z AGVA 2 10 Screw 2 5x16 ZnG with cone head 16 7 Picture 2 1 3 4 7 5 8 7 9...

Page 9: ...serve the right to make changes without prior notice The dimensions of suspended furniture panel The dimensions of the place of the REGO 200VE W suspended 9 a Picture 140 140x4 560 575 600 22 625 600 500 250 22 32 5 500 250 32 5 O 2 d e p t h 5 m m 1 6 h o l e s ...

Page 10: ...e It is recommended to carry out routine maintenance of the air handling unit KOMFOVENT DOMEKT REGO 200VE W 3 4 times per year All components inside the unit are easily detachable for cleaning Don t forget to unplug the cables out of electric components and unscrew bolts from electric heater and rotary heat exchanger Unscrew Installation and Maintenance Service Manual 10 b Picture We reserve the r...

Page 11: ...because wrong direction of turns gives only 30 of rating Check if fan freely rotates and is not mechanically damaged if impeller does not touch suction nozzles fan does not spread noise the pressure tubes are connected to the nozzle if required mounting bolts are screwed 3 Air heater check Recommended to perform periodical inspection and cleaning of heater Check the plates of water air heater The ...

Page 12: ...8000 dB A Supply air flow into air ducts Intake 55 52 50 50 50 47 43 38 54 1 Supply 60 62 63 61 60 58 54 50 65 0 Exhaust air flow into air ducts Extract 55 52 50 50 50 48 43 38 54 3 Exhaust 60 62 63 61 60 58 54 50 65 0 Kitchen hood connection 58 57 55 55 56 54 51 47 60 5 Bathroom connection 59 59 59 58 58 56 52 48 62 7 Surrounding 3 m distance 52 53 51 44 37 32 27 23 46 5 For AHU REGO 200VW B soun...

Page 13: ...We reserve the right to make changes without prior notice REGO 200VE W B AC Performance REGO 200VE W B EC Performance Correction factor for REGO 200VW 25Pa Static pressure Pa Air volume m3 h Fan power W Static pressure Pa Fan power W Air volume m3 h ...

Page 14: ...th sides of the unit Ordering Key REGO 200 V E W B K AC C4 F Filter class F5 or F7 Controller type С4 Motor type AC alternating current EC electronically commutated Kitchen hood By pass Air heater W water E electric Version vertical Size shows nominal air flow AHU type REGO with rotary heat exchanger 92 136 320 81 145 148 145 600 660 625 160 300 125 125 5x ...

Page 15: ...UAB Amalva Ozo str 10 LT 08200 Vilnius Lithuania e mail info amalva lt www amalva com www kofovent com 2012 ...