2.7 Trouble shooting
Depending on the conditions in your installation, there may be a wide variety of reasons for the fault. In multi-axis
systems there may be further hidden causes of a fault.
Detailled hints for removal of faults can be found in the
chapter "Trouble-Shoot-
ing". Our customer service can give you further assistance with problems.
Fault
Possible causes
Measures to remove the cause of
the fault
HMI message:
communication
fault
wrong cable used
cable plugged into wrong position in
servo amplifier or PC
wrong PC interface selected
use null-modem cable
plug cable into the correct sockets on the
servo amplifier and PC
select correct interface
Motor does not
rotate
servo amplifier not enabled
break in setpoint cable
motor phases swapped
brake not released
drive is mechanically blocked
no. of motor poles set incorrectly
feedback set up incorrectly
apply enable signal
check setpoint cable
correct motor phase sequence
check brake control
check mechanism
set no. of motor poles
set up feedback correctly
Motor oscil-
lates
gain too high (speed controller)
shielding in feedback cable is broken
AGND not wired up
reduce Kp (speed controller)
replace feedback cable
join AGND to CNC-GND
Drive reports
following error
I
rms
or I
peak
is set to low
setpoint ramp is too long
increase I
rms
or I
peak
(keep within motor lim-
its!)
shorten setpoint ramp +/-
Motor over-
heating
I
rms
/I
peak
set too high
reduce I
rms
/I
peak
Drive too soft
Kp (speed controller) too low
Tn (speed controller) too high
ARLPF / ARHPF too high
ARLP2 too high
increase Kp (speed controller)
use motor default value for Tn (speed con-
troller)
reduce ARLPF / ARHPF
reduce ARLP2
Drive runs
roughly
Kp (speed controller) too high
Tn (speed controller) too low
ARLPF / ARHPF too low
ARLP2 too low
reduce Kp (speed controller)
use motor default value for Tn (speed con-
troller)
increase ARLPF / ARHPF
increase ARLP2
Axis drifts at
setpoint = 0V
offset not correctly adjusted for ana-
log setpoint provision
AGND not joined to the CNC-GND of
the controls
adjust setpoint-offset (analog I/O)
join AGND and CNC-GND
S300 Safety Guide | 2 English
Kollmorgen | wiki-kollmorgen.eu | December 2015
57
Summary of Contents for SERVOSTAR 300
Page 30: ...S300 Safety Guide 1 Deutsch 30 Kollmorgen wiki kollmorgen eu December 2015...
Page 58: ...S300 Safety Guide 2 English 58 Kollmorgen wiki kollmorgen eu December 2015...
Page 86: ...S300 Safety Guide 3 Fran ais 86 Kollmorgen wiki kollmorgen eu December 2015...
Page 114: ...S300 Safety Guide 4 Italiano 114 Kollmorgen wiki kollmorgen eu December 2015...
Page 117: ...5 1 2 PDF 5 1 3 Symbol S300 Safety Guide 5 Kollmorgen wiki kollmorgen eu December 2015 117...
Page 122: ...S300 Safety Guide 5 5 2 3 UN 230 B S300 122 Kollmorgen wiki kollmorgen eu December 2015...
Page 126: ...S300 Safety Guide 5 5 3 2 SERVOSTAR 300 126 Kollmorgen wiki kollmorgen eu December 2015...
Page 139: ...5 6 3 3 S300 Safety Guide 5 Kollmorgen wiki kollmorgen eu December 2015 139...
Page 153: ...S300 Safety Guide Kollmorgen wiki kollmorgen eu December 2015 153...