8.6.2 Auxiliary voltage power supply 24 VDC (X10)
The following diagram describes external 24 VDC power supply (PELV). The required supply
current rating depends on the use of motor brake (
2 pin, pitch 5.08 mm
T-type mating connector data (
Undervoltage fault limit 19 V
Overvoltage fault limit 30 V
Pin Signal
Description
1
+ 24 V
+24 VDC supply voltage, PELV
2
GND
Ground for 24 VDC supply voltage, PELV
24 V supply (PELV)
Units
Input data
Auxiliary voltage supply (PELV)
VDC
24 V (±10%, check voltage drop)
- control current without motor brake
A
< 1
- control current with one motor brake
A
< 3.1
- control current with two motor brakes
A
< 5.2
8.6.2.1 Fusing
Use 24 VDC supply manufacturers recommendation for fusing.
8.6.2.2 Wiring example 24 VDC supply
Maximum current for one string of daisy-chained X10T connectors is 20 A. The sum control
current of connected drives should not extend 20 A. With the data given in the table above,
you can connect for example:
6 single axis drives, or 4 dual axis drives, or 3 2 dual axis drives.
Wiring example with three phase power supply unit:
AKD2G-S Installation Manual, Safety 1 | 8 Electrical Installation
Kollmorgen | kdn.kollmorgen.com | July 2020
75