AKD Installation | 7 Technical description and data
7.6 Electrical Data AKD-xzzz07
Electrical data
Units
AKD-
x00307
AKD-
x00607
AKD-
x01207
AKD-
x02407
AKD-
x04807
Rated supply voltage (L1/L2/L3)
V
3 x 240 V to 480 V ±10%
Rated supply input frequency
Hz
AC with 50 Hz to 400 Hz ±5% or DC
Rated input power for S1 operation
kVA
2.24
4.49
7.65
15.2
40.9
Rated input current
at 3x240 V
A
2.7
5.4
9.2
18.3
49.3
at 3x400 V
A
2.7
5.4
9.2
18.3
49.3
at 3x480 V
A
2.7
5.4
9.2
18.3
49.3
Permitted switch on/off frequency, mains
1/h
30
Max. inrush current (@480V, 20°C)
A
9
9
9
9
9
Rated DC bus link voltage
(Bus Turn on Delay 3ph 1 sec)
V=
340 to 680
Continuous output current ( ± 3%)
at 240 V
Arms
3
6
12
24
48
at 400 V
Arms
3
6
12
24
48
at 480 V
Arms
3
6
12
24
48
Peak output current (for 5 s, ± 3%)
Arms
9
18
30
48
96
Continuous output power @ rated input current
at 3x240 V
kVA
0.6
1.25
2.5
5
10
at 3x400 V
kVA
1
2
4.2
8.3
16.6
at 3x480 V
kVA
1.2
2.5
5
10
20
Peak output power (for 1 s)
at 3x240 V
kVA
1.8
3.75
6.25
10
20
at 3x400 V
kVA
3
6.75
10.4
16.7
33
at 3x480 V
kVA
3.6
7.5
12.5
20
40
Technical data for regen circuit
—
Motor inductance min.
at 240 V
mH
3.2
1.6
1.3
0.6
0.3
at 400 V
mH
5.3
2.6
2.1
1
0.5
at 480 V
mH
6.3
3.2
2.5
1.2
0.6
Motor inductance max.
mH
600
300
250
120
60
Thermal dissipation, output stage disable
W
max. 20
max. 20
max. 20
max. 25
max. 25
Thermal dissipation at rated current
W
102
129
153
237
640
Noise emission (low speed/high speed
fan)
dB(A)
34/43
34/43
44/52
48/58
48/72
Aux. voltage supply (PELV)
V=
24 V (±10%, check voltage drop)
-current B, P, T types without/with motor
brake
A=
1 / 2.5
1 / 2.5
1 / 2.5
2 / 4
2 / *
-current M type without/with motor brake
A=
1.3 / 2.8
1.3 / 2.8
1.3 / 2.8
2.3 / 4.3
2.3 / *
* = motor holding brake is supplied with separated 24 V ±10% auxiliary voltage (
38