4.4 Installation, setup and normal operation
Installation and setup information are given in this manual:
Mechanical installation (
Electrical installation (
Setup (
Normal operation tested for environmental class 3K3 according to IEC 61800-2 (
The manufacturer of the machine defines the necessary end user expertise based on the risk
assessment for the machine and describes the requirements for normal operation based on
the application.
4.5 Decommissioning
Only professional staff who are qualified in electrical engineering are allowed to decom-
mission parts of the system.
DANGER
: Lethal Voltages!
There is a danger of serious personal injury or death by electrical shock or electrical arcing.
Switch off the main switch of the switchgear cabinet.
Secure the system against restarting.
Block the main switch.
Wait at least 5 minutes after disconnecting.
4.6 Maintenance and cleaning
The device does not require maintenance, it should be inspected once a year by professional
staff.
Do not immerse or spray the device. Avoid that liquid enters the device. The inside of the
unit can only be cleaned by the manufacturer. Opening the device voids the warranty.
To clean the device exterior:
1. Decommission the device (see chapter 4.5 "Decommissioning").
2. Casing: Clean with Isopropanol or similar cleaning solution.
Caution
: Highly Flammable! Risk of injury by explosion and fire.
Observe the safety notes given on the cleaning liquid package.
Wait at least 30 minutes after cleaning before putting the device back into operation.
3. Protective grill on fan: Clean with a dry brush.
4.7 Disassembly
Only professional staff who are qualified in electrical engineering are allowed to disassemble
parts of the system.
1. Decommission the device (see chapter 4.5 "Decommissioning").
2. Check temperature.
CAUTION
: High Temperature! Risk of minor burns. During operation, the heat sink of
the drive may reach temperatures above 80 °C (176 °F). Before touching the device,
check the temperature and wait until it has cooled below 40 °C (104 °F).
3. Remove the connectors. Disconnect the potential earth connection last.
4. Demount: loosen the fastening screws. Remove the device.
AKD2G-S Installation Manual, Safety 1 | 4 Product life cycle handling
Kollmorgen | kdn.kollmorgen.com | July 2020