C6-17-08
UAB AMALVA we reserve the right to make changes without prior notice
21
1. ELECTRICAL INSTALLATION INSTRUCTIONS
The installation can only be performed by qualified personnel. It is necessary to follow the requirements below
during the installation.
It is recommended to lay the control cables separately from the power
cables, at a minimum distance of 20 cm.
The connector connection is performed strictly according to the wiring
diagram numbering, or with adequate markings (see the principal wiring
diagram of the unit).
When removing the unit parts, do not pull on the connecting wires and
cables!
Before performing any work inside the equipment, make sure that the air
handling is switched off and disconnected from the mains power supply.
1.1. Power supply connection
The unit is designed for a supply voltage of 230 V AC, or 50 Hz; therefore, you must install a socket with an
earthing of the corresponding capacity next to it (see the wiring diagram). The power cable type is indicated in
the wiring diagram.
The unit must be connected to the stationary installation using a 16 A
circuit breaker with 300 mA current leakage protection (type B or B+).
The air handling unit is designed to connect only to a neat outlet, with
protective grounding meeting all the electrical safety requirements.
1.2. Control panel installation
1. The control panel must be installed in the premises under the following conditions:
• at an ambient temperature of 0 °C... 40 °C;
• relative humidity ranging from 20%... 80 %;
• protection from accidentally vertically falling water drops (IP X2).
2. Control panel connection through the hole in the back or in the bottom.
3. The control panel can be mounted on a flush mounting box or in any other place, simply by screwing it to
the surface through the two holes on the fastening surface.
4. The control panel is connected to the controller box. The length of installation cable for the control panel
may not exceed 150 m.
Control panel connection
Yellow (A)
( ) White
(+) Red
Green (B)
Yellow (A)
(+) Red
Green (B)
( ) White
Yellow (A)
( ) White
(+) Red
Green (B)
Yellow (A)
(+) Red
Green (B)
( ) White
The cable thicknesses for the panel connection and others are specified
in the wiring diagram!
Remove protective screen tape, before mounting front cover on the con
-
trol panel!