7.4.3 First actions in case of an alarm when the rotor motor has stopped
•
Switch off the main voltage supply upstream of the control unit, wait 10 seconds and switch the
voltage on again. If the motor starts, the motor guard of the control unit had tripped. Make sure that
the exchanger rotates freely.
•
Check the fuse upstream of the control unit.
•
Check the fuse of the control unit.
•
If the motor still does not work, leave further troubleshooting to an expert.
7.4.4 Replacement of drive belt
The rotor is belt driven. The belts loosen during their service life and wear in use. For this reason, we
recommend regular maintenance intervals. If the belt is loose, shorten it by removing a suitable length of the
belt.
If the belt needs to be replaced, we recommend that you contact service. This will ensure the use of the
correct belt and specific installation instructions.
Figure 7.4.4.1: The belt direction is marked on the belt with an arrow.
Figure 7.4.4.2: Ensure that the belt rotates around the motor pulley and rotor as shown.
After installation, the belt rotates 180 degrees as the rotor rotates.